171 Albany Drive NW - Swimming Pool
171 Albany Drive NW Edmonton AB T6V 1J6 · Aquatic Facility
8 inspections
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1. The automated controller was in alarm. Investigate and take any necessary actions needed to correct.2. The water level in the pool basin was too high. Lower water levels as needed.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological water sample submitted on 22 May 2026 was unsatisfactory: HPC 150 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The microbiological water sample result collected on 09/06/2025 [ID#: 25-EN-161E00316] was unsatisfactory: Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The microbiological water sample result collected on 09/06/2025 [ID#: 25-EN-161E00316] was unsatisfactory: Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Free chlorine is 0.04 ppm which is too low.pH is 7.62 which is too high.Make necessary chemical adjustments.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Turnover period is 5 hours which is too fast. A 4 hour turnover period is required.The float valve in flow meter #2 is stuck. Repair/replace. A total flow rate between filter flow meter #1 and filter flow meter # 2 must be maintained between 80-147 GPM.The automated controller was in alarm. Automated controller pH is 7.41 and manual pH readings are 7.62 which is a difference of +/- 0.22. A difference of +/- 0.20 is considered to be acceptable. Repair/adjust as needed.There was a leak from the autofill valve line in the pool mechanical room. Repair.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The microbiological water sample result collected on 09/06/2025 [ID#: 25-EN-161E00316] was unsatisfactory: Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?