Didsbury Aquatic Centre - Swimming Pool
1702 21 Avenue Didsbury AB T0M 0W0 · Aquatic Facility
16 inspections
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The most recent bacteriological water sample indicated a Heterotrophic Plate Count of 3120 CFU/mL.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample submitted on June 2, 2026 indicated an elevated HPC value of 2240CFU/ml.**Treat and resubmit sample
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The most recent bacteriological water sample indicated a Heterotrophic Plate Count of 2120 CFU/mL.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **OUTSTANDING**1. ONE OF THE SKIMMERS (THE ONE THAT IS NEAR THE CHANGING ROOMS AT THE SHALLOW END) WAS ACCIDENTALLY SEALED PERMANENTLY (i.e. NO FLOW GOES THROUGH IT). COMPLETE THE FOLLOWING:1. PLEASE HAVE THE STAFF CHECK THE WATER CHEMISTRY IN THIS AREA ONCE A DAY TO MAKE SURE IT IS MIXING ADEQUATELY AND THAT NO DEAD SPOTS ARE BEING CREATED. PERIODICALLY TAKE BACTERIOLOGICAL WATER SAMPLES IN THIS AREA. RECOMMEND RENOVATING THE SKIMMER TO REPLACE THE BLOCKED LINE. **Repairs would require a major renovation and shutdown of facility. Currently none is planned. ***A dye circulation test is scheduled for September to determine extent of pool circulation concerns.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **OUTSTANDING**1. ONE OF THE SKIMMERS (THE ONE THAT IS NEAR THE CHANGING ROOMS AT THE SHALLOW END) WAS ACCIDENTALLY SEALED PERMANENTLY (i.e. NO FLOW GOES THROUGH IT). COMPLETE THE FOLLOWING:1. PLEASE HAVE THE STAFF CHECK THE WATER CHEMISTRY IN THIS AREA ONCE A DAY TO MAKE SURE IT IS MIXING ADEQUATELY AND THAT NO DEAD SPOTS ARE BEING CREATED. PERIODICALLY TAKE BACTERIOLOGICAL WATER SAMPLES IN THIS AREA. RECOMMEND RENOVATING THE SKIMMER TO REPLACE THE BLOCKED LINE. **Repairs would require a major renovation and shutdown of facility. Currently none is planned.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The digital flow meter indicated a flow rate of 545GPM for the swimming pool. Legislation would normally limit this pool to a maximum flow of 375GPM. Pools built before November 2006 may use filter manufacturer specifications to determine maximum flow rate, provided that water quality can be reliably maintained. The high rate sand filter used for this basin indicates a maximum flow rate of 500GPM.Lower the pool circulation system's flow rate to below the maximum flow rate indicated by filter manufacturer specifications.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The most recent bacteriological water sample indicated a Heterotrophic Plate Count of 2230 CFU/mL.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **OUTSTANDING**1. ONE OF THE SKIMMERS (THE ONE THAT IS NEAR THE CHANGING ROOMS AT THE SHALLOW END) WAS ACCIDENTALLY SEALED PERMANENTLY (i.e. NO FLOW GOES THROUGH IT). COMPLETE THE FOLLOWING:1. PLEASE HAVE THE STAFF CHECK THE WATER CHEMISTRY IN THIS AREA ONCE A DAY TO MAKE SURE IT IS MIXING ADEQUATELY AND THAT NO DEAD SPOTS ARE BEING CREATED. PERIODICALLY TAKE BACTERIOLOGICAL WATER SAMPLES IN THIS AREA. RECOMMEND RENOVATING THE SKIMMER TO REPLACE THE BLOCKED LINE. **Repairs would require a major renovation and shutdown of facility. Currently none is planned.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The digital flow meter indicated a flow rate of 545GPM for the swimming pool. Legislation would normally limit this pool to a maximum flow of 375GPM. Pools built before November 2006 may use filter manufacturer specifications to determine maximum flow rate, provided that water quality can be reliably maintained. The high rate sand filter used for this basin indicates a maximum flow rate of 500GPM.Lower the pool circulation system's flow rate to below the maximum flow rate indicated by filter manufacturer specifications.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The digital flow meter indicated a flow rate of 545GPM for the swimming pool. Legislation would normally limit this pool to a maximum flow of 375GPM. Pools built before November 2006 may use filter manufacturer specifications to determine maximum flow rate, provided that water quality can be reliably maintained. The high rate sand filter used for this basin indicates a maximum flow rate of 500GPM.Lower the pool circulation system's flow rate to below the maximum flow rate indicated by filter manufacturer specifications.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **OUTSTANDING**1. ONE OF THE SKIMMERS (THE ONE THAT IS NEAR THE CHANGING ROOMS AT THE SHALLOW END) WAS ACCIDENTALLY SEALED PERMANENTLY (i.e. NO FLOW GOES THROUGH IT). COMPLETE THE FOLLOWING:1. PLEASE HAVE THE STAFF CHECK THE WATER CHEMISTRY IN THIS AREA ONCE A DAY TO MAKE SURE IT IS MIXING ADEQUATELY AND THAT NO DEAD SPOTS ARE BEING CREATED. PERIODICALLY TAKE BACTERIOLOGICAL WATER SAMPLES IN THIS AREA. RECOMMEND RENOVATING THE SKIMMER TO REPLACE THE BLOCKED LINE. **Repairs would require a major renovation and shutdown of facility. Currently none is planned.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **OUTSTANDING**1. ONE OF THE SKIMMERS (THE ONE THAT IS NEAR THE CHANGING ROOMS AT THE SHALLOW END) WAS ACCIDENTALLY SEALED PERMANENTLY (i.e. NO FLOW GOES THROUGH IT). COMPLETE THE FOLLOWING:1. PLEASE HAVE THE STAFF CHECK THE WATER CHEMISTRY IN THIS AREA ONCE A DAY TO MAKE SURE IT IS MIXING ADEQUATELY AND THAT NO DEAD SPOTS ARE BEING CREATED. PERIODICALLY TAKE BACTERIOLOGICAL WATER SAMPLES IN THIS AREA. RECOMMEND RENOVATING THE SKIMMER TO REPLACE THE BLOCKED LINE. **Repairs would require a major renovation and shutdown of facility. Currently none is planned.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1. The digital flow metre is not operational.**August 7, 2024: part has been ordered. Tentative replacement date is in August. COMPLETE THE FOLLOWING:1. Replace the flow metre.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- **NOT OBSERVED DURING INSPECTION**1. Duct tape is being used to cover tiles that are in disrepair at the shallow end of the pool deck.COMPLETE THE FOLLOWING:1. Repair tiles.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
3 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1. The digital flow metre is not operational.COMPLETE THE FOLLOWING:1. Replace the flow metre.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **OUTSTANDING**1. ONE OF THE SKIMMERS (THE ONE THAT IS NEAR THE CHANGING ROOMS AT THE SHALLOW END) WAS ACCIDENTALLY SEALED PERMANENTLY (i.e. NO FLOW GOES THROUGH IT). COMPLETE THE FOLLOWING:1. PLEASE HAVE THE STAFF CHECK THE WATER CHEMISTRY IN THIS AREA ONCE A DAY TO MAKE SURE IT IS MIXING ADEQUATELY AND THAT NO DEAD SPOTS ARE BEING CREATED. PERIODICALLY TAKE BACTERIOLOGICAL WATER SAMPLES IN THIS AREA. RECOMMEND RENOVATING THE SKIMMER TO REPLACE THE BLOCKED LINE. **Repairs would require a major renovation and shutdown of facility. Currently none is planned.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- 1. Duct tape is being used to cover tiles that are in disrepair at the shallow end of the pool deck.COMPLETE THE FOLLOWING:1. Repair tiles.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **OUTSTANDING**1. ONE OF THE SKIMMERS (THE ONE THAT IS NEAR THE CHANGING ROOMS AT THE SHALLOW END) WAS ACCIDENTALLY SEALED PERMANENTLY (i.e. NO FLOW GOES THROUGH IT). COMPLETE THE FOLLOWING:1. PLEASE HAVE THE STAFF CHECK THE WATER CHEMISTRY IN THIS AREA ONCE A DAY TO MAKE SURE IT IS MIXING ADEQUATELY AND THAT NO DEAD SPOTS ARE BEING CREATED. PERIODICALLY TAKE BACTERIOLOGICAL WATER SAMPLES IN THIS AREA. RECOMMEND RENOVATING THE SKIMMER TO REPLACE THE BLOCKED LINE. **Repairs would require a major renovation and shutdown of facility. Currently none is planned.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample result collected on October 17, 2023 showed HPC level - 200 CFU/ml. Please treat water and resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- ONE OF THE SKIMMERS (THE ONE THAT IS NEAR THE CHANGING ROOMS AT THE SHALLOW END) WAS ACCIDENTALLY SEALED PERMANENTLY (i.e. NO FLOW GOES THROUGH IT). PLEASE HAVE THE STAFF CHECK THE WATER CHEMISTRY IN THIS AREA ONCE A DAY TO MAKE SURE IT IS MIXING ADEQUATELY AND THAT NO DEAD SPOTS ARE BEING CREATED. PERIODICALLY TAKE BACTERIOLOGICAL WATER SAMPLES IN THIS AREA.RECOMMEND RENOVATING THE SKIMMER TO REPLACE THE BLOCKED LINE. ** Dec 1 2021: Discussed this skimmer with the pool operator - there are plans to renovate and address this concern in 2023. July 26, 2022: The operator is aware of the outstanding violation. Renovations may be conducted in 2023 or 2024 depending on budget.January 13, 2023: Violation still outstanding.June 15th, 2023: Violation still outstanding.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?