Banff Gate Mountain Resort - Indoor Whirlpool
302 George Biggy Senior Road Dead Man's Flats AB T1W 2T8 · Aquatic Facility
14 inspections
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample submitted on March 30, 2026 had Pseudomonas isolated. Close whirlpool until disinfection treatment done. Submit a new sample after treatment.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample taken on March 9, 2026 was not tested as the id# sticker was not put on the bottle. New water sample to be submitted this week.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample taken on February 23, 2026 was not tested as there was no time of collection on the requisition form. New sample to be submitted this week.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample taken on February 2, 2026 had Pseudomonas isolated. Close whirlpool until a Pseudomonas disinfection is done. Resample.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- There is no clock in the indoor pool area for patrons to determined length of stay in the whirlpool. Install clock in clear view of users of the indoor whirlpool.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Nov 11/24 water sample was not tested as it was received by the lab more than 24 hours after the sample was taken (wrong date possibly written on the form as to when it was taken). Resample to be submitted tomorrow.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The valve for the skimmer nearest the stairs to outside whirlpool was shut off and main drain valve was fully open. Flow needs to be maximized from surface of whirlpool; both skimmers are to be functional.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- August 12/24 water sample was not tested as there was no id# on the bottle. Resample to be submitted.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The valve for the skimmer nearest the stairs to outside whirlpool was shut off and main drain valve was fully open. Flow needs to be maximized from surface of whirlpool; both skimmers are to be functional.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The valve for the skimmer nearest the stairs to outside whirlpool was shut off and main drain valve was fully open. Flow needs to be maximized from surface of whirlpool; both skimmers are to be functional.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The valve for the skimmer nearest the stairs to outside whirlpool was shut off and main drain valve was fully open. Flow needs to be maximized from surface of whirlpool; both skimmers are to be functional.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Could not locate current anti-entrapment plan. Please provide copy for review.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?