Clarion Pointe Rimbey - Whirlpool
5702 43 Street Rimbey AB T0C 2J0 · Aquatic Facility
6 inspections
- Risk Management Inspection
0 infractions
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- - HPC measured at 150 CFU per milliliter per 100 milliliter sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- - Observed significant loud and unusual noise coming from the whirlpool circulation pump. Possible causes can include the following: 1) Cavitation—air trapped in the pump causing vibrations. 2) Bearing wear—deterioration of the motor bearings leading to grinding sounds. 3) Impeller issues—obstructions or damage to the impeller causing imbalance. 4) Loose components—vibrations from unsecured pump parts.Please ensure the whirlpool circulation place is serviced or replaced to ensure adequate circulation and water quality is maintained.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- - The flow meter for the whirlpool system is currently not operational. Please ensure a new flow meter is installed to accurately measure and record the flow rate throughout the system.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- - The whirlpool water temperature measured at 43.0 degrees Celsius. Please ensure the whirlpool water temperature does not exceed 40.0 degrees Celsius. Please ensure the temperature is lowered.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
3 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- - Observed significant loud and unusual noise coming from the whirlpool circulation pump. Possible causes can include the following: 1) Cavitation—air trapped in the pump causing vibrations. 2) Bearing wear—deterioration of the motor bearings leading to grinding sounds. 3) Impeller issues—obstructions or damage to the impeller causing imbalance. 4) Loose components—vibrations from unsecured pump parts.Please ensure the whirlpool circulation place is serviced or replaced to ensure adequate circulation and water quality is maintained.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- - The flow meter for the whirlpool system is currently not operational. Please ensure a new flow meter is installed to accurately measure and record the flow rate throughout the system.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- - The whirlpool water temperature measured at 43.0 degrees Celsius. Please ensure the whirlpool water temperature does not exceed 40.0 degrees Celsius. Please ensure the temperature is lowered.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- (X) Unsatisfactory bacteriological water sample report received, for the collection taken on December 23, 2025. The report indicates a HPC of 210 per millitre per 100 millitre sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- - The flow meter for the whirlpool system is currently not operational. Please ensure a new flow meter is installed to accurately measure and record the flow rate throughout the system.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- - Observed significant loud and unusual noise coming from the whirlpool circulation pump. Possible causes can include the following: 1) Cavitation—air trapped in the pump causing vibrations. 2) Bearing wear—deterioration of the motor bearings leading to grinding sounds. 3) Impeller issues—obstructions or damage to the impeller causing imbalance. 4) Loose components—vibrations from unsecured pump parts.Please ensure the whirlpool circulation place is serviced or replaced to ensure adequate circulation and water quality is maintained.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- - The whirlpool water temperature measured at 43.0 degrees Celsius. Please ensure the whirlpool water temperature does not exceed 40.0 degrees Celsius. Please ensure the temperature is lowered.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- (X) Unsatisfactory bacteriological water sample report received, for the collection taken on December 23, 2025. The report indicates a HPC of 210 per millitre per 100 millitre sample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Initial Inspection
0 infractions