Skip to content
Loading map…

Abbey Centre McKay Ranch - Leisure Pool

4500 Womacks Road Blackfalds AB T0M 0J0 · Aquatic Facility

10 inspections

  1. Risk Management Inspection

    0 infractions

  2. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow meter not functioning. Unable to calculate turnover or filtration rate. Repair flow meter.
  3. Risk Management Inspection

    0 infractions

  4. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC 210July 15 sample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Water level was low. Cascading was caused due to customer use and wind. Increase water level to allow for cascading when not in use.Flow meter is air locked. Unable to determine turnover or filtrate rates.Repair.Pool volume 253622.6L = 6700 galMinimum turnover flow rate = 279Filter size 21.64 sq ft
  5. Demand Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Water level was low. Cascading was caused due to customer use and wind. Increase water level to allow for cascading when not in use.Flow meter is air locked. Unable to determine turnover or filtrate rates.Repair.Pool volume 253622.6L = 6700 galMinimum turnover flow rate = 279Filter size 21.64 sq ft
  6. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow meter is air locked. Unable to determine turnover or filtrate rates.Repair.Pool volume 253622.6L = 6700 galMinimum turnover flow rate = 279Filter size 21.64 sq ft
  7. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow meter is air locked. Unable to determine turnover or filtrate rates.Repair.Pool volume 253622.6L = 6700 galMinimum turnover flow rate = 279Filter size 21.64 sq ft
  8. Risk Management Inspection

    0 infractions

  9. Monitoring Inspection

    1 infraction

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The basin is clean and in good condition.There is a leak where the chemical injection tubing joins the main line. Parts have been ordered and the repair work will be completed in the fall after the pool has been shut down for the season. The leak is minimal enough to not cause water damage issues and water is collected in a bucket to prevent it from pooling.
  10. Demand Inspection

    1 infraction

    • 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
      • Flow meter not in operation. Could not calculate the turnover rate and filtration rate. ** Repair or replace flow meter.