Gleniffer Lake Resort - South Outdoor Pool
35468 Range Road 30 Red Deer County AB T0M 1V0 · Aquatic Facility
12 inspections
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- 1. Routine water sample result: HPC – 250 CFU/mlClose the pool from public use immediately. Shock chlorinate the pool. After shock chlorinating, backwash the filter. Re-balance the water chemistry to bring the free chlorine level to at least 1.0ppm. The pool can then be re-opened to the public. Resample on your regular sampling day
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1. The circulation flow rate was too slow to meet the minimum 8 hr time limit. Backwash the filters to allow the circulation flow rate to meet the minimum 8 hr turnover time.Volume: 48500 usgFlow Rate: 82 gpmTurnover: 9.8 hrMinimum Turnover Time: 8 hrMinimum Flow Rate to Achieve Minimum Turnover Time: 101 gpmAn automated control system is installed and functioning.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1.Volume: 48,500 usgFlow Rate: 95 gpmTurnover: 8.5hrMinimum Turnover Time: 6 hrsMinimum Flow to Achieve: 135 gpm An automated control system is installed and functioning.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- 1. Bac-T water sample result: HPC= 130.Check the water chemistry, pH and Free Chlorine are within proscribed limits and retest this week.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Monitoring Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Volume: 30,000 usgFlow Rate: 80 gpmTurnover: 6.25hrMinimum flow rate to meet required 4 hr turnover = 125 gpm.Max Flow Rate: 148 gpmAdjust the flow rate to meet the required turnover time of 4 hours.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- 1. The pool water was cloudy or not sufficiently clear so that the main drains were clearly visible. Close the pool until such time as the water clarity meets the standard as follows: So that the patterns of lines on the pool bottom are clearly visible, or a disc 150 millimetres in diameter placed at the deepest point is clearly visible from any point on the deck 9 meters away.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
0 infractions
- Monitoring Inspection
0 infractions