Carefree Resort - Large Pool

2540 Township 353 Red Deer County AB T4G 0K6 · Aquatic Facility

5 inspections

  1. Monitoring Inspection

    0 infractions

  2. Monitoring Inspection

    0 infractions

  3. Demand Inspection

    0 infractions

  4. Risk Management Inspection

    1 infraction

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Anti Entrapment Plan submitted in 2019. Pump: There are 3 Griswold R4GH10T 10 HP pumps in place HOWEVER, only 1 is run at a time, the other two are powered off. Max flow rate 558 gpm using flow meter and bypassing filters. More resistance is added to the system when the filters are on so this max flow rate would be less. 3, Submerged Suction Outlets / Main drains Hayward 12 x 12” covers WG1032BHF2 Maximum Flow Floor Rating 515 gpm. 7 year life span. Installed May 2023 APSP 16 2016 Compliant. Flow divided among the three. If one outlet blocked then other 2 will accommodate 100% of the flow between them – so 50%. 558/2 = 279 gpmSumps x 3. Field fabricated. Interconnected, drawings/photos and measurements provided. Currently, the main drain covers are not compatible with the sumps as the sump depths do not meet the manufacturer's installation requirements. New main drain covers that are compatible with the sump depths and the 6" diameter pipe that goes to the recirculation pump must be considered when choosing appropriate covers. SVRS in place for added protection - not a requirement as there are three interconnected main drains and they are over 26 inches apart. SVRS are to reduce physical entrapment risk, not hair entanglement. Please test SVRS according to manufacturer's specifications and keep records.No equalizer lines or submerged vacuum ports. Action:Main drain covers to be changed out with ones that are compatible for the sumps and that meet or exceed the maximum flow rating of the pump prior to the start of next season. Please advise the health inspector of the make and model of cover proposed for use prior to purchasing and installation.
  5. Monitoring Inspection

    2 infractions

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Anti Entrapment Plan submitted in 2019. Pump: There are 3 Griswold R4GH10T 10 HP pumps in place HOWEVER, only 1 is run at a time, the other two are powered off. Max flow rate 558 gpm using flow meter and bypassing filters. More resistance is added to the system when the filters are on so this max flow rate would be less. 3, Submerged Suction Outlets / Main drains Hayward 12 x 12” covers WG1032BHF2 Maximum Flow Floor Rating 515 gpm. 7 year life span. Installed May 2023 APSP 16 2016 Compliant. Flow divided among the three. If one outlet blocked then other 2 will accommodate 100% of the flow between them – so 50%. 558/2 = 279 gpmSumps x 3. Field fabricated. Interconnected, drawings/photos and measurements provided. Currently, the main drain covers are not compatible with the sumps as the sump depths do not meet the manufacturer's installation requirements. New main drain covers that are compatible with the sump depths and the 6" diameter pipe that goes to the recirculation pump must be considered when choosing appropriate covers. SVRS in place for added protection - not a requirement as there are three interconnected main drains and they are over 26 inches apart. SVRS are to reduce physical entrapment risk, not hair entanglement. Please test SVRS according to manufacturer's specifications and keep records.No equalizer lines or submerged vacuum ports. Action:Main drain covers to be changed out with ones that are compatible for the sumps and that meet or exceed the maximum flow rating of the pump prior to the start of next season. Please advise the health inspector of the make and model of cover proposed for use prior to purchasing and installation.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Taylor test kit in place. Ampules are clear, regents were within date with exception of pH reagent which was expired. Action:Please send a photo of the pH reagent when it has been replaced and I will provide you with an updated. inspection report.