ST HELENA OF THE CROSS
10115 S PARNELL ST, CHICAGO, IL 60628 · School
7 inspections
- Canvass
0 infractions
- Canvass Re-Inspection
2 infractions
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- SEAL ALL OPENINGS AROUND PIPE FITTINGS UNDER SINKS IN FIRST AND SECOND FLOOR WASHROOMS. REMOVE PEELING PAINT ON WALLS IN FIRST FLOOR STORAGE AREA AND GIRLS WASHROOM. REPAIR RIGHT CORNER OF BOILER ROOM DOOR.
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- REPAIR OR REPLACE FAUCETS IN GIRLS AND BOYS SECOND FLOOR WASHROOMS. INCREASE HOT WATER PRESSURE ON SINK IN BOYS BASEMENT WASHROOM. PROVIDE VENTILATION IN BASEMENT WASHROOMS. REPAIR LEAKING FAUCET HANDLES ON 3-COMP SINK.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- Canvass
6 infractions
- 18. NO EVIDENCE OF RODENT OR INSECT OUTER OPENINGS PROTECTED/RODENT PROOFED, A WRITTEN LOG SHALL BE MAINTAINED AVAILABLE TO THE INSPECTORS
- OBSERVED 10-15 MICE DROPPINGS ON FLOOR IN CORNER ACROSS FROM REFRIGERATOR, 10-15 MICE DROPPINGS SCATTERED ON SHELVES AND INSIDE CABINETS IN FIRST FLOOR STORAGE AREA. INSTRUCTED MANAGER TO CALL AN EXTERMINATOR FOR SERVICE, CLEAN AND SANITZE ALL AREAS. SERIOUS VIOLATION 7-38-020 CITATION ISSUED.
- 33. FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS
- CLEAN ALL SHELVES AND CABINETS IN STORAGE AREAS.
- 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
- FLOORS NEED CLEANING ALONG WALLS AND IN ALL CORNERS IN ALL STORAGE AREAS.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- SEAL ALL OPENINGS AROUND PIPE FITTINGS UNDER SINKS IN FIRST AND SECOND FLOOR WASHROOMS. REMOVE PEELING PAINT ON WALLS IN FIRST FLOOR STORAGE AREA AND GIRLS WASHROOM.
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- REPAIR OR REPLACE FAUCETS IN GIRLS AND BOYS SECOND FLOOR WASHROOMS. REPAIR 3-COMP SINK AND REPLACE MISSING DRAINPIPES.
- 40. REFRIGERATION AND METAL STEM THERMOMETERS PROVIDED AND CONSPICUOUS
- PROVIDE THERMOMETER IN TEMPORARY REFRIGERATOR. DO NOT OVERSTOCK REFRIGERATOR FOR PROPER AIR CIRCULATION.
- 18. NO EVIDENCE OF RODENT OR INSECT OUTER OPENINGS PROTECTED/RODENT PROOFED, A WRITTEN LOG SHALL BE MAINTAINED AVAILABLE TO THE INSPECTORS
- Canvass Re-Inspection
2 infractions
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- MUST REMOVE PEELING PAINT FROM WALLS AND CEILINGS IN THE IST FLOOR BOYS AND GIRLS WASHROOMS AND REPAINT AREAS. MUST REMOVE RUST FROM 3RD STALL DIVIDER IN 2ND FLOOR BOYS WASHROOM AND REPAINT OR REPLACE.
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- MUST REPAIR LEAKY FAUCET AT MOP SINKS ON THE 2ND AND 3RD FLOORS. ALSO REPAIR LEAKY FAUCET AT THE THREE COMPARTMENT SINK.
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- Canvass
3 infractions
- 18. NO EVIDENCE OF RODENT OR INSECT OUTER OPENINGS PROTECTED/RODENT PROOFED, A WRITTEN LOG SHALL BE MAINTAINED AVAILABLE TO THE INSPECTORS
- FOUND EVIDENCE OF MICE ON SITE AND OUTER OPENINGS NOT PROTECTED. FOUND APPROXIMATELY 45-50 MICE DROPPINGS SCATTERED ALONGS WALLS,UNDER WALL HEATERS,UNDER SEATING AND THROUGHOUT STUDENT DINING AREA ADJACENT TO THE PREP KITCHEN. MUST REMOVE DROPPINGS,SANITIZE AFFECTED AREAS AND HAVE THE PEST CONTROL COMPANY SERVICE AREAS. ALSO FOUND APPROXIMATELY 1/4 INCH GAPS ALONG THE BOTTOM,BETWEEN AND ALONG THE TOP OF THE TWO MAIN ENTRANCE DOORS. MUST REPAIR AND MAKE DOORS COMPLETELY INSECT AND RODENT PROOF. SERIOUS CITATION ISSUED 7-38-020.
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- MUST REMOVE PEELING PAINT FROM WALLS AND CEILINGS IN THE IST FLOOR BOYS AND GIRLS WASHROOMS AND REPAINT AREAS. MUST REMOVE RUST FROM 3RD STALL DIVIDER IN 2ND FLOOR BOYS WASHROOM AND REPAINT OR REPLACE.
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- MUST REPAIR LEAKY FAUCET AT MOP SINKS ON THE 2ND AND 3RD FLOORS. ALSO REPAIR LEAKY FAUCET AT THE THREE COMPARTMENT SINK.
- 18. NO EVIDENCE OF RODENT OR INSECT OUTER OPENINGS PROTECTED/RODENT PROOFED, A WRITTEN LOG SHALL BE MAINTAINED AVAILABLE TO THE INSPECTORS
- Canvass
2 infractions
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- The flow of air discharged from kitchen fans shall always be through a duct to a point above the roofline. Ventilation: All plumbing fixtures, such as toilets, sinks, washbasins, etc., must be adequately trapped, vented, and re-vented and properly connected to the sewer in accordance with the plumbing chapter of the Municipal Code of Chicago and the Rules and Regulations of the Board of Health. MUST REPAIR LOW WATER PRESSURE OF HOT WATER/1ST WASH BOWL IN BOYS WASHROOM 1ST FLOOR
- 41. PREMISES MAINTAINED FREE OF LITTER, UNNECESSARY ARTICLES, CLEANING EQUIPMENT PROPERLY STORED
- Cleaning equipment shall be properly stored away from food, utensils, equipment, and clean linens. All parts of the food establishment and all parts of the property used in connection with the operation of the establishment shall be kept neat and clean and should not produce any offensive odors. MUST REMOVE DRY FOOD STORAGE FOR FOOD DEPOSITORY FROM UNDER BENCHES,1ST FLOOR AND ELEVATE IN ANOTHER AREA TO PREVENT A PEAST HARBORAGE AREA.
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- Canvass
3 infractions
- 33. FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS
- All food and non-food contact surfaces of equipment and all food storage utensils shall be thoroughly cleaned and sanitized daily. OBSERVED LOWER SHELVES OF PREP TABLE NOT CLEAN,MUST DETAIL CLEAN.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- The walls and ceilings shall be in good repair and easily cleaned. OBSERVED DUST BUILD-UP ON WALLS IN PRE-K ROOM.MUST CLEAN.
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- The flow of air discharged from kitchen fans shall always be through a duct to a point above the roofline. Ventilation: All plumbing fixtures, such as toilets, sinks, washbasins, etc., must be adequately trapped, vented, and re-vented and properly connected to the sewer in accordance with the plumbing chapter of the Municipal Code of Chicago and the Rules and Regulations of the Board of Health. OBSERVED LEAKY FAUCETS AT 3-COMP SINK AND MOP SINKS,MUST REPAIR.
- 33. FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS