171 Albany Drive NW - Swimming Pool

171 Albany Drive NW Edmonton AB T6V 1J6 · Aquatic Facility

8 inspections

  1. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The automated controller was in alarm. Investigate and take any necessary actions needed to correct.2. The water level in the pool basin was too high. Lower water levels as needed.
  2. Risk Management Inspection

    0 infractions

  3. Risk Management Inspection

    0 infractions

  4. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample submitted on 22 May 2026 was unsatisfactory: HPC 150 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
  5. Risk Management Inspection

    0 infractions

  6. Risk Management Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample result collected on 09/06/2025 [ID#: 25-EN-161E00316] was unsatisfactory: Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
  7. Monitoring Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample result collected on 09/06/2025 [ID#: 25-EN-161E00316] was unsatisfactory: Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • Free chlorine is 0.04 ppm which is too low.pH is 7.62 which is too high.Make necessary chemical adjustments.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Turnover period is 5 hours which is too fast. A 4 hour turnover period is required.The float valve in flow meter #2 is stuck. Repair/replace. A total flow rate between filter flow meter #1 and filter flow meter # 2 must be maintained between 80-147 GPM.The automated controller was in alarm. Automated controller pH is 7.41 and manual pH readings are 7.62 which is a difference of +/- 0.22. A difference of +/- 0.20 is considered to be acceptable. Repair/adjust as needed.There was a leak from the autofill valve line in the pool mechanical room. Repair.
  8. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample result collected on 09/06/2025 [ID#: 25-EN-161E00316] was unsatisfactory: Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.