Banff Boundary Lodge - Whirlpool

1000 Harvie Heights Road Harvie Heights AB T1W 2W2 · Aquatic Facility

16 inspections

  1. Demand Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The pH measured (7.31) is higher than the reading, 7.1 (set 7.3).-Ensure the automated and monitoring equipment are well calibrated
    • 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
      • Permit was not displayed at the facility.-Ensure permit is displayed in a conspicuous place that is easily seen by patrons.
  2. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample from Wednesday October 1st, 2025, had Total Coliforms present. - Operators were informed to treat and re-sample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The pH measured (7.31) is higher than the reading, 7.1 (set 7.3).-Ensure the automated and monitoring equipment are well calibrated
    • 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
      • Permit was not displayed at the facility.-Ensure permit is displayed in a conspicuous place that is easily seen by patrons.
  3. Demand Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The pH measured (7.31) is higher than the reading, 7.1 (set 7.3).-Ensure the automated and monitoring equipment are well calibrated
    • 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
      • Permit was not displayed at the facility.-Ensure permit is displayed in a conspicuous place that is easily seen by patrons.
  4. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample from Wednesday July 2nd, 2025, had TC present. - Operators were informed to treat and re-sample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The pH measured (7.31) is higher than the reading, 7.1 (set 7.3).-Ensure the automated and monitoring equipment are well calibrated
    • 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
      • Permit was not displayed at the facility.-Ensure permit is displayed in a conspicuous place that is easily seen by patrons.
  5. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample from Thursday June 19th, 2025, had an HPC of 110 CFU/ml. - Operators were informed to treat and re-sample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The pH measured (7.31) is higher than the reading, 7.1 (set 7.3).-Ensure the automated and monitoring equipment are well calibrated
    • 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
      • Permit was not displayed at the facility.-Ensure permit is displayed in a conspicuous place that is easily seen by patrons.
  6. Demand Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The pH measured (7.31) is higher than the reading, 7.1 (set 7.3).-Ensure the automated and monitoring equipment are well calibrated
    • 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
      • Permit was not displayed at the facility.-Ensure permit is displayed in a conspicuous place that is easily seen by patrons.
  7. Demand Inspection

    0 infractions

  8. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample from Monday February 10th, 2025, had Total Coliforms present.- Operators were informed to treat and submit a re-sample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample from Thursday February 6th, 2025, was not processed by the lab. Wrong date on the form. - Operators were informed to submit a re-sample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • No flow rating was able to be determined. - Ensure the flow meter is working and in good repair and proper turnover rates are being met.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • No readings were recorded on October 12th, 2023. - Ensure tests are performed and logs are filled out daily.
  9. Monitoring Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample from Monday February 10th, 2025, had Total Coliforms present.- Operators were informed to treat and submit a re-sample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample from Thursday February 6th, 2025, was not processed by the lab. Wrong date on the form. - Operators were informed to submit a re-sample.
  10. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample from Thursday February 6th, 2025, was not processed by the lab. Wrong date on the form. - Operators were informed to submit a re-sample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • No flow rating was able to be determined. - Ensure the flow meter is working and in good repair and proper turnover rates are being met.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • No readings were recorded on October 12th, 2023. - Ensure tests are performed and logs are filled out daily.
  11. Demand Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • No flow rating was able to be determined. - Ensure the flow meter is working and in good repair and proper turnover rates are being met.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • No readings were recorded on October 12th, 2023. - Ensure tests are performed and logs are filled out daily.
  12. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample from Thursday November 21st, 2024, had Total Coliforms present.- Operators were informed to treat and re-sample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • No flow rating was able to be determined. - Ensure the flow meter is working and in good repair and proper turnover rates are being met.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • No readings were recorded on October 12th, 2023. - Ensure tests are performed and logs are filled out daily.
  13. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample from Thursday October 10th, 2024, had pseudomonas isolated. - Operators were informed to treat and re-sample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • No flow rating was able to be determined. - Ensure the flow meter is working and in good repair and proper turnover rates are being met.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • No readings were recorded on October 12th, 2023. - Ensure tests are performed and logs are filled out daily.
  14. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample from Thursday August 29th, 2024, had pseudomonas isolated. - Operators were informed to treat and re-sample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • No flow rating was able to be determined. - Ensure the flow meter is working and in good repair and proper turnover rates are being met.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • No readings were recorded on October 12th, 2023. - Ensure tests are performed and logs are filled out daily.
  15. Monitoring Inspection

    4 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • Initially the pH of the hot tub was very low couldn't get a reading, the automated controller said it was 6.1. - Sodium Bicarbonate was added and pH levels were raised to 7.3. Ensure the pH remains within the 6.8-7.6 range.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity was initially 29ppm. - Sodium bicarbonate was added, and the alkalinity reached 90ppm. Ensure it remains in the 60-180 ppm range.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • No flow rating was able to be determined. - Ensure the flow meter is working and in good repair and proper turnover rates are being met.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • No readings were recorded on October 12th, 2023. - Ensure tests are performed and logs are filled out daily.
  16. Risk Management Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sampling frequency was reviewed from Jan 2023 to July 2023. It was identified that there were 6 weeks of water samples missing. Please ensure a water sample is submitted to ProvLab every 7 days. If closures occur because of maintenance, please contact EPH.