Burman University - Swimming Pool
6730 University Drive Lacombe AB T4L 2E5 · Aquatic Facility
8 inspections
- Monitoring Inspection
1 infraction
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- The maximum flow rate of the drain covers is 460 gpm.The maximum flow rate of the system is 750 gpm (based on pump curve).The minimum flow rate that the system must maintain in order to reach minimum turnover is 431 gpm. Typical operational flow rate is approximately 525 gpm.ACTION:Ensure that the maximum flow rate of the system does not exceed the maximum flow rate of the covers for submerged suction outlets.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water sample received.Sample collected March 17, 2026:Total Coliforms - ABSENTHPC - 150 CFUPlease shock chlorinate as per the steps outlined here: https://www.albertahealthservices.ca/assets/wf/eph/wf-eph-interpret-microbiological-sample-results-pools.pdf
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water sample received:Total Coliforms - ABSENTHPC - 110 CFU/mLSample collected July 2, 2025.Discussed results and next steps with Dan. Pool operator not on-site during call - staff member advised to close the pool from public access until the pool can be shocked according to the instructions here: https://www.albertahealthservices.ca/assets/wf/eph/wf-eph-interpret-microbiological-sample-results-pools.pdf
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Total Alkalinity was measured at 24 ppm.Please ensure that Total Alkalinity is always maintained between 60-180 ppm in order to meet the requirements.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Total Alkalinity measured 13 ppm during the inspection. CPO added sodium bicarbonate during the inspection increase the TA. Please ensure to always have sodium bicarbonate on hand to increase TA when required.Please ensure total alkalinity must be between 60-180 ppm to prevent walls and surface of the pool from damaging.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions
- Monitoring Inspection
0 infractions