789 Tamarack Way NW - Swimming Pool

789 Tamarack Way NW Edmonton AB T6T0N3 · Aquatic Facility

18 inspections

  1. Risk Management Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample submitted on 9 July 2026 was unsatisfactory: HPC 610 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • the sample 26EN-184E00098 submitted on July 3, 2026, was unsatisfactory: HPC was 110. This was a second consecutive unsatisfactory result.
  2. Risk Management Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample submitted on 9 July 2026 was unsatisfactory: HPC 610 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • the sample 26EN-184E00098 submitted on July 3, 2026, was unsatisfactory: HPC was 110. This was a second consecutive unsatisfactory result.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Floating weir is missing on the skimmer located in the deep end. Skimmer weirs were installed however have been broken. Suggested to staff that they discuss with pool service provider and determine if alternative weirs such as a round weir would be suitable for the make and model of skimmer installed.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Controller pH was 7. 1 and manual was 7.37. pH values were not consistent. Pool service tech is scheduled for weekly onsite service call tomorrow. Follow up and ensure controller is cleaned and calibrated.
  3. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample submitted on 9 July 2026 was unsatisfactory: HPC 610 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • the sample 26EN-184E00098 submitted on July 3, 2026, was unsatisfactory: HPC was 110. This was a second consecutive unsatisfactory result.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Floating weir is missing on the skimmer located in the deep end. Staff confirmed part is on order. Once received and installed forward photos to confirm violation has been corrected.
  4. Risk Management Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample submitted on [Date] was unsatisfactory: HPC 130 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • the sample 26EN-184E00098 submitted on July 3, 2026, was unsatisfactory: HPC was 110. This was a second consecutive unsatisfactory result.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Floating weir is missing on the skimmer located in the deep end. Staff confirmed part is on order. Once received and installed forward photos to confirm violation has been corrected.
  5. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample submitted on [Date] was unsatisfactory: HPC 130 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • the sample 26EN-184E00098 submitted on July 3, 2026, was unsatisfactory: HPC was 110. This was a second consecutive unsatisfactory result.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Floating weir is missing on the skimmer located in the deep end. Staff confirmed part is on order. Once received and installed forward photos to confirm violation has been corrected.
  6. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample submitted on [Date] was unsatisfactory: HPC 130 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Floating weir is missing on the skimmer located in the deep end. Staff confirmed part is on order. Once received and installed forward photos to confirm violation has been corrected.
  7. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Floating weir is missing on the skimmer located in the deep end. Staff confirmed part is on order. Once received and installed forward photos to confirm violation has been corrected.
  8. Monitoring Inspection

    4 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • pH of the pool water was 7.76. Make adjusts to ensure the pool pH remains between 6.8-7.6
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Skimmer located on the west side of the pool near the shallow end did not appear to be adequately skimming. Floating weir was also missing on the skimmer of the pool on the each side by the deep end. Check skimmer and make adjustments to ensure adequate skimming action is occurring in both skimmer pots. A float valve may be required to adjust flow in the skimmers.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Return inlet on the east wall of the deep end was missing an eyeball fitting. Obtain the required equipment to ensure good circulation of the pool.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The manual pH (7.76) of the pool water was not consistent with the pH value measured by the controller (7.4). Check the controller and make necessary adjustments including but not limited to calibration or cleaning to ensure the manual and automated controller readings are consistent. Noted that the flow cell for the chemical probes was turned off and not flowing during initial part of inspection and was corrected onsite.
  9. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample submitted on 22 May 2026 was unsatisfactory: HPC 460 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
  10. Risk Management Inspection

    0 infractions

  11. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample submitted on [Date] was unsatisfactory: HPC 560 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
  12. Risk Management Inspection

    0 infractions

  13. Monitoring Inspection

    2 infractions

    • 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
      • Low ORP was observed and alarm on controller. Service technician onsite noted that the salt cell was not generating chlorine and manual chemical has been added to maintain chlorine residual. Chlorine generation by the controller must be repaired or replaced before the pool can open for the season.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The skimmer pot on the west side of the pool was not skimming very well. Adjust the skimmer to ensure proper skimming. Also the round weirs installed were not sitting level in the skimmer pot. Obtain floating weirs that will provide proper skimming action.
  14. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow through the skimmers was not adequate to ensure proper skimming action was noted. Investigate is the floating weirs require replacement or pump flow adjustment is needed to provide adequate flow for proper skimming.
  15. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample submitted on [Date] was unsatisfactory: HPC 1050 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow through the skimmers was not adequate to ensure proper skimming action was noted. Investigate is the floating weirs require replacement or pump flow adjustment is needed to provide adequate flow for proper skimming.
  16. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow through the skimmers was not adequate to ensure proper skimming action was noted. Investigate is the floating weirs require replacement or pump flow adjustment is needed to provide adequate flow for proper skimming.
  17. Risk Management Inspection

    3 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow through the skimmers was not adequate to ensure proper skimming action was noted. Investigate is the floating weirs require replacement or pump flow adjustment is needed to provide adequate flow for proper skimming.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Large debris had blown into the pool basin. Remove and vacuum the basin to remove debris and dirt.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Testing of routine chemical parameters was noted along with dates so results could be tracked. Ensure that the salt concentration is being monitored as the proper concentration range is required for the salt chlorine generator to work correctly. Also make sure servicing such as back washing is documented on the records.
  18. Monitoring Inspection

    3 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • Free chlorine was measured at 0 ppm in the pool. Observed the pool was slightly cloudy at time of inspection. Service the salt chlorine system to ensure a consistent free chlorine of at least 1 can be maintained at all times.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. Alarm light was illuminated on the controller indicating "very low salt" and a low ORP (160 mV). Investigate and make adjustments as required to ensure chlorine generation system in good working order.2. The flow rate of the system was 60 GPM. The system must have a flow rate of at least 74 GPM. Check circulation system to ensure the flow rate is within design specifications (80 GPM).3. Pool basin was overfilled and no skimming action was observed. Adjust the water level in the pool and ensure there is proper suction to ensure adequate skimming of the pool water.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Large debris had blown into the pool basin. Remove and vacuum the basin to remove debris and dirt.