Barrhead Regional Aquatic Centre - Whirlpool
5609 47 Street Barrhead AB T7N 1A1 · Aquatic Facility
Inspection summary
Barrhead Regional Aquatic Centre - Whirlpool has been inspected 8 times by Alberta Health Services (Environmental Public Health) since November 1, 2023. The most recent inspection, on September 21, 2026, recorded 2 infractions.
4 of 8 inspections on record found no infractions at all. In the past 12 months there were 4 inspections with 9 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality.
Recent inspections have recorded more infractions than earlier ones, so it is worth reading the latest reports closely.
What these findings mean
Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.
Pool and spa water qualityHigher risk
For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.
Recorded 9 times across 3 separate inspections, most recently on September 21, 2026. For example:
Is the bacteriological quality of the water in this pool satisfactory (Critical)?
Permits, records and postingLower risk
Operating permits, water-test logs, posted bather rules and emergency procedures. Daily test logs are how operators show the water was checked and treated between inspections.
Recorded once on November 1, 2023. For example:
Are proper testing, monitoring, and other records being properly maintained?
About this data
These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.
8 inspections
- Risk Management Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Pseudomonas aeruginosa was isolated in the Sept 14, 2026 water sample. In discussion with the operator, the basin was thoroughly cleaned during the shutdown. We discussed bringing the Free Chlorine to 10ppm overnight and to submit a water sample on the following Monday. Until the water results come back free from Pseudomonas, please try to keep the Free chlorine above 2ppm.Sept 21 update- The hot tub was shocked and a water sample was submitted.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The Sept 14/26 water sample result for Heterotrophic Plate Count (HPC) is greater than 57,000 cfu/ml. High HPC is often found in low chlorinated water, or if large amounts of contaminates are introduced. The inspection on Sept 16 found satisfactory levels of chlorine in the hot tub. Please submit a Resample on Monday to determine if the HPC is lowered.Sept 21- A water sample was submitted Sept 21, 2026
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Pseudomonas aeruginosa was isolated in the Sept 14, 2026 water sample. In discussion with the operator, the basin was thoroughly cleaned during the shutdown. We discussed bringing the Free Chlorine to 10ppm overnight and to submit a water sample on the following Monday. Until the water results come back free from Pseudomonas, please try to keep the Free chlorine above 2ppm.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The Sept 14/26 water sample result for Heterotrophic Plate Count (HPC) is greater than 57,000 cfu/ml. High HPC is often found in low chlorinated water, or if large amounts of contaminates are introduced. The inspection on Sept 16 found satisfactory levels of chlorine in the hot tub. Please submit a Resample on Monday to determine if the HPC is lowered.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- A water inlet cover is not installed properly on the water inlet pipe. Action shall be taken to replace/repair the cover. The improper inlet cap can cause a physical Hazzard to the client.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Debris is present at the bottom of the hot tub. Action shall be taken to clean all debris up prior to opening to the public.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
3 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The water in the whirl pool was high enough to skim the pool. The water high was adjusted during the inspection to allow for pool skimming.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- A water inlet cover is not installed properly on the water inlet pipe. Action shall be taken to replace/repair the cover. The improper inlet cap can cause a physical Hazzard to the client.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Debris is present at the bottom of the hot tub. Action shall be taken to clean all debris up prior to opening to the public.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
0 infractions
- Monitoring Inspection
0 infractions
- Monitoring Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Record keeping showed that hot tub Cl levels were low (0.28 ppm) and there was a gap in the record keeping times as to what happened before adjusting Cl levels. Operator confirmed that hot tub was shut down and levels were adjusted, however this was not documented in the record keeping logs in the mechanical room. Please ensure proper record keeping of water quality and actions taken to adjust water quality is documented.
- 16. Are proper testing, monitoring, and other records being properly maintained?