Home 2 Suites by Hilton - Edmonton South - Whirlpool
1140 103 A Street SW Edmonton AB T5J 2Z1 · Aquatic Facility
9 inspections
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- There was a discrepancy between the automated controller reading for pH 7.0, and the manual reading for pH 7.66. Please address.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 14.16 gpm/sq ft based on a filtration area of 7.06 sq ft and flow rate 100 gpm. Note: flow rate should not exceed 88 gpm to provide proper filtration rate.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- There was a discrepancy between the automated controller reading for pH 7.3 and the manual pH reading 7.6.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- the sample 24EN-263E00797 submitted on September 19, 2024, was unsatisfactory: Pseudomonas aeruginosa isolated and HPC over 57000. The previous sample was satisfactory.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- the sample 24EN-263E00797 submitted on September 19, 2024, was unsatisfactory: Pseudomonas aeruginosa isolated and HPC over 57000. The previous sample was satisfactory.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- There was a discrepancy between the automated controller reading for pH 7.3 and the manual pH reading 7.6.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- the sample WE-24-0011066 submitted on February 2, 2024, was unsatisfactory: Pseudomonas aeruginosa isolated.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- There was a discrepancy between the automated controller reading for pH 7.3 and the manual pH reading 7.6.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- There was a discrepancy between the automated controller reading for pH 7.3 and the manual pH reading 7.6.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- There was a discrepancy between the automated controller reading for pH 7.3 and the manual pH reading 7.6.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 13.46 gpm/sq ft based on a filtration area of 7.06 sq ft, which exceeded the maximum allowed filtration rate of 12.5 gpm/ft2. Note: flow rate should not exceed 88 gpm to provide proper filtration rate.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?