71 Glamis Drive SW - Swimming Pool has been inspected 14 times by Alberta Health Services (Environmental Public Health) since September 23, 2024. The most recent inspection, on September 21, 2026, recorded 4 infractions.

None of the 14 inspections on record were free of infractions. In the past 12 months there were 9 inspections with 37 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality.

Recent inspections have recorded more infractions than earlier ones, so it is worth reading the latest reports closely.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded 32 times across 14 separate inspections, most recently on September 21, 2026. For example: Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?

  • Permits, records and postingLower risk

    Operating permits, water-test logs, posted bather rules and emergency procedures. Daily test logs are how operators show the water was checked and treated between inspections.

    Recorded 10 times across 10 separate inspections, most recently on September 21, 2026. For example: Are proper testing, monitoring, and other records being properly maintained?

  • Food safety training and certificationLower risk

    Many jurisdictions require trained pool operators and certified lifeguards. These findings mean required training, certification or staffing records were missing at the time of inspection.

    Recorded 6 times across 6 separate inspections, most recently on September 21, 2026. For example: Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?

About this data

These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

14 inspections

  1. Demand Inspection

    4 infractions

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • **OUTSTANDING**1. The safety vacuum release system on the pump is checked, but it is not being recorded. **July 10, 2026: there was no safety vacuum release system installed. COMPLETE THE FOLLOWING:1. The checks for safety vacuum release system on the pump must also be recorded in writing in the pool records.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • 1. The basin has one single blockable submerged suction outlet and no safety vacuum release system (SVRS) or other secondary anti-entrapment device installed. The Operator stated the pump was recently replaced. *September 21, 2026: the facility Manager stated that their contracted pool company would be returning to install the system. COMPLETE THE FOLLOWING:1. Install a secondary entrapment device. Manufacturer's manual and certificate of installation need to be available for review.*Update the anti-entrapment plan as soon as it is installed.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • 1. The following information is missing from the water chemistry log sheets:- Setpoint for the automated controllers (checked daily)- Total alkalinity not recorded (must be tested and recorded at least once a week)- Water clarity (checked daily)- Time of tests - New test results after chemicals are added to adjust water chemistry- Drain cover checks (checked daily)COMPLETE THE FOLLOWING:1. Ensure the above information is included in the log sheets.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • 1. A new VGBA-2017 compliant drain cover was installed to replace the old VGB-2008 drain cover. A new anti-entrapment plan completed; however, information is missing to complete the full review of the plan:- Please confirm the sump dimensions including sump depth, pipe size, and pipe exit. - Manufacturer maximum flow rate for drain cover.- Information on secondary anti-entrapment device not complete.- Plumbing schematics. COMPLETE THE FOLLOWING:1. Ensure the above information is confirmed and updated in the anti-entrapment plan. Please send for review to the district Inspector once completed.
  2. Risk Management Inspection

    3 infractions

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • **OUTSTANDING**1. The safety vacuum release system on the pump is checked, but it is not being recorded. **July 10, 2026: there was no safety vacuum release system installed. COMPLETE THE FOLLOWING:1. The checks for safety vacuum release system on the pump must also be recorded in writing in the pool records.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • 1. The basin has one single blockable submerged suction outlet and no safety vacuum release system (SVRS) or other secondary anti-entrapment device installed. The Operator stated the pump was recently replaced. COMPLETE THE FOLLOWING:1. Install a secondary entrapment device. Manufacturer's manual and certificate of installation need to be available for review.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Several test kit reagents were passed their best before dates: Please purchase new test kit reagents and ensure they are not used beyond their best before dates
  3. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample collected Aug 19 had presence of Total ColiformTreat, balance, and resample
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • **OUTSTANDING**1. The safety vacuum release system on the pump is checked, but it is not being recorded. **July 10, 2026: there was no safety vacuum release system installed. COMPLETE THE FOLLOWING:1. The checks for safety vacuum release system on the pump must also be recorded in writing in the pool records.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • 1. The basin has one single blockable submerged suction outlet and no safety vacuum release system (SVRS) or other secondary anti-entrapment device installed. The Operator stated the pump was recently replaced. COMPLETE THE FOLLOWING:1. Install a secondary entrapment device. Manufacturer's manual and certificate of installation need to be available for review.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Several test kit reagents were passed their best before dates: Please purchase new test kit reagents and ensure they are not used beyond their best before dates
  4. Risk Management Inspection

    3 infractions

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • **OUTSTANDING**1. The safety vacuum release system on the pump is checked, but it is not being recorded. **July 10, 2026: there was no safety vacuum release system installed. COMPLETE THE FOLLOWING:1. The checks for safety vacuum release system on the pump must also be recorded in writing in the pool records.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • 1. The basin has one single blockable submerged suction outlet and no safety vacuum release system (SVRS) or other secondary anti-entrapment device installed. The Operator stated the pump was recently replaced. COMPLETE THE FOLLOWING:1. Install a secondary entrapment device. Manufacturer's manual and certificate of installation need to be available for review.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Several test kit reagents were passed their best before dates: Please purchase new test kit reagents and ensure they are not used beyond their best before dates
  5. Demand Inspection

    6 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample collected on July 7, 2026 had presence of Total Coliforms
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 1. The water sample collected on July 2, 2026 had a heterotrophic plate count of 990 colony forming units/mL.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • 1. The basin has one single blockable submerged suction outlet and no safety vacuum release system (SVRS) or other secondary anti-entrapment device installed. The Operator stated the pump was recently replaced. COMPLETE THE FOLLOWING:1. Install a secondary entrapment device. Manufacturer's manual and certificate of installation need to be available for review.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • **OUTSTANDING**1. The safety vacuum release system on the pump is checked, but it is not being recorded. **July 10, 2026: there was no safety vacuum release system installed. COMPLETE THE FOLLOWING:1. The checks for safety vacuum release system on the pump must also be recorded in writing in the pool records.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • 1. The Operator did not appear to know how to treat the swimming pool water in response to unsatisfactory water samples. The facility had written procedures for responding to unsatisfactory water samples and contamination incidents; however, the Operator was not aware of these documents. These documents were reviewed with the Operator during the inspection. COMPLETE THE FOLLOWING:1. Ensure all those who are in care and control of the swimming pool are trained and aware of the proper procedures for treating water in response to unsatisfactory water samples and contamination incidents.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • 1. The Operator was not recording name of chemicals and amounts added to balance water chemistry. Water chemistry parameters were also not being tested and recorded after chemicals were added. 2. Total alkalinity was not tested and recorded in the log sheet.3. Combined chlorine was not recorded in the log sheet. 4. The following test kit reagents were passed their best before dates:- DPD reagent #1: 11/25- pH indicator: 12/25- Total alkalinity indicator: 12/255. Drain cover is not checked daily. Daily checks are not recorded in the log sheet. COMPLETE THE FOLLOWING:1. Ensure more details are recorded in the log sheet regarding additional chemicals being added, water chemistry after chemicals have been added, and corrective actions taken whenever there was an unsatisfactory water sample.2. Total alkalinity must be tested at least once a week and recorded in the log sheet. 3. Combined chlorine must be calculated and recorded in the log sheet.4. Please purchase new test kit reagents and ensure they are not used beyond their best before dates.5. Check the condition of the drain cover daily and record the checks in the log sheet.
  6. Demand Inspection

    5 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample collected on July 7, 2026 had presence of Total Coliforms
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 1. The water sample collected on July 2, 2026 had a heterotrophic plate count of 990 colony forming units/mL.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The safety vacuum release system on the pump is checked, but it is not being recorded. - The checks for safety vacuum release system on the pump must also be recorded in writing. Asked the pool operator he said he checks it but doesn't record.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Testing is not being performed on weekends. - Please ensure testing is done each day the pool is in operation.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • No written policies, and plans were available during the site visit. - Please ensure to have the written policies, and plans available at all times and also ensure that the pool operator has access to it.
  7. Demand Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 1. The water sample collected on July 2, 2026 had a heterotrophic plate count of 990 colony forming units/mL.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The safety vacuum release system on the pump is checked, but it is not being recorded. - The checks for safety vacuum release system on the pump must also be recorded in writing. Asked the pool operator he said he checks it but doesn't record.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Testing is not being performed on weekends. - Please ensure testing is done each day the pool is in operation.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • No written policies, and plans were available during the site visit. - Please ensure to have the written policies, and plans available at all times and also ensure that the pool operator has access to it.
  8. Risk Management Inspection

    3 infractions

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The safety vacuum release system on the pump is checked, but it is not being recorded. - The checks for safety vacuum release system on the pump must also be recorded in writing. Asked the pool operator he said he checks it but doesn't record.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Testing is not being performed on weekends. - Please ensure testing is done each day the pool is in operation.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • No written policies, and plans were available during the site visit. - Please ensure to have the written policies, and plans available at all times and also ensure that the pool operator has access to it.
  9. Demand Inspection

    5 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • 1. Sample collected on December 23, 2025 was present for total coliforms.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 1. Sample collected on December 23, 2025 had a heterotrophic plate count of 510 colony forming units/ mL.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The safety vacuum release system on the pump is checked, but it is not being recorded. - The checks for safety vacuum release system on the pump must also be recorded in writing. Asked the pool operator he said he checks it but doesn't record.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Testing is not being performed on weekends. - Please ensure testing is done each day the pool is in operation.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • No written policies, and plans were available during the site visit. - Please ensure to have the written policies, and plans available at all times and also ensure that the pool operator has access to it.
  10. Demand Inspection

    3 infractions

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The safety vacuum release system on the pump is checked, but it is not being recorded. - The checks for safety vacuum release system on the pump must also be recorded in writing. Asked the pool operator he said he checks it but doesn't record.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Testing is not being performed on weekends. - Please ensure testing is done each day the pool is in operation.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • No written policies, and plans were available during the site visit. - Please ensure to have the written policies, and plans available at all times and also ensure that the pool operator has access to it.
  11. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Pool water sample submitted on Nov 28, 2024 resulted in the presence of Total Coliform.ID: 24ES-334E00051
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The safety vacuum release system on the pump is not checked.- This must be checked per manufacturer's instructions at a frequency required by manufacturer. This must also be recorded in writing.
  12. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Pool water sample submitted on Nov 6, 2024 resulted in the presence of Total Coliform.ID: 24ES-312E00058
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The safety vacuum release system on the pump is not checked.- This must be checked per manufacturer's instructions at a frequency required by manufacturer. This must also be recorded in writing.
  13. Monitoring Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample was not processed as it was submitted after hours (or lab cut-off). Sample requisition/ID: 24ES-279E0004; collected on Oct 4, 2024 and received Oct 5, 2024. -submit a water sample and drop off before 4pm, Mon-Fri.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The safety vacuum release system on the pump is not checked.- This must be checked per manufacturer's instructions at a frequency required by manufacturer. This must also be recorded in writing.
  14. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample collected on Sept 20 resulted in Total Coliforms PRESENT. Sampel Req: 24ES-264E00187
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The safety vacuum release system on the pump is not checked.- This must be checked per manufacturer's instructions at a frequency required by manufacturer. This must also be recorded in writing.
Own this business? Add a badge to your website