Little School Age Program Ltd.

5009 49 Street Lacombe AB T4L 1Y2 · Child Care Facility

11 inspections

  1. Risk Management Inspection

    0 infractions

  2. Risk Management Inspection

    1 infraction

    • 08. Is this facility properly constructed (Non-Critical)?
      • Gap in the floor, and hole in the washroom floor have been sealed with silicone/caulking.Hole in the washroom wall overed with raw (unfinished) wood.ACTION: please seal the raw wood so that it is non-absorbent and easy to clean.
  3. Risk Management Inspection

    3 infractions

    • 03. Are clients at this facility being protected from hazards (Critical)?
      • Following conditions were noted during the inspection:1) Kitchen area was accessible to children. There was no physical barrier (door/guards/walls) to stop the kids from assessing kitchen area. Stove, iron, and sharp knife were observed in access to children.2) Chemical were observed in open shelves.Following actions are required:-Close the kitchen area with suitable guards to prevent kids accessibility.-Store all the chemicals including cleaning supplies in locked cabinets.December 5th, 2025: Violation was still pending.
    • 08. Is this facility properly constructed (Non-Critical)?
      • 1) Hole was observed in the bathroom wall (Boys washroom).Make sure to fill in the hole to prevent further damage to the wall.** Gap was observed in the wooden flooring (area dedicated for kids aged between 3 to 5 years).It is highly recommended to fill those gaps to make flooring smooth and easily cleanable.December 5th, 2025: Violation was still pending.
    • 32. Are general nuisance conditions, other than those noted in other violations, being prevented at this child care facility (Non-Critical)?
      • Tall storage shelves in the facility were not anchored to walls.Make sure to anchor the tall shelves to wall to prevent any injury.December 5th, 2025: Violation was still pending.
  4. Monitoring Inspection

    3 infractions

    • 03. Are clients at this facility being protected from hazards (Critical)?
      • Following conditions were noted during the inspection:1) Kitchen area was accessible to children. There was no physical barrier (door/guards/walls) to stop the kids from assessing kitchen area. Stove, iron, and sharp knife were observed in access to children.2) Chemical were observed in open shelves.Following actions are required:-Close the kitchen area with suitable guards to prevent kids accessibility.-Store all the chemicals including cleaning supplies in locked cabinets.
    • 08. Is this facility properly constructed (Non-Critical)?
      • 1) Hole was observed in the bathroom wall (Boys washroom).Make sure to fill in the hole to prevent further damage to the wall.** Gap was observed in the wooden flooring (area dedicated for kids aged between 3 to 5 years).It is highly recommended to fill those gaps to make flooring smooth and easily cleanable.
    • 32. Are general nuisance conditions, other than those noted in other violations, being prevented at this child care facility (Non-Critical)?
      • Tall storage shelves in the facility were not anchored to walls.Make sure to anchor the tall shelves to wall to prevent any injury.
  5. Demand Inspection

    0 infractions

  6. Risk Management Inspection

    0 infractions

  7. Risk Management Inspection

    1 infraction

    • 08. Is this facility properly constructed (Non-Critical)?
      • Holes on the ceilings were corrected. Holes and gaps on the floor was observed near the OSC side, along with gaps in the flooring. Please ensure that the walls, ceiling, and floors are smooth, easy to clean, and non-absorbent to prevent potential physical hazards, pest infestations, and the accumulation of debris.
  8. Monitoring Inspection

    2 infractions

    • 04. Are clients at this facility being protected from hazards (Non-Critical)?
      • During the inspection, no electrical outlet covers were observed, and it was confirmed with the operator that the outlets were non-GFCI. To prevent potential electrical hazards, including shock risks and injury, please ensure that all outlets are properly covered and maintained
    • 08. Is this facility properly constructed (Non-Critical)?
      • Holes were observed on the ceiling above the storage room and on the floor near the OSC side, along with gaps in the flooring. Please ensure that the walls, ceiling, and floors are smooth, easy to clean, and non-absorbent to prevent potential physical hazards, pest infestations, and the accumulation of debris.
  9. Demand Inspection

    0 infractions

  10. Risk Management Inspection

    0 infractions

  11. Monitoring Inspection

    1 infraction

    • 21. Is the plumbing system adequate and being properly maintained (Critical)?
      • Water temperature at the faucet in the washroom was measured at 57.1C. Please ensure to keep hot water taps at or below 54C (recommended 49C).