Days Inn & Suites Cochrane - Whirlpool
5 Westside Drive Cochrane AB T4C 1M1 · Aquatic Facility
Inspection summary
Days Inn & Suites Cochrane - Whirlpool has been inspected 14 times by Alberta Health Services (Environmental Public Health) since October 31, 2025. The most recent inspection, on October 15, 2026, found no infractions.
4 of 14 inspections on record found no infractions at all. In the past 12 months there were 14 inspections with 30 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality and Chemicals and toxic substances.
Recent inspections have recorded fewer infractions than earlier ones, so the record is improving.
What these findings mean
Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.
Pool and spa water qualityHigher risk
For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.
Recorded 22 times across 10 separate inspections, most recently on July 2, 2026. For example:
Is the bacteriological quality of the water in this pool satisfactory (Critical)?
Chemicals and toxic substancesHigher risk
Pool chemicals such as chlorine and acid must be labelled, stored apart from each other and handled safely. Mixing them by mistake can release toxic gas, so storage and handling problems are treated seriously.
Recorded 8 times across 5 separate inspections, most recently on December 12, 2025. For example:
Is the chemical quality of the water in this pool satisfactory (Critical)?
About this data
These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.
14 inspections
- Risk Management Inspection
0 infractions
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Pseudomonas aeruginosa was isolated from water sample. Treat the whirlpool basin following AHS guidelines and submit another sample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- High Heterotrophic Plate Count of over 57,000 CFU/mL was measured from sample. Treat whirlpool and submit resample.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample collected on June 15, 2026 was Unsatisfactory. Pseudomonas: ISOLATED
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample submitted on April 13 was Unsatisfactory.Pseudomonas: ISOLATED
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample submitted on April 13 was Unsatisfactory.HPC: >57000 CFU/mL.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample submitted on Dec. 15 was not processed by the lab due to no identification number on the bottle.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample submitted on Dec. 15 was not processed by the lab due to no identification number on the bottle.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Risk Management Inspection
2 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- *The Free Chlorine was measured greater than 8ppm, over rate. Automatic reader was showing FCL: 3. 32ppm
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The automated monitoring system’s chemical readings were inconsistent with manual testing. Automated reading for pH was 6.8 and manual testing was under range less than 6.5.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
2 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- *The Free Chlorine was measured greater than 8ppm, over rate. Automatic reader was showing FCL: 3. 32ppm
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The automated monitoring system’s chemical readings were inconsistent with manual testing. Automated reading for pH was 6.8 and manual testing was under range less than 6.5.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
5 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- *The Free Available Chlorine was measured at 0.5 ppm.*Manual pH testing of the whirlpool water showed pH was very low, less than 6.5
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The alkalinity of the whirlpool water was measured greater than 200ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The automated monitoring system’s chemical readings were inconsistent with manual testing. Automated reading for pH was 6.8 and manual testing was under range less than 6.5.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Excessive foaming was observed in the whirlpool water.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- The Clock by the whirlpool area was not operational
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
7 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Bacteriological water sample taken from the whirlpool on November 24, 2025 had Pseudomonas PRESENT.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Bacteriological water sample taken from the whirlpool on November 24, 2025, had HPC 930cf/mL
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- *The Free Available Chlorine was measured at 0.5 ppm.*Manual pH testing of the whirlpool water showed pH was very low, less than 6.5
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The alkalinity of the whirlpool water was measured greater than 200ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The automated monitoring system’s chemical readings were inconsistent with manual testing. Automated reading for pH was 6.8 and manual testing was under range less than 6.5.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Excessive foaming was observed in the whirlpool water.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- The Clock by the whirlpool area was not operational
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Initial Inspection
5 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- *The Free Available Chlorine was measured at 0.5 ppm.*Manual pH testing of the whirlpool water showed pH was very low, less than 6.5
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The alkalinity of the whirlpool water was measured greater than 200ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The automated monitoring system’s chemical readings were inconsistent with manual testing. Automated reading for pH was 6.8 and manual testing was under range less than 6.5.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Excessive foaming was observed in the whirlpool water.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- The Clock by the whirlpool area was not operational
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Sample from Oct. 27 was unsatisfactory. Pseudomonas: ISOLATED and HPC: 300CFU/mL.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sample from Oct. 27 - HPC: 300CFU/mL.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?