Skip to content
Loading map…

Claresholm Aquatic Centre - Whirlpool

212 41 Avenue W Claresholm AB T0L 0T0 · Aquatic Facility

14 inspections

  1. Monitoring Inspection

    0 infractions

  2. Risk Management Inspection

    1 infraction

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Confirmed that there is no suction relief or drain interconnections on the east side whirlpool main drain. The drain directly feeds a high flow jet pump.
  3. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 1/29. The bacterial water sample submitted on January 27th was unsatisfactory. HPC was 220 CFU/mL.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Confirmed that there is no suction relief or drain interconnections on the east side whirlpool main drain. The drain directly feeds a high flow jet pump.
  4. Risk Management Inspection

    1 infraction

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Confirmed that there is no suction relief or drain interconnections on the east side whirlpool main drain. The drain directly feeds a high flow jet pump.
  5. Demand Inspection

    1 infraction

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Confirmed that there is no suction relief or drain interconnections on the east side whirlpool main drain. The drain directly feeds a high flow jet pump.
  6. Monitoring Inspection

    0 infractions

  7. Demand Inspection

    1 infraction

    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • Sample July 15, not processed.Incomplete form.- Operator informed
  8. Risk Management Inspection

    0 infractions

  9. Risk Management Inspection

    1 infraction

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • pH measured at 7.74 today.To be maintained between 6.8 and 7.6
  10. Monitoring Inspection

    1 infraction

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • pH measured at 7.9 and at 8.02 - to be 6.8-7.6- Planning on dumping some and re-balancing.
  11. Risk Management Inspection

    0 infractions

  12. Monitoring Inspection

    1 infraction

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • pH reading of 7.76 by inspector today.- To be 7.6 or less.
  13. Risk Management Inspection

    0 infractions

  14. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • One floating weir is missing from a skimmer.- To have in place