KENSINGTON PLACE NURSING AND REHABILITATION CENTER
3405 S MICHIGAN AVE, CHICAGO, IL 60616 · Long Term Care
11 inspections
- Canvass
0 infractions
- Canvass
6 infractions
- 39. CONTAMINATION PREVENTED DURING FOOD PREPARATION, STORAGE & DISPLAY
- ICE MACHINE IN NEED OF CLEANING TO REMOVE ALL BUILD UP. INSTRUCTED TO CLEAN AND MAINTAIN.
- 49. NON-FOOD/FOOD CONTACT SURFACES CLEAN
- SIDE OF COOKING EQUIPMENT AND FRYERS WITH GREASE ACCUMULATION. INSTRUCTED TO CLEAN AND MAINTAIN.
- 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
- LEAK UNDER 3 COMPARTMENT SINK IN NEED OF REPAIR. INSTRUCTED TO CORRECT AND MAINTAIN.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- SEE VIOLATION #60
- 56. ADEQUATE VENTILATION & LIGHTING; DESIGNATED AREAS USED
- LIGHT SHEILDS IN PREP AND STORAGE AREAS IN NEED OF REPLACING WHERE DAMAGED OR MISSING. INSTRUCTED TO REPLACE AND CORRECT.
- 60. PREVIOUS CORE VIOLATION CORRECTED
- PREVIOUS CORE VIOLATION NOT CORRECTED FROM JUNE 21, 2021 REPORT #2521618 6-201.11 OBSERVED UNEVEN WALLS AND COVING NOT TIGHT FITTING ON THE WALL UNDER THE 3 COMPARTMENT SINK AND THE 2 COMPARTMENT SINK. OBSERVED MISSING CEILING TILES BY THE ICE MACHINE. INSTRUCTED TO MAKE ALL SURFACES SMOOTH AND EASILY CLEANABLE.
- 39. CONTAMINATION PREVENTED DURING FOOD PREPARATION, STORAGE & DISPLAY
- Canvass Re-Inspection
4 infractions
- 16. FOOD-CONTACT SURFACES: CLEANED & SANITIZED
- 4-602.11(B-E) OBSERVED A BROWNISH SUBSTANCE ON THE PANEL OF THE ICE MACHINE LOCATED IN THE FOOD PREP AREA. INSTRUCTED TO CLEAN AND SANITIZE.
- 53. TOILET FACILITIES: PROPERLY CONSTRUCTED, SUPPLIED, & CLEANED
- 5-501.17 OBSERVED NO COVERED RECEPTACLE INSIDE OF THE WOMEN'S TOILET ROOM. INSTRUCTED TO PROVIDE.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- 6-201.13 OBSERVED COVING DEATTACHED FROM THE WALL IN VARIOUS AREAS OF THE FOOD PREP AREA. INSTRUCTED TO MAKE COVING TIGHT FITTING. 6-501.114 OBSERVED EXCESSIVE CLUTTER IN THE MEN'S LOCKER ROOM. INSTRUCTED TO ORGANIZE AND REMOVE ALL UNNECESSARY CLUTTER.
- 56. ADEQUATE VENTILATION & LIGHTING; DESIGNATED AREAS USED
- 6-303.11 OBSERVED LOW LIGHTING IN THE DRY STORAGE ROOM THAT IS LOCATED BY THE WALK IN COOLER. INSTRUCTED TO INCREASE LIGHT INTENSITY.
- 16. FOOD-CONTACT SURFACES: CLEANED & SANITIZED
- Canvass
13 infractions
- 1. PERSON IN CHARGE PRESENT, DEMONSTRATES KNOWLEDGE, AND PERFORMS DUTIES
- 2-101.11 OBSERVED PERSON IN CHARGE WITHOUT A VALID CITY OF CHICAGO FOOD SERVICE SANITATION MANAGER'S CERTIFICATE. INSTRUCTED TO MEET REQUIREMENT. PRIORITY FOUNDATION 7-38-012. CITATION ISSUED UNDER #2.
- 2. CITY OF CHICAGO FOOD SERVICE SANITATION CERTIFICATE
- 2-101.11 OBSERVED THE PERSON IN CHARGE WITHOUT A VALID CITY OF CHICAGO FOOD SERVICE SANITATION MANAGER'S CERTIFICATE. INSTRUCTED TO MEET REQUIREMENT. PRIORITY FOUNDATION. CITATION ISSUED. 7-38-012.
- 16. FOOD-CONTACT SURFACES: CLEANED & SANITIZED
- 4-602.11(B-E) OBSERVED A BROWNISH SUBSTANCE ON THE PANEL OF THE ICE MACHINE LOCATED IN THE FOOD PREP AREA. INSTRUCTED TO CLEAN AND SANITIZE.
- 48. WAREWASHING FACILITIES: INSTALLED, MAINTAINED & USED; TEST STRIPS
- 49. NON-FOOD/FOOD CONTACT SURFACES CLEAN
- 4-601.11(C) OBSERVED INTERIOR OF FRYER WITH ACCUMULATED DEBRIS. INSTRUCTED TO CLEAN. OBSERVED RUST ON THE TOP OF THE GREASE TRAP AND ON SHELVES IN THE WALK IN COOLER. INSTRUCTED TO REMOVE RUST.
- 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
- 5-204.12 UNABLE TO LOCATE THE BACK FLOW PREVENTION DEVICE ON THE ICE MACHINE. INSTRUCTED TO LOCATE.
- 52. SEWAGE & WASTE WATER PROPERLY DISPOSED
- 5-402.13 OBSERVED WASTE WATER BACKING UP FROM THE GREASE TRAP THAT IS LOCATED INSIDE OF THE DRY STORAGE ROOM. INSTRUCTED TO REPAIR AND NEVER ALLOW WASTE WATER TO BACK UP THROUGH THE GREASE TRAP. FACILITY MAY NOT USE THE 3 COMPARTMENT SINK TO WASH RINSE AND SANITIZE UTENSILS, FACILITY INSTRUCTED TO ONLY USE THE LOW TEMPERATURE DISH MACHINE TO WASH RINSE AND SANITIZE ALL EQUIPMENT AND UTENSILS. PRIORITY VIOLATION. CITATION ISSUED. 7-38-030(C).
- 53. TOILET FACILITIES: PROPERLY CONSTRUCTED, SUPPLIED, & CLEANED
- 5-501.17 OBSERVED NO COVERED RECEPTACLE INSIDE OF THE WOMEN'S TOILET ROOM. INSTRUCTED TO PROVIDE.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- 6-201.11 OBSERVED UNEVEN WALLS AND COVING NOT TIGHT FITTING ON THE WALL UNDER THE 3 COMPARTMENT SINK AND THE 2 COMPARTMENT SINK. OBSERVED MISSING CEILING TILES BY THE ICE MACHINE. INSTRUCTED TO MAKE ALL SURFACES SMOOTH AND EASILY CLEANABLE.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- 6-201.13 OBSERVED COVING DEATTACHED FROM THE WALL IN VARIOUS AREAS OF THE FOOD PREP AREA. INSTRUCTED TO MAKE COVING TIGHT FITTING.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- 6-501.12 OBSERVED STANDING WATER AROUND THE GREASE TRAP IN THE DRY STORAGE ROOM AND AROUND THE FRYER BY THE COOKING EQUIPMENT. INSTRUCTED TO REMOVE STANDING WATER. OBSERVED DEBRIS ON THE FLOORS IN THE DRY STORAGE AREAS. INSTRUCTED TO CLEAN.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- 6-501.114 OBSERVED EXCESSIVE CLUTTER IN THE MEN'S LOCKER ROOM. INSTRUCTED TO ORGANIZE AND REMOVE ALL UNNECESSARY CLUTTER.
- 56. ADEQUATE VENTILATION & LIGHTING; DESIGNATED AREAS USED
- 6-303.11 OBSERVED LOW LIGHTING IN THE DRY STORAGE ROOM THAT IS LOCATED BY THE WALK IN COOLER. INSTRUCTED TO INCREASE LIGHT INTENSITY.
- 1. PERSON IN CHARGE PRESENT, DEMONSTRATES KNOWLEDGE, AND PERFORMS DUTIES
- Canvass Re-Inspection
0 infractions
- Canvass
5 infractions
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- AN EXPOSED HANDWASHING SINK IS NEEDED IN THE DISHWASHING AREA FOR HANDWASHING WHERE THE DISHMACHINE IS LOCATED. MUST INSTALL WITH HOT AND COLD RUNNING WATER, SOAP AND HANDTOWELS. PRIORITY FOUNDATION VIOLATION 7-38-030(C).
- 49. NON-FOOD/FOOD CONTACT SURFACES CLEAN
- THE INTERIOR BOTTOM OF THE FRYER NEEDS CLEANING TO REMOVE GREASE AND BUILD UP; CLEAN AND MAINTAIN.
- 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
- OBSERVED LEAKING FROM THE FAUCET OF THE TWO COMP SINK IN THE KITCHEN; REPAIR LEAK AT FAUCET. INSTRUCTED TO CLEAN THE EXTERIOR OF THE GREASE TRAP AT THE DISHMACHINE.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- OBSERVED ITEMS STORED IN THE UTILITY CLOSET IN THE BASEMENT WHERE THE UTILITY SINK IS LOCATED; MUST REMOVE ITEMS FROM UTILITY CLOSET.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- INSTRUCTED TO CLEAN FLOORS UNDER DISHMACHINE AND IN CORNER AREAS OF STORAGE.
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- Canvass Re-Inspection
9 infractions
- 38. INSECTS, RODENTS, & ANIMALS NOT PRESENT
- 6-202.15 DOORS TO THE REAR EXIT IN NEED OF RODENT PROOFING. MUST CORRECT AND MAINTAIN.
- 49. NON-FOOD/FOOD CONTACT SURFACES CLEAN
- 4-601.11 ALL SIDES OF COOKING EQUIPMENT IN NEED OF CLEANING TO REMOVE ALL GREASE BUILD UP. MUST DETAIL CLEAN AND MAINTAIN.
- 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
- 5-204.12 BACK FLOW PREVENTOR NOT LOCATED ON NEW ICE MACHINE. MUST LOCATE AND MAINTAIN.
- 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
- LEAKS AT P-TRAP AT 3 COMPARTMENT SINK AND 2 COMPARTMENT SINK. INSTRUCTED TO REPAIR.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- 6-201.11 WALLS BEHIND COOKING EQUIPMENT IN NEED OF DETAIL CLEANING TO REMOVE ALL GREASE BUILD UP. MUST CLEAN AND MAINTAIN.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- COVING IN STORAGE AREA IN NEED OF REPAIRING IN CORNER. MUST CORRECT AND MAINTAIN.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- FLOOR IN WALK IN COOLER IN NEED OF REPAIR. FLOOR IS PULLING APART FROM THE WALL. FLOOR TILES IN FRONT OF 3 COMPARTMENT SINK ARE LOSE AND PEELING UP. ALL FLOORS MUST BE SMOOTH AND EASILY CLEANABLE. CORRECT AND MAINTAIN.
- 56. ADEQUATE VENTILATION & LIGHTING; DESIGNATED AREAS USED
- 6-202.11 LIGHTS IN STORAGE ROOM IN NEED OF SHEILDING. MUST CORRECT AND MAINTAIN.
- 56. ADEQUATE VENTILATION & LIGHTING; DESIGNATED AREAS USED
- 6-304.11 AIR VENT IN WALK IN COOLER IN NEED OF DETAIL CLEANING . MUST CORRECT AND MAINTAIN.
- 38. INSECTS, RODENTS, & ANIMALS NOT PRESENT
- Canvass
12 infractions
- 3. MANAGEMENT, FOOD EMPLOYEE AND CONDITIONAL EMPLOYEE; KNOWLEDGE, RESPONSIBILITIES AND REPORTING
- TO HAVE A SIGNED EMPLOYEE HEALTH POLICY FOR EACH EMPLOYEE. PRIORITY FOUNDATION 7-38-010. NO 2-201.11 NO WRITTEN EMPLOYEE HEALTH POLICY PROVIDED ON THE PREMISES. MANAGEMENT INSTRUCTED CITATION ISSUED.
- 5. PROCEDURES FOR RESPONDING TO VOMITING AND DIARRHEAL EVENTS
- INSTRUCTED TO PROVIDE A CLEAN-UP PROCEDURE AND SUPPLIES. PRIORITY FOUNDATION 7-38-005. NO CITATION 2-501.11 NO CLEAN-UP PROCEDURE ON PREMISES FOR VOMIT AND DIARRHEAL EVENTS. MANAGEMENT ISSUED.
- 38. INSECTS, RODENTS, & ANIMALS NOT PRESENT
- 6-202.15 DOORS TO THE REAR EXIT IN NEED OF RODENT PROOFING. MUST CORRECT AND MAINTAIN.
- 48. WAREWASHING FACILITIES: INSTALLED, MAINTAINED & USED; TEST STRIPS
- FOUND CHEMICAL DISH MACHINE NOT IN USE. MACHINE HAD NOT BEEN TURN ON FOR THE DAY. MACHINE SANITIZER AT 0 PPM. INSTRUCTED MANAGER TO CALL FOR SERVICE AND NOT TO USE MACHINE UNTIL CORRECTED AND REINSPECTED, INSTRUCTED TO USE 3 COMPARTMENT SINK. NO CITATION ISSUED DUE TO MACHINE NOT IN USE AT THIS TIME.
- 49. NON-FOOD/FOOD CONTACT SURFACES CLEAN
- 4-601.11 ALL SIDES OF COOKING EQUIPMENT IN NEED OF CLEANING TO REMOVE ALL GREASE BUILD UP. MUST DETAIL CLEAN AND MAINTAIN.
- 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
- 5-204.12 BACK FLOW PREVENTOR NOT LOCATED ON NEW ICE MACHINE. MUST LOCATE AND MAINTAIN.
- 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
- LEAKS AT P-TRAP AT 3 COMPARTMENT SINK AND 2 COMPARTMENT SINK. INSTRUCTED TO REPAIR.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- FLOOR IN WALK IN COOLER IN NEED OF REPAIR. FLOOR IS PULLING APART FROM THE WALL. FLOOR TILES IN FRONT OF 3 COMPARTMENT SINK ARE LOSE AND PEELING UP. ALL FLOORS MUST BE SMOOTH AND EASILY CLEANABLE. CORRECT AND MAINTAIN.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- 6-201.11 WALLS BEHIND COOKING EQUIPMENT IN NEED OF DETAIL CLEANING TO REMOVE ALL GREASE BUILD UP. MUST CLEAN AND MAINTAIN.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- COVING IN STORAGE AREA IN NEED OF REPAIRING IN CORNER. MUST CORRECT AND MAINTAIN.
- 56. ADEQUATE VENTILATION & LIGHTING; DESIGNATED AREAS USED
- 6-202.11 LIGHTS IN STORAGE ROOM IN NEED OF SHEILDING. MUST CORRECT AND MAINTAIN.
- 56. ADEQUATE VENTILATION & LIGHTING; DESIGNATED AREAS USED
- 6-304.11 AIR VENT IN WALK IN COOLER IN NEED OF DETAIL CLEANING . MUST CORRECT AND MAINTAIN.
- 3. MANAGEMENT, FOOD EMPLOYEE AND CONDITIONAL EMPLOYEE; KNOWLEDGE, RESPONSIBILITIES AND REPORTING
- Canvass
4 infractions
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- ICE BUILD UP ON DOOR OF WALK-IN FREEZER; REMOVE SO THAT DOOR CLOSES PROPERLY.
- 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
- CLEAN FLOORS ALONG WALLBASE AND AT CORNERS IN DRY FOOD STORAGE AREA, KITCHEN AND AT REAR LEADING TO OUTSIDE GARBAGE AREA.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- REMOVE COBWEBS FROM WALL AT CORNERS IN DRY FOOD STORAGE AREA, AND FOOD SPLASHES ON WALL BY COOKING EQUIPMENT.
- 41. PREMISES MAINTAINED FREE OF LITTER, UNNECESSARY ARTICLES, CLEANING EQUIPMENT PROPERLY STORED
- REMOVE CLUTTER IN MEN'S RESTROOM FOR STAFF, ORGANNIZE AND MAINTAIN.
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- Canvass
5 infractions
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- SOME RUST OBSERVED ON SHELVES INSIDE OF THE WALK-IN COOLER AND WALK-IN FREEZER; MUST REMOVE RUST OR REPLACE SHELVES.
- 33. FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS
- MUST CLEAN EXTERIOR SURFACES OF COOKING EQUIPMENT AND BOTTOM INTERIOR OF FRYER TO REMOVE GREASE. CLEAN INTERIOR PANEL OF ICE MACHINE IN KITCHEN.
- 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
- FLOORS NEED DETAIL CLEANING UNDER AROUND AND BEHIND COOKING EQUIPMENT AND DISHMACHINE. CLEAN FLOORS IN STORAGE ROOMS UNDER SHELVES. FLOOR IN WALK-IN COOLER RUSTED AND IN POOR REPAIR; REPAIR FLOOR IN WALK-IN COOLER. SOME FLOOR TILE MISSING OR CRACKED IN DISHWASHING AREA; REPAIR OR REPLACE FLOOR TILE WHERE NEEDED IN THIS AREA.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- ICE BUILD UP ON DOOR OF WALK-IN FREEZER; REMOVE SO THAT DOOR CLOSES PROPERLY. INTERIOR WALL PANEL OF WALK-IN COOLER (NEAR THE DOOR OF THE COOLER) IS IN POOR REPAIR; REPAIR WHERE NEEDED.
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- OBSERVED INAPPROPRIATE ITEM BEING USED FOR DRAIN STOPPERS AT THE THREE COMP SINK IN THE KITCHEN; APPROPRIATE DRAIN STOPPERS NEEDED FOR THE THREE COMP SINK; PROVIDE.
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- Canvass
4 infractions
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- PEELING PAINT AND MOLD LIKE SUBSTANCE ON DRY STORAGE ROOM WALLS, INSTRUCTED TO REMOVE.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- DAMAGED WALL SECTION, MISSING BASEBOARD AT DISH WASHING AREA, INSTRUCTED TO REPAIR.
- 36. LIGHTING: REQUIRED MINIMUM FOOT-CANDLES OF LIGHT PROVIDED, FIXTURES SHIELDED
- INADEQUATE LIGHTING INSIDE WALK-IN COOLER. INSTRUCTED TO INSTALL.
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- LEAKY PIPE UNDER 3-COMP SINK, INSTRUCTED TO REPAIR. MISSING SINK STOPPERS, INSTRUCTED TO PROVIDE.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS