Chateau Inn and Suites Bonnyville- Whirlpool
4404 52 Avenue Bonnyville AB T9N 0C3 · Aquatic Facility
12 inspections
- Monitoring Inspection
3 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The turnover period calculated is 2375 Gallon/100 GPM= 23 min. Increase/adjust the flow rate to allow the turnover to be within 20 minutes.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- An updated anti-entrapment plan was not available and has not been developed following recent alterations.Ensure that an updated anti-entrapment plan is created and submitted for review.
- 18. Have plans for construction, renovations or alteration for the pool been submitted for written approval?
- Drain covers for the suction outlets were reportedly replaced around November 2025. The circulation pump was replaced around June 2025, and the jet pump was replaced in January 2026. However, alteration plans were not submitted for review prior to completing these changes.Moving forward, ensure that the local Public Health Inspector (PHI) or Alberta Health Services (AHS) Environmental Public Health department is notified of any planned renovations or alterations prior to commencement. Additionally, updated documentation outlining the changes made to the pool system last year must be submitted for review.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The turnover period calculated is 2375 Gallon/75GPM=31 min. Increase/adjust the flow rate to allow the turnover to be within 20 minutes.Sand was observed in the hot tub basin. Please identify the root cause (aging of sand/ filter backwashing due) and take corrective actions.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
3 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- pH was not measured in number (too low/undetected).Action required:Please adjust pH between 6.8 to 7.6
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The turnover period calculated is 2375 Gallon/75GPM=31 min. Increase/adjust the flow rate to allow the turnover to be within 20 minutes.Sand was observed in the hot tub basin. Please identify the root cause (aging of sand/ filter backwashing due) and take corrective actions.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Clock was not visible from the hot tub. Ensure that the clock is visible to patrons using the hot tub.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
5 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- pH measured was 6.7Action required:Please adjust pH between 6.8 to 7.6
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Total alkalinity measured 56 ppm.Action required:Please adjust total alkalinity between 60-180 ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The turnover period calculated is 2375 Gallon/75GPM=31 min. Increase/adjust the flow rate to allow the turnover to be within 20 minutes.Sand was observed in the hot tub basin. Please identify the root cause (aging of sand/ filter backwashing due) and take corrective actions.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Clock was not visible from the hot tub. Ensure that the clock is visible to patrons using the hot tub.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The scum baskets were observed to have dirt, debris, scum build up and hair.Please clean the scum baskets regularly.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- 1. Water temperature= 41 C. Please maintain the water temperature no more than 40 C.2. Rusty outlets. Please repair or replace the rusty outlets.3. Plastic cups on skimmers. Please clean the skimmers.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Monitoring Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The pool volume is 2375gal (9 m3). The turnover = 2375/95= 25min. Please increase the flow rate to 120GPM to allow the turnover to be within 20min.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- 1. Water temperature= 41 C. Please maintain the water temperature no more than 40 C.2. Rusty outlets. Please repair or replace the rusty outlets.3. Plastic cups on skimmers. Please clean the skimmers.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
0 infractions
- Risk Management Inspection
3 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- pH=6.5
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- AL=26
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The pool volume is 2375gal (9 m3). The turn over = 2375/100=23.75 min. Please increase the flow rate to 120GPM to allow the turn over to be within 20min.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
3 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- pH=6.5
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- AL=35
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The pool volume is 2375gal (9 m3). The turn over = 2375/100=23.75 min. Please increase the flow rate to 120GPM to allow the turn over to be within 20min.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The pool volume is 2375gal (9 m3). The turn over = 2375/100=23.75 min. Please increase the flow rate to 120GPM to allow the turn over to be within 20min.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The whirlpool basin floor is in disrepair with paint chipping away.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The pool volume is 2375gal (9 m3). The turn over = 2375/100=23.75 min. Please increase the flow rate to 120GPM to allow the turn over to be within 20min.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The whirlpool basin floor is in disrepair with paint chipping away.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Sample collected on July 31, 2023: TC absentPA ISOLATEDHPC <10 CFU/mL
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The pool volume is 2375gal (9 m3). The turn over = 2375/100=23.75 min. Please increase the flow rate to 120GPM to allow the turn over to be within 20min.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The whirlpool basin floor is in disrepair with paint chipping away.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?