Holiday Inn Express & Suites Edmonton South - Whirlpool

2440 Calgary Trail NW Edmonton AB T6J 5J6 · Aquatic Facility

15 inspections

  1. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Circulation pump is still making a loud noise. Operator believes the pump needs a new bearing. Operator will be putting forward a a request to management to purchase a new pump.
  2. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample submitted on 12/11/2025 was unsatisfactory: Pseudomonas aeruginosa isolated, Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Circulation pump is still making a loud noise. Operator believes the pump needs a new bearing. Operator will be putting forward a a request to management to purchase a new pump.
  3. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Circulation pump is still making a loud noise. Operator believes the pump needs a new bearing. Operator will be putting forward a a request to management to purchase a new pump.
  4. Demand Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Circulation pump is still making a loud noise. Operator believes the pump needs a new bearing. Operator will be putting forward a a request to management to purchase a new pump.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter has been replaced however appeared to have debris on the float. When the operator turned of the circulation pump the float did not return to zero. Service the flow meter so that it is measuring the correct flow rate. Current flow rate that was observed was 30 GPM. This flow is below the minimum required flow for the system.
  5. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. Circulation pump is still making a loud noise. Operator believes the pump needs a new bearing. Service the pump to address possible pump failure.2. Noted air bubbling in the system. There is air entering the plumbing and creating a slight cloudy hue to the water. Follow up and repair as required.3. The flow meter was not working at time of inspection. Operator confirmed they have ordered a new on March 6, 2025 and should be delivered next week.4. Acid feed pump is making loud noises when operating. Investigate to confirm need for service or replacement. Operator confirmed that a new bearing is needed.
  6. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample submitted on 5 June 2025 was unsatisfactory: Pseudomonas aeruginosa isolated, Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. Circulation pump is still making a loud noise. Operator believes the pump needs a new bearing. Service the pump to address possible pump failure.2. Noted air bubbling in the system. There is air entering the plumbing and creating a slight cloudy hue to the water. Follow up and repair as required.3. The flow meter was not working at time of inspection. Operator confirmed they have ordered a new on March 6, 2025 and should be delivered next week.4. Acid feed pump is making loud noises when operating. Investigate to confirm need for service or replacement. Operator confirmed that a new bearing is needed.
  7. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. Circulation pump is still making a loud noise. Operator believes the pump needs a new bearing. Service the pump to address possible pump failure.2. Noted air bubbling in the system. There is air entering the plumbing and creating a slight cloudy hue to the water. Follow up and repair as required.3. The flow meter was not working at time of inspection. Operator confirmed they have ordered a new on March 6, 2025 and should be delivered next week.4. Acid feed pump is making loud noises when operating. Investigate to confirm need for service or replacement. Operator confirmed that a new bearing is needed.
  8. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • the sample 25EN-086E00387 submitted on March 27, 2025, was unsatisfactory: Pseudomonas aeruginosa was isolated.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. Circulation pump is still making a loud noise. Operator believes the pump needs a new bearing. Service the pump to address possible pump failure.2. Noted air bubbling in the system. There is air entering the plumbing and creating a slight cloudy hue to the water. Follow up and repair as required.3. The flow meter was not working at time of inspection. Operator confirmed they have ordered a new on March 6, 2025 and should be delivered next week.4. Acid feed pump is making loud noises when operating. Investigate to confirm need for service or replacement. Operator confirmed that a new bearing is needed.
  9. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. Circulation pump is still making a loud noise. Operator believes the pump needs a new bearing. Service the pump to address possible pump failure.2. Noted air bubbling in the system. There is air entering the plumbing and creating a slight cloudy hue to the water. Follow up and repair as required.3. The flow meter was not working at time of inspection. Operator confirmed they have ordered a new on March 6, 2025 and should be delivered next week.4. Acid feed pump is making loud noises when operating. Investigate to confirm need for service or replacement. Operator confirmed that a new bearing is needed.
  10. Risk Management Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample submitted on 2/27/2025 was unsatisfactory: Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced. Operator was finishing treatment of the basin during the inspection.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. Circulation pump is still making a loud noise. Operator believes the pump needs a new bearing. Service the pump to address possible pump failure.2. Noted air bubbling in the system. There is air entering the plumbing and creating a slight cloudy hue to the water. Follow up and repair as required.3. The flow meter was not working at time of inspection. Operator confirmed they have ordered a new on March 6, 2025 and should be delivered next week.4. Acid feed pump is making loud noises when operating. Investigate to confirm need for service or replacement.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • Observed that facility was using non-pool grade acid for pH adjustment. Coil cleaning acid was observed which has a dye in the product. Remove the product and procure the correct pool chemical for the system.
  11. Monitoring Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample submitted on 2/27/2025 was unsatisfactory: Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced. Operator was finishing treatment of the basin during the inspection.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The pH tested from the pool was 7.19 and the pH reading from the chemical controller was9.0. The values were not consistent. Make the necessary adjustments to the chemical controller to ensurethat the manual and controller readings are consistent.2. The free chlorine in the pool was at or above 6 ppm. Check to ensure that the chemical controller setpoints are adjusted to ensure the chlorine over doses what is needed to maintain a reasonable chlorineresidual.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. Circulation pump is still making a loud noise. Operator believes the pump needs a new bearing. Service the pump to address possible pump failure.2. Noted air bubbling in the system. There is air entering the plumbing and creating a slight cloudy hue to the water. Follow up and repair as required.3. The flow meter was not working at time of inspection. Operator stated that he has tried to clean but may require replacement. Confirm on timeframe to obtain replacement flow meter.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • The clock on deck was not operational. Replace the battery or clock so that patrons can monitor length of stay.
  12. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample submitted on 2/27/2025 was unsatisfactory: Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity is 40ppm. Adjust the alkalinity in the whirlpool to between 60-180 ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. Circulation pump is making a loud noise. Operator believes the pump needs a new bearing. Service the pump to address possible pump failure.2. Water leaking noted at the fresh water fill connection to pool plumbing. Pool operator has a replacement valve to replace the leaking fitting. Repair fitting to prevent further leaking.
  13. Risk Management Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity is 40ppm. Adjust the alkalinity in the whirlpool to between 60-180 ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. Circulation pump is making a loud noise. Operator believes the pump needs a new bearing. Service the pump to address possible pump failure.2. Water leaking noted at the fresh water fill connection to pool plumbing. Pool operator has a replacement valve to replace the leaking fitting. Repair fitting to prevent further leaking.
  14. Monitoring Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Microbiological water samples are not being submitted to the lab weekly. Ensure that water samples are submitted weekly. The last sample was submitted on April 5, 2024 and was satisfactory.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity is 40ppm. Adjust the alkalinity in the whirlpool to between 60-180 ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. Circulation pump is making a loud noise. Operator believes the pump needs a new bearing. Service the pump to address possible pump failure.2. Water leaking noted at the fresh water fill connection to pool plumbing. Pool operator has a replacement valve to replace the leaking fitting. Repair fitting to prevent further leaking.3. ORP was higher than set point. Noted operator identified low chlorine in the morning and manually dosed. Ensure the controller is adequately feeding the system as required. Service of controller by a qualified technician may be needed.
  15. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample submitted on 2023-08-23 was unsatisfactory: Pseudomonas aeruginosa isolated, Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.