Camp Kindle - Swimming Pool

26050 Range Road 61 Mountain View County AB T0M 2E0 · Aquatic Facility

11 inspections

  1. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The most recent bacteriological water sample received indicates a presence of total coliform bacteria.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The most recent bacteriological water sample received indicates an HPC count exceeding 57,000 CFU/mL.
  2. Risk Management Inspection

    0 infractions

  3. Risk Management Inspection

    1 infraction

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • A portion of the pool basin surface near the main drain is peeling, creating an area that would not be easily cleanable.Repair noted area to ensure basin surface is smooth and easily cleanable.
  4. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on July 22, 2025, indicated an elevated HPC level of >57,000CFU/ml.**Treat pool and resubmit sample.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • A portion of the pool basin surface near the main drain is peeling, creating an area that would not be easily cleanable.Repair noted area to ensure basin surface is smooth and easily cleanable.
  5. Monitoring Inspection

    1 infraction

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • A portion of the pool basin surface near the main drain is peeling, creating an area that would not be easily cleanable.Repair noted area to ensure basin surface is smooth and easily cleanable.
  6. Risk Management Inspection

    0 infractions

  7. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted on the 20th of June indicated an HPC in exceedance of 57,000 CFU/mL. Water sample submitted on June 13th came back with an elevated HPC level of 2680CFU/ml.Treat pool and resubmit sample. Verify water chemistry and ensure that the pool basin and water lines have been thoroughly disinfected via shock treatment or other suitable means.
  8. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted on June 13th came back with an elevated HPC level of 2680CFU/ml.**Treat pool and resubmit sample.
  9. Monitoring Inspection

    0 infractions

  10. Risk Management Inspection

    0 infractions

  11. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The pool sample has total coliforms present.