Canalta Cochrane - Whirlpool

10 Westside Drive Cochrane AB T4C 1M1 · Aquatic Facility

7 inspections

  1. Risk Management Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Total Alkalinity was measured at 48ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Controller readings are not consistent with manual tests. Free chlorine was measured as over 8ppm (est. at 10-11ppm), controller was reading 7.53ppm.Please make sure digital test kit is calibrated.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • One of the chemical feeding pipes had minor leak and causing white scale built up on the pipe surface.
  2. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Controller readings are not consistent with manual tests. Free chlorine was measured as over 8ppm (est. at 10-11ppm), controller was reading 7.53ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The calculated filtration rate was 13.88 USG/M/ft^2, based on 68 GPM at the flow meter and the effective filtration area being 4.9 ft^2. COMPLETE THE FOLLOWING:1. Ensure the filtration rate does not exceed the maximum filtration rate of 12.5 USG/M/ft^2 for a whirlpool.
  3. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • 1. Water sample collected on July 14, 2025 was unsatisfactory:- Present for Total Coliforms.- Pseudomonas Aeruginosa isolated.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 1. July 14, 2025 water sample had a Heterotrophic Plate Count of 480 Colony Forming Units/mL.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The calculated filtration rate was 13.88 USG/M/ft^2, based on 68 GPM at the flow meter and the effective filtration area being 4.9 ft^2. COMPLETE THE FOLLOWING:1. Ensure the filtration rate does not exceed the maximum filtration rate of 12.5 USG/M/ft^2 for a whirlpool.
  4. Demand Inspection

    6 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Unsatisfactory water sample result was received from the lab for the sample collected on Feb. 24.Pseudomonas Aeruginosa: Isolated
    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample submitted on Aug.12 was unsatisfactory.Pseudomonas Aeruginosa ISOLATED.
    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample from Oct.7 had Pseudomonas Isolated.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Unsatisfactory water sample result was received from the lab for the sample collected on Feb. 24.HPC : >57,000 CFU/ ml.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample from Oct. 7 was unsatisfactory. HPC>57000.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The calculated filtration rate was 13.88 USG/M/ft^2, based on 68 GPM at the flow meter and the effective filtration area being 4.9 ft^2. COMPLETE THE FOLLOWING:1. Ensure the filtration rate does not exceed the maximum filtration rate of 12.5 USG/M/ft^2 for a whirlpool.
  5. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample from Oct.7 had Pseudomonas Isolated.
    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample submitted on Aug.12 was unsatisfactory.Pseudomonas Aeruginosa ISOLATED.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample from Oct. 7 was unsatisfactory. HPC>57000.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The calculated filtration rate was 13.88 USG/M/ft^2, based on 68 GPM at the flow meter and the effective filtration area being 4.9 ft^2. COMPLETE THE FOLLOWING:1. Ensure the filtration rate does not exceed the maximum filtration rate of 12.5 USG/M/ft^2 for a whirlpool.
  6. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample submitted on Aug.12 was unsatisfactory.Pseudomonas Aeruginosa ISOLATED.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The calculated filtration rate was 13.88 USG/M/ft^2, based on 68 GPM at the flow meter and the effective filtration area being 4.9 ft^2. COMPLETE THE FOLLOWING:1. Ensure the filtration rate does not exceed the maximum filtration rate of 12.5 USG/M/ft^2 for a whirlpool.
  7. Initial Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The calculated filtration rate was 13.88 USG/M/ft^2, based on 68 GPM at the flow meter and the effective filtration area being 4.9 ft^2. COMPLETE THE FOLLOWING:1. Ensure the filtration rate does not exceed the maximum filtration rate of 12.5 USG/M/ft^2 for a whirlpool.