Holiday Inn Express - Whirlpool

462 Smith Street Hinton AB T7V 2A1 · Aquatic Facility

14 inspections

  1. Monitoring Inspection

    0 infractions

  2. Monitoring Inspection

    0 infractions

  3. Risk Management Inspection

    0 infractions

  4. Monitoring Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • No written policies and plans were available at the time of inspection. The facility also did not have any general sanitation plan, anti-entrapment plan, water quality incident response plan, and safety and supervision plan.Please ensure to send all these documents to the PHI once completed.
  5. Risk Management Inspection

    0 infractions

  6. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter is not in operation. As a result, the turnover period and rate of filtration of the whirlpool are not determined.Please repair or replace the flow meter.
  7. Risk Management Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Bacti water sample submitted more than 24 hours after collection.
  8. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Bacti water sample submitted more than 24 hours after collection.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • pH was measured at 7.68Ensure to lower the pH to between 6.8-7.6
  9. Monitoring Inspection

    1 infraction

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • pH was measured at 7.68Ensure to lower the pH to between 6.8-7.6
  10. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The pressure gauge for the Hot tub sand filter is not functional. Please repair and ensure the pressure gauge is in good repair.
  11. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Unsatisfactory bacteriological water sample, Accession #WE-23-0133014: Pseudomonas aeruginosa isolated. Treat the whirlpool and ensure it is safe prior to reopening of the hot tub.Resample at your earliest convenience once the water chemistry is balanced.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The pressure gauge for the Hot tub sand filter is not functional. Please repair and ensure the pressure gauge is in good repair.
  12. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The pressure gauge for the Hot tub sand filter is not functional. Please repair and ensure the pressure gauge is in good repair.
  13. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The pressure gauge for the Hot tub sand filter is not functional. Please repair and ensure the pressure gauge is in good repair.
  14. Monitoring Inspection

    2 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The pH was tested twice and measured at 7.8 and 8.0.Please adjust the pH so that it is within the acceptable range of 6.8 to 7.6.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Total Alkalinity is 33 ppm.Ensure the Total Alkalinity is maintained between 60 -180 PPM.