Banff Boundary Lodge - Whirlpool
1000 Harvie Heights Road Harvie Heights AB T1W 2W2 · Aquatic Facility
16 inspections
- Demand Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The pH measured (7.31) is higher than the reading, 7.1 (set 7.3).-Ensure the automated and monitoring equipment are well calibrated
- 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
- Permit was not displayed at the facility.-Ensure permit is displayed in a conspicuous place that is easily seen by patrons.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample from Wednesday October 1st, 2025, had Total Coliforms present. - Operators were informed to treat and re-sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The pH measured (7.31) is higher than the reading, 7.1 (set 7.3).-Ensure the automated and monitoring equipment are well calibrated
- 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
- Permit was not displayed at the facility.-Ensure permit is displayed in a conspicuous place that is easily seen by patrons.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The pH measured (7.31) is higher than the reading, 7.1 (set 7.3).-Ensure the automated and monitoring equipment are well calibrated
- 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
- Permit was not displayed at the facility.-Ensure permit is displayed in a conspicuous place that is easily seen by patrons.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample from Wednesday July 2nd, 2025, had TC present. - Operators were informed to treat and re-sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The pH measured (7.31) is higher than the reading, 7.1 (set 7.3).-Ensure the automated and monitoring equipment are well calibrated
- 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
- Permit was not displayed at the facility.-Ensure permit is displayed in a conspicuous place that is easily seen by patrons.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample from Thursday June 19th, 2025, had an HPC of 110 CFU/ml. - Operators were informed to treat and re-sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The pH measured (7.31) is higher than the reading, 7.1 (set 7.3).-Ensure the automated and monitoring equipment are well calibrated
- 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
- Permit was not displayed at the facility.-Ensure permit is displayed in a conspicuous place that is easily seen by patrons.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The pH measured (7.31) is higher than the reading, 7.1 (set 7.3).-Ensure the automated and monitoring equipment are well calibrated
- 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
- Permit was not displayed at the facility.-Ensure permit is displayed in a conspicuous place that is easily seen by patrons.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
0 infractions
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample from Monday February 10th, 2025, had Total Coliforms present.- Operators were informed to treat and submit a re-sample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample from Thursday February 6th, 2025, was not processed by the lab. Wrong date on the form. - Operators were informed to submit a re-sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- No flow rating was able to be determined. - Ensure the flow meter is working and in good repair and proper turnover rates are being met.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- No readings were recorded on October 12th, 2023. - Ensure tests are performed and logs are filled out daily.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample from Monday February 10th, 2025, had Total Coliforms present.- Operators were informed to treat and submit a re-sample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample from Thursday February 6th, 2025, was not processed by the lab. Wrong date on the form. - Operators were informed to submit a re-sample.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample from Thursday February 6th, 2025, was not processed by the lab. Wrong date on the form. - Operators were informed to submit a re-sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- No flow rating was able to be determined. - Ensure the flow meter is working and in good repair and proper turnover rates are being met.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- No readings were recorded on October 12th, 2023. - Ensure tests are performed and logs are filled out daily.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- No flow rating was able to be determined. - Ensure the flow meter is working and in good repair and proper turnover rates are being met.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- No readings were recorded on October 12th, 2023. - Ensure tests are performed and logs are filled out daily.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample from Thursday November 21st, 2024, had Total Coliforms present.- Operators were informed to treat and re-sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- No flow rating was able to be determined. - Ensure the flow meter is working and in good repair and proper turnover rates are being met.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- No readings were recorded on October 12th, 2023. - Ensure tests are performed and logs are filled out daily.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample from Thursday October 10th, 2024, had pseudomonas isolated. - Operators were informed to treat and re-sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- No flow rating was able to be determined. - Ensure the flow meter is working and in good repair and proper turnover rates are being met.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- No readings were recorded on October 12th, 2023. - Ensure tests are performed and logs are filled out daily.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample from Thursday August 29th, 2024, had pseudomonas isolated. - Operators were informed to treat and re-sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- No flow rating was able to be determined. - Ensure the flow meter is working and in good repair and proper turnover rates are being met.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- No readings were recorded on October 12th, 2023. - Ensure tests are performed and logs are filled out daily.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
4 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Initially the pH of the hot tub was very low couldn't get a reading, the automated controller said it was 6.1. - Sodium Bicarbonate was added and pH levels were raised to 7.3. Ensure the pH remains within the 6.8-7.6 range.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The total alkalinity was initially 29ppm. - Sodium bicarbonate was added, and the alkalinity reached 90ppm. Ensure it remains in the 60-180 ppm range.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- No flow rating was able to be determined. - Ensure the flow meter is working and in good repair and proper turnover rates are being met.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- No readings were recorded on October 12th, 2023. - Ensure tests are performed and logs are filled out daily.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sampling frequency was reviewed from Jan 2023 to July 2023. It was identified that there were 6 weeks of water samples missing. Please ensure a water sample is submitted to ProvLab every 7 days. If closures occur because of maintenance, please contact EPH.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?