Derrick Golf & Winter Club - Swimming Pool
3500 119 Street NW Edmonton AB T6J 5P5 · Aquatic Facility
4 inspections
- Monitoring Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter was not operational: turnover period and rate of filtration could not be confirmed. Please repair or replace the flow meter.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
1 infraction
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Maximum flow rate for the Aquastar 1216101 covers was 460 gpm, while the pump can produce the flow over 500 gpm (as per anti-entrapment compliance assessment). A set-up for flow secured system with the circulation pump VFD is required.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Monitoring Inspection
1 infraction
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Maximum flow rate for the Aquastar 1216101 covers was 460 gpm, while the pump can produce the flow over 500 gpm (as per anti-entrapment compliance assessment). A set-up for flow secured system with the circulation pump VFD is required.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?