Derrick Golf & Winter Club - Women's Whirlpool

3500 119 Street NW Edmonton AB T6J 5P5 · Aquatic Facility

7 inspections

  1. Monitoring Inspection

    0 infractions

  2. Demand Inspection

    5 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • the sample 25EN-310E00597 submitted on November 6, 2025, was unsatisfactory: Total coliforms were present and HPC 230.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • the sample 25EN-310E00597 submitted on November 6, 2025, was unsatisfactory: Total coliforms were present and HPC 230.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Rate of filtration for the filtration system was 15.26 gpm/sq ft based on a flow rate 110 gpm and a filtration area of 7.155 sq ft. According to the filter data plate, the maximum flow rate allowed by the manufacturer is 100.8 gpm for commercial application, while the observed flow rate was 110 gpm. Therefore, the flow rate cannot exceed 100 gpm (which will result in the rate of filtration 13.97 gpm/ft2), if the chemical and microbiological parameters can be maintained, or the flow rate must be lowered to 90 gpm to provide the rate of filtration 12.5 gpm/ft2.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The recirculation pump flow meter was not operational: turnover period and rate of filtration could not be confirmed. Please repair or replace the flow meter.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • According to the new Anti-Entrapment Compliance Plan, new covers Aquastar 914101 have maximum flow rate allowed 250 gpm but total flow rate that can be produced by the system is 286 gpm (as per new Anti-Entrapment Compliance Plan). At the time of the inspection, the flow meters were not operating properly. Ensure that the flow rate for the system does not exceed the maximum allowed flow rate for the main drain covers.
  3. Monitoring Inspection

    3 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Rate of filtration for the filtration system was 15.26 gpm/sq ft based on a flow rate 110 gpm and a filtration area of 7.155 sq ft. According to the filter data plate, the maximum flow rate allowed by the manufacturer is 100.8 gpm for commercial application, while the observed flow rate was 110 gpm. Therefore, the flow rate cannot exceed 100 gpm (which will result in the rate of filtration 13.97 gpm/ft2), if the chemical and microbiological parameters can be maintained, or the flow rate must be lowered to 90 gpm to provide the rate of filtration 12.5 gpm/ft2.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The recirculation pump flow meter was not operational: turnover period and rate of filtration could not be confirmed. Please repair or replace the flow meter.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • According to the new Anti-Entrapment Compliance Plan, new covers Aquastar 914101 have maximum flow rate allowed 250 gpm but total flow rate that can be produced by the system is 286 gpm (as per new Anti-Entrapment Compliance Plan). At the time of the inspection, the flow meters were not operating properly. Ensure that the flow rate for the system does not exceed the maximum allowed flow rate for the main drain covers.
  4. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Rate of filtration for the filtration system was 15.26 gpm/sq ft based on a flow rate 110 gpm and a filtration area of 7.155 sq ft. According to the filter data plate, the maximum flow rate allowed by the manufacturer is 100.8 gpm for commercial application, while the observed flow rate was 110 gpm. Therefore, the flow rate cannot exceed 100 gpm (which will result in the rate of filtration 13.97 gpm/ft2), if the chemical and microbiological parameters can be maintained, or the flow rate must be lowered to 90 gpm to provide the rate of filtration 12.5 gpm/ft2.
  5. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorine residual was 2.01 ppm. Ensure that the combined chlorine residual is kept at the lowest level possible.
  6. Monitoring Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorine residual was 2.01 ppm. Ensure that the combined chlorine residual is kept at the lowest level possible.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Invalid installation of the inner adapter frame for the main drain outlets.
  7. Risk Management Inspection

    3 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Rate of filtration for the filtration system was 15.37 gpm/sq ft based on a filtration area of 7.155 sq ft.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Aquastar covers rating listed in the report was 560 gpm. The estimated maximum flow rate for the system listed in the report was 308 gpm, which exceeds the maximum flow rate of the Hayward covers. Please confirm the actual maximum flow rate for the system.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Water temperature was 105.6F (automated controller reading).