Gleniffer Lake Resort - South Hot Tub Indoor

35468 Range Road 30 Red Deer County AB T0M 1V0 · Aquatic Facility

16 inspections

  1. Monitoring Inspection

    1 infraction

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Anti-entrapment plan updates provided, the following is outstanding: Two pumps are included on the plan. Maximum flow rating for each is required. The operator will confirm interconnectedness of sumps and pumps. Drawings available were proposed plans and likely do not represent what is in place. Operator is aware that if the jet pump is pulling from single main drain in basin - that a secondary anti-entrapment device will be required. Prior to purchase and install, the operator will provide the health inspector with the type, make and model of the secondary anti-entrapment device. Pumps:Champion 56 frame (recirc) and B&D BDXBTVAR300. Max flow of each pump separately to be determined. Picture of flow meter provided. Variable speed B&D pump, must be turned to its highest speed and flow measured. Ensure filters backwashed, skimmers turned off to get the reading. 2" lines out sumps for both recirculation and jet pumps. Covers:One cover has been replaced as it was cracked. Certificates of compliance provided for the new one and existing covers. Existing covers expire Sept 16, 2025. New cover will expire October 1, 2030 as there is a 7 year expiry from date of install. Please update new cover date in anti-entrapment plan. Covers are ANSI/APSP-16 compliant. Photo of new cover provided. SumpHayward WG1154AV sumps, and covers are WG1048E with corresponding WG1056C rings. Drawing and photos of sumps provided. No equalizer lines in placeActions: 1) Determine interconnectedness of sumps/pumps. If a single main drain situation exists, secondary anti-entrapment required - must be approved by health inspector prior to purchased and install. 2) Provide drawing that shows current piping schematic from hot tub basin to pump in mechanical room. 3) get max flow rates for each pump independently4) Update anti-entrapment plan and submit to health inspector.
  2. Monitoring Inspection

    1 infraction

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Anti-entrapment plan updates provided, the following is outstanding: Two pumps are included on the plan. Maximum flow rating for each is required. The operator will confirm interconnectedness of sumps and pumps. Drawings available were proposed plans and likely do not represent what is in place. Operator is aware that if the jet pump is pulling from single main drain in basin - that a secondary anti-entrapment device will be required. Prior to purchase and install, the operator will provide the health inspector with the type, make and model of the secondary anti-entrapment device. Pumps:Champion 56 frame (recirc) and B&D BDXBTVAR300. Max flow of each pump separately to be determined. Picture of flow meter provided. Variable speed B&D pump, must be turned to its highest speed and flow measured. Ensure filters backwashed, skimmers turned off to get the reading. 2" lines out sumps for both recirculation and jet pumps. Covers:One cover has been replaced as it was cracked. Certificates of compliance provided for the new one and existing covers. Existing covers expire Sept 16, 2025. New cover will expire October 1, 2030 as there is a 7 year expiry from date of install. Please update new cover date in anti-entrapment plan. Covers are ANSI/APSP-16 compliant. Photo of new cover provided. SumpHayward WG1154AV sumps, and covers are WG1048E with corresponding WG1056C rings. Drawing and photos of sumps provided. No equalizer lines in placeActions: 1) Determine interconnectedness of sumps/pumps. If a single main drain situation exists, secondary anti-entrapment required - must be approved by health inspector prior to purchased and install. 2) Provide drawing that shows current piping schematic from hot tub basin to pump in mechanical room. 3) get max flow rates for each pump independently4) Update anti-entrapment plan and submit to health inspector.
  3. Risk Management Inspection

    1 infraction

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Anti-entrapment plan updates provided, the following is outstanding: Two pumps are included on the plan. Maximum flow rating for each is required. The operator will confirm interconnectedness of sumps and pumps. Drawings available were proposed plans and likely do not represent what is in place. Operator is aware that if the jet pump is pulling from single main drain in basin - that a secondary anti-entrapment device will be required. Prior to purchase and install, the operator will provide the health inspector with the type, make and model of the secondary anti-entrapment device. Pumps:Champion 56 frame (recirc) and B&D BDXBTVAR300. Max flow of each pump separately to be determined. Picture of flow meter provided. Variable speed B&D pump, must be turned to its highest speed and flow measured. Ensure filters backwashed, skimmers turned off to get the reading. 2" lines out sumps for both recirculation and jet pumps. Covers:One cover has been replaced as it was cracked. Certificates of compliance provided for the new one and existing covers. Existing covers expire Sept 16, 2025. New cover will expire October 1, 2030 as there is a 7 year expiry from date of install. Please update new cover date in anti-entrapment plan. Covers are ANSI/APSP-16 compliant. Photo of new cover provided. SumpHayward WG1154AV sumps, and covers are WG1048E with corresponding WG1056C rings. Drawing and photos of sumps provided. No equalizer lines in placeActions: 1) Determine interconnectedness of sumps/pumps. If a single main drain situation exists, secondary anti-entrapment required - must be approved by health inspector prior to purchased and install. 2) Provide drawing that shows current piping schematic from hot tub basin to pump in mechanical room. 3) get max flow rates for each pump independently4) Update anti-entrapment plan and submit to health inspector.
  4. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • 1. Routine water sample result: Pseudomonas PresentClose the pool from public use immediately. Drain and thoroughly clean and sanitize the pool basin and all accessible surfaces. Shock chlorinate the pool. After shock chlorinating, backwash the filter. Re-balance the water chemistry to bring the free chlorine level to at least 2.0ppm. The pool can then be re-opened to the public.Resample on your regular sampling day
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Anti-entrapment plan updates provided, the following is outstanding: Two pumps are included on the plan. Maximum flow rating for each is required. The operator will confirm interconnectedness of sumps and pumps. Drawings available were proposed plans and likely do not represent what is in place. Operator is aware that if the jet pump is pulling from single main drain in basin - that a secondary anti-entrapment device will be required. Prior to purchase and install, the operator will provide the health inspector with the type, make and model of the secondary anti-entrapment device. Pumps:Champion 56 frame (recirc) and B&D BDXBTVAR300. Max flow of each pump separately to be determined. Picture of flow meter provided. Variable speed B&D pump, must be turned to its highest speed and flow measured. Ensure filters backwashed, skimmers turned off to get the reading. 2" lines out sumps for both recirculation and jet pumps. Covers:One cover has been replaced as it was cracked. Certificates of compliance provided for the new one and existing covers. Existing covers expire Sept 16, 2025. New cover will expire October 1, 2030 as there is a 7 year expiry from date of install. Please update new cover date in anti-entrapment plan. Covers are ANSI/APSP-16 compliant. Photo of new cover provided. SumpHayward WG1154AV sumps, and covers are WG1048E with corresponding WG1056C rings. Drawing and photos of sumps provided. No equalizer lines in placeActions: 1) Determine interconnectedness of sumps/pumps. If a single main drain situation exists, secondary anti-entrapment required - must be approved by health inspector prior to purchased and install. 2) Provide drawing that shows current piping schematic from hot tub basin to pump in mechanical room. 3) get max flow rates for each pump independently4) Update anti-entrapment plan and submit to health inspector.
  5. Risk Management Inspection

    1 infraction

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Anti-entrapment plan updates provided, the following is outstanding: Two pumps are included on the plan. Maximum flow rating for each is required. The operator will confirm interconnectedness of sumps and pumps. Drawings available were proposed plans and likely do not represent what is in place. Operator is aware that if the jet pump is pulling from single main drain in basin - that a secondary anti-entrapment device will be required. Prior to purchase and install, the operator will provide the health inspector with the type, make and model of the secondary anti-entrapment device. Pumps:Champion 56 frame (recirc) and B&D BDXBTVAR300. Max flow of each pump separately to be determined. Picture of flow meter provided. Variable speed B&D pump, must be turned to its highest speed and flow measured. Ensure filters backwashed, skimmers turned off to get the reading. 2" lines out sumps for both recirculation and jet pumps. Covers:One cover has been replaced as it was cracked. Certificates of compliance provided for the new one and existing covers. Existing covers expire Sept 16, 2025. New cover will expire October 1, 2030 as there is a 7 year expiry from date of install. Please update new cover date in anti-entrapment plan. Covers are ANSI/APSP-16 compliant. Photo of new cover provided. SumpHayward WG1154AV sumps, and covers are WG1048E with corresponding WG1056C rings. Drawing and photos of sumps provided. No equalizer lines in placeActions: 1) Determine interconnectedness of sumps/pumps. If a single main drain situation exists, secondary anti-entrapment required - must be approved by health inspector prior to purchased and install. 2) Provide drawing that shows current piping schematic from hot tub basin to pump in mechanical room. 3) get max flow rates for each pump independently4) Update anti-entrapment plan and submit to health inspector.
  6. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • 1. Routine water sample result: Pseudomonas PresentClose the pool from public use immediately. Drain and thoroughly clean and sanitize the pool basin and all accessible surfaces. Shock chlorinate the pool. After shock chlorinating, backwash the filter. Re-balance the water chemistry to bring the free chlorine level to at least 2.0ppm. The pool can then be re-opened to the public.Resample on your regular sampling day
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Anti-entrapment plan updates provided, the following is outstanding: Two pumps are included on the plan. Maximum flow rating for each is required. The operator will confirm interconnectedness of sumps and pumps. Drawings available were proposed plans and likely do not represent what is in place. Operator is aware that if the jet pump is pulling from single main drain in basin - that a secondary anti-entrapment device will be required. Prior to purchase and install, the operator will provide the health inspector with the type, make and model of the secondary anti-entrapment device. Pumps:Champion 56 frame (recirc) and B&D BDXBTVAR300. Max flow of each pump separately to be determined. Picture of flow meter provided. Variable speed B&D pump, must be turned to its highest speed and flow measured. Ensure filters backwashed, skimmers turned off to get the reading. 2" lines out sumps for both recirculation and jet pumps. Covers:One cover has been replaced as it was cracked. Certificates of compliance provided for the new one and existing covers. Existing covers expire Sept 16, 2025. New cover will expire October 1, 2030 as there is a 7 year expiry from date of install. Please update new cover date in anti-entrapment plan. Covers are ANSI/APSP-16 compliant. Photo of new cover provided. SumpHayward WG1154AV sumps, and covers are WG1048E with corresponding WG1056C rings. Drawing and photos of sumps provided. No equalizer lines in placeActions: 1) Determine interconnectedness of sumps/pumps. If a single main drain situation exists, secondary anti-entrapment required - must be approved by health inspector prior to purchased and install. 2) Provide drawing that shows current piping schematic from hot tub basin to pump in mechanical room. 3) get max flow rates for each pump independently4) Update anti-entrapment plan and submit to health inspector.
  7. Monitoring Inspection

    2 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • 1. FC was 1.9. Operator adjusted feed and brought FC back within acceptable limits quickly.Water Chemistry: FC 4.2 pH 7.1
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Anti-entrapment plan updates provided, the following is outstanding: Two pumps are included on the plan. Maximum flow rating for each is required. The operator will confirm interconnectedness of sumps and pumps. Drawings available were proposed plans and likely do not represent what is in place. Operator is aware that if the jet pump is pulling from single main drain in basin - that a secondary anti-entrapment device will be required. Prior to purchase and install, the operator will provide the health inspector with the type, make and model of the secondary anti-entrapment device. Pumps:Champion 56 frame (recirc) and B&D BDXBTVAR300. Max flow of each pump separately to be determined. Picture of flow meter provided. Variable speed B&D pump, must be turned to its highest speed and flow measured. Ensure filters backwashed, skimmers turned off to get the reading. 2" lines out sumps for both recirculation and jet pumps. Covers:One cover has been replaced as it was cracked. Certificates of compliance provided for the new one and existing covers. Existing covers expire Sept 16, 2025. New cover will expire October 1, 2030 as there is a 7 year expiry from date of install. Please update new cover date in anti-entrapment plan. Covers are ANSI/APSP-16 compliant. Photo of new cover provided. SumpHayward WG1154AV sumps, and covers are WG1048E with corresponding WG1056C rings. Drawing and photos of sumps provided. No equalizer lines in placeActions: 1) Determine interconnectedness of sumps/pumps. If a single main drain situation exists, secondary anti-entrapment required - must be approved by health inspector prior to purchased and install. 2) Provide drawing that shows current piping schematic from hot tub basin to pump in mechanical room. 3) get max flow rates for each pump independently4) Update anti-entrapment plan and submit to health inspector.
  8. Monitoring Inspection

    1 infraction

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Anti-entrapment plan updates provided, the following is outstanding: Two pumps are included on the plan. Maximum flow rating for each is required. The operator will confirm interconnectedness of sumps and pumps. Drawings available were proposed plans and likely do not represent what is in place. Operator is aware that if the jet pump is pulling from single main drain in basin - that a secondary anti-entrapment device will be required. Prior to purchase and install, the operator will provide the health inspector with the type, make and model of the secondary anti-entrapment device. Pumps:Champion 56 frame (recirc) and B&D BDXBTVAR300. Max flow of each pump separately to be determined. Picture of flow meter provided. Variable speed B&D pump, must be turned to its highest speed and flow measured. Ensure filters backwashed, skimmers turned off to get the reading. 2" lines out sumps for both recirculation and jet pumps. Covers:One cover has been replaced as it was cracked. Certificates of compliance provided for the new one and existing covers. Existing covers expire Sept 16, 2025. New cover will expire October 1, 2030 as there is a 7 year expiry from date of install. Please update new cover date in anti-entrapment plan. Covers are ANSI/APSP-16 compliant. Photo of new cover provided. SumpHayward WG1154AV sumps, and covers are WG1048E with corresponding WG1056C rings. Drawing and photos of sumps provided. No equalizer lines in placeActions: 1) Determine interconnectedness of sumps/pumps. If a single main drain situation exists, secondary anti-entrapment required - must be approved by health inspector prior to purchased and install. 2) Provide drawing that shows current piping schematic from hot tub basin to pump in mechanical room. 3) get max flow rates for each pump independently4) Update anti-entrapment plan and submit to health inspector.
  9. Risk Management Inspection

    1 infraction

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Anti-entrapment plan updates provided, the following is outstanding: Two pumps are included on the plan. Maximum flow rating for each is required. The operator will confirm interconnectedness of sumps and pumps. Drawings available were proposed plans and likely do not represent what is in place. Operator is aware that if the jet pump is pulling from single main drain in basin - that a secondary anti-entrapment device will be required. Prior to purchase and install, the operator will provide the health inspector with the type, make and model of the secondary anti-entrapment device. Pumps:Champion 56 frame (recirc) and B&D BDXBTVAR300. Max flow of each pump separately to be determined. Picture of flow meter provided. Variable speed B&D pump, must be turned to its highest speed and flow measured. Ensure filters backwashed, skimmers turned off to get the reading. 2" lines out sumps for both recirculation and jet pumps. Covers:One cover has been replaced as it was cracked. Certificates of compliance provided for the new one and existing covers. Existing covers expire Sept 16, 2025. New cover will expire October 1, 2030 as there is a 7 year expiry from date of install. Please update new cover date in anti-entrapment plan. Covers are ANSI/APSP-16 compliant. Photo of new cover provided. SumpHayward WG1154AV sumps, and covers are WG1048E with corresponding WG1056C rings. Drawing and photos of sumps provided. No equalizer lines in placeActions: 1) Determine interconnectedness of sumps/pumps. If a single main drain situation exists, secondary anti-entrapment required - must be approved by health inspector prior to purchased and install. 2) Provide drawing that shows current piping schematic from hot tub basin to pump in mechanical room. 3) get max flow rates for each pump independently4) Update anti-entrapment plan and submit to health inspector.
  10. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 1. Routine water sample result: HPC – 220 CFU/ml / PseudomonasClose the pool from public use immediately. Shock chlorinate the pool. After shock chlorinating, backwash the filter. Re-balance the water chemistry to bring the free chlorine level to at least 1.0ppm. The pool can then be re-opened to the public.Resample on your regular sampling day
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Anti-entrapment plan updates provided, the following is outstanding: Two pumps are included on the plan. Maximum flow rating for each is required. The operator will confirm interconnectedness of sumps and pumps. Drawings available were proposed plans and likely do not represent what is in place. Operator is aware that if the jet pump is pulling from single main drain in basin - that a secondary anti-entrapment device will be required. Prior to purchase and install, the operator will provide the health inspector with the type, make and model of the secondary anti-entrapment device. Pumps:Champion 56 frame (recirc) and B&D BDXBTVAR300. Max flow of each pump separately to be determined. Picture of flow meter provided. Variable speed B&D pump, must be turned to its highest speed and flow measured. Ensure filters backwashed, skimmers turned off to get the reading. 2" lines out sumps for both recirculation and jet pumps. Covers:One cover has been replaced as it was cracked. Certificates of compliance provided for the new one and existing covers. Existing covers expire Sept 16, 2025. New cover will expire October 1, 2030 as there is a 7 year expiry from date of install. Please update new cover date in anti-entrapment plan. Covers are ANSI/APSP-16 compliant. Photo of new cover provided. SumpHayward WG1154AV sumps, and covers are WG1048E with corresponding WG1056C rings. Drawing and photos of sumps provided. No equalizer lines in placeActions: 1) Determine interconnectedness of sumps/pumps. If a single main drain situation exists, secondary anti-entrapment required - must be approved by health inspector prior to purchased and install. 2) Provide drawing that shows current piping schematic from hot tub basin to pump in mechanical room. 3) get max flow rates for each pump independently4) Update anti-entrapment plan and submit to health inspector.
  11. Risk Management Inspection

    2 infractions

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Anti-entrapment plan updates provided, the following is outstanding: Two pumps are included on the plan. Maximum flow rating for each is required. The operator will confirm interconnectedness of sumps and pumps. Drawings available were proposed plans and likely do not represent what is in place. Operator is aware that if the jet pump is pulling from single main drain in basin - that a secondary anti-entrapment device will be required. Prior to purchase and install, the operator will provide the health inspector with the type, make and model of the secondary anti-entrapment device. Pumps:Champion 56 frame (recirc) and B&D BDXBTVAR300. Max flow of each pump separately to be determined. Picture of flow meter provided. Variable speed B&D pump, must be turned to its highest speed and flow measured. Ensure filters backwashed, skimmers turned off to get the reading. 2" lines out sumps for both recirculation and jet pumps. Covers:One cover has been replaced as it was cracked. Certificates of compliance provided for the new one and existing covers. Existing covers expire Sept 16, 2025. New cover will expire October 1, 2030 as there is a 7 year expiry from date of install. Please update new cover date in anti-entrapment plan. Covers are ANSI/APSP-16 compliant. Photo of new cover provided. SumpHayward WG1154AV sumps, and covers are WG1048E with corresponding WG1056C rings. Drawing and photos of sumps provided. No equalizer lines in placeActions: 1) Determine interconnectedness of sumps/pumps. If a single main drain situation exists, secondary anti-entrapment required - must be approved by health inspector prior to purchased and install. 2) Provide drawing that shows current piping schematic from hot tub basin to pump in mechanical room. 3) get max flow rates for each pump independently4) Update anti-entrapment plan and submit to health inspector.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is peeling paint on the ceiling and the walls in the pool area due to a roof leak. The windows that separate the pool from the common hallway are cracked. The pool deck is not getting cleaned and sanitized daily. The scum lines are becoming visible in the pool basin. The metal frames on the windows is rusting and staining the walls. There are some missing and cracked tiles in the pool basin.Facility will be closing in the winter for routine maintenance and work will be completed then. Please ensure all work is completed by April 1, 2024. If work is completed before then, let me know and I will do a reinspection sooner.
  12. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 1. Routine water sample result: HPC – 200 CFU/mlClose the pool from public use immediately. Shock chlorinate the pool. After shock chlorinating, backwash the filter. Re-balance the water chemistry to bring the free chlorine level to at least 1.0ppm. The pool can then be re-opened to the public.Resample on your regular sampling day
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Anti-entrapment plan updates provided, the following is outstanding: Two pumps are included on the plan. Maximum flow rating for each is required. The operator will confirm interconnectedness of sumps and pumps. Drawings available were proposed plans and likely do not represent what is in place. Operator is aware that if the jet pump is pulling from single main drain in basin - that a secondary anti-entrapment device will be required. Prior to purchase and install, the operator will provide the health inspector with the type, make and model of the secondary anti-entrapment device. Pumps:Champion 56 frame (recirc) and B&D BDXBTVAR300. Max flow of each pump separately to be determined. Picture of flow meter provided. Variable speed B&D pump, must be turned to its highest speed and flow measured. Ensure filters backwashed, skimmers turned off to get the reading. 2" lines out sumps for both recirculation and jet pumps. Covers:One cover has been replaced as it was cracked. Certificates of compliance provided for the new one and existing covers. Existing covers expire Sept 16, 2025. New cover will expire October 1, 2030 as there is a 7 year expiry from date of install. Please update new cover date in anti-entrapment plan. Covers are ANSI/APSP-16 compliant. Photo of new cover provided. SumpHayward WG1154AV sumps, and covers are WG1048E with corresponding WG1056C rings. Drawing and photos of sumps provided. No equalizer lines in placeActions: 1) Determine interconnectedness of sumps/pumps. If a single main drain situation exists, secondary anti-entrapment required - must be approved by health inspector prior to purchased and install. 2) Provide drawing that shows current piping schematic from hot tub basin to pump in mechanical room. 3) get max flow rates for each pump independently4) Update anti-entrapment plan and submit to health inspector.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is peeling paint on the ceiling and the walls in the pool area due to a roof leak. The windows that separate the pool from the common hallway are cracked. The pool deck is not getting cleaned and sanitized daily. The scum lines are becoming visible in the pool basin. The metal frames on the windows is rusting and staining the walls. There are some missing and cracked tiles in the pool basin.Facility will be closing in the winter for routine maintenance and work will be completed then. Please ensure all work is completed by April 1, 2024. If work is completed before then, let me know and I will do a reinspection sooner.
  13. Risk Management Inspection

    2 infractions

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Anti-entrapment plan updates provided, the following is outstanding: Two pumps are included on the plan. Maximum flow rating for each is required. The operator will confirm interconnectedness of sumps and pumps. Drawings available were proposed plans and likely do not represent what is in place. Operator is aware that if the jet pump is pulling from single main drain in basin - that a secondary anti-entrapment device will be required. Prior to purchase and install, the operator will provide the health inspector with the type, make and model of the secondary anti-entrapment device. Pumps:Champion 56 frame (recirc) and B&D BDXBTVAR300. Max flow of each pump separately to be determined. Picture of flow meter provided. Variable speed B&D pump, must be turned to its highest speed and flow measured. Ensure filters backwashed, skimmers turned off to get the reading. 2" lines out sumps for both recirculation and jet pumps. Covers:One cover has been replaced as it was cracked. Certificates of compliance provided for the new one and existing covers. Existing covers expire Sept 16, 2025. New cover will expire October 1, 2030 as there is a 7 year expiry from date of install. Please update new cover date in anti-entrapment plan. Covers are ANSI/APSP-16 compliant. Photo of new cover provided. SumpHayward WG1154AV sumps, and covers are WG1048E with corresponding WG1056C rings. Drawing and photos of sumps provided. No equalizer lines in placeActions: 1) Determine interconnectedness of sumps/pumps. If a single main drain situation exists, secondary anti-entrapment required - must be approved by health inspector prior to purchased and install. 2) Provide drawing that shows current piping schematic from hot tub basin to pump in mechanical room. 3) get max flow rates for each pump independently4) Update anti-entrapment plan and submit to health inspector.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is peeling paint on the ceiling and the walls in the pool area due to a roof leak. The windows that separate the pool from the common hallway are cracked. The pool deck is not getting cleaned and sanitized daily. The scum lines are becoming visible in the pool basin. The metal frames on the windows is rusting and staining the walls. There are some missing and cracked tiles in the pool basin.Facility will be closing in the winter for routine maintenance and work will be completed then. Please ensure all work is completed by April 1, 2024. If work is completed before then, let me know and I will do a reinspection sooner.
  14. Risk Management Inspection

    2 infractions

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Anti-entrapment plan updates still required. Only 1 recirculation pump is included on the plan, jet pump needs to be included and it needs to be confirmed whether recirc and jet pumps are interconnected. Need to confirm pipe diameter leaving sump and going to pumps. Hayward covers are only rated using a 1.5" to 2" pipe diameter. Need certificates of compliance for covers. Need make and model of sumps - as the Hayward covers are only compatible with Hayward sumps. Updated copies of the anti-entrapment plans are required by October 31, 23Need drawing of pool system including SOFA and pumps interconnectedness, sump dimensions/depth of pipe, size of pipe in sump. Equalizer line covers - what type.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is peeling paint on the ceiling and the walls in the pool area due to a roof leak. The windows that separate the pool from the common hallway are cracked. The pool deck is not getting cleaned and sanitized daily. The scum lines are becoming visible in the pool basin. The metal frames on the windows is rusting and staining the walls. There are some missing and cracked tiles in the pool basin.Facility will be closing in the winter for routine maintenance and work will be completed then. Please ensure all work is completed by April 1, 2024. If work is completed before then, let me know and I will do a reinspection sooner.
  15. Monitoring Inspection

    1 infraction

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is peeling paint on the ceiling and the walls in the pool area due to a roof leak. The windows that separate the pool from the common hallway are cracked. The pool deck is not getting cleaned and sanitized daily. The scum lines are becoming visible in the pool basin. The metal frames on the windows is rusting and staining the walls. There are some missing and cracked tiles in the pool basin.Facility will be closing in the winter for routine maintenance and work will be completed then. Please ensure all work is completed by April 1, 2024. If work is completed before then, let me know and I will do a reinspection sooner.
  16. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Results for sample collected July 19 were: TC absentHPC 1750