Hotel 11 - Pool
11 Freeport Crescent NE Calgary AB T3J 0T4 · Aquatic Facility
17 inspections
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing concern** The flow rate for the pool is too fast. The current flow of 92 USGPM exceeds the maximum rate of filtration.REQUIREMENT: The maximum rate of filtration for a high-rate sand filter must not be greater than 10 liters per second per square meter (15 US gallons per minute per square foot) for swimming pools.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Minor crack observed on the upper left corner of the drain cover.**Please replace the drain cover immediately.**Perform daily visual checks on the drain cover.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample (26ES-131E00028) collected on May 11, 2026, was not processed by the lab as the date/time of sample collection was later than the date/time of receipt.Please submit another water sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing concern** The flow rate for the pool is too fast. The current flow of 92 USGPM exceeds the maximum rate of filtration.REQUIREMENT: The maximum rate of filtration for a high-rate sand filter must not be greater than 10 liters per second per square meter (15 US gallons per minute per square foot) for swimming pools.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Minor crack observed on the upper left corner of the drain cover.**Please replace the drain cover immediately.**Perform daily visual checks on the drain cover.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing concern** The flow rate for the pool is too fast. The current flow of 92 USGPM exceeds the maximum rate of filtration.REQUIREMENT: The maximum rate of filtration for a high-rate sand filter must not be greater than 10 liters per second per square meter (15 US gallons per minute per square foot) for swimming pools.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Minor crack observed on the upper left corner of the drain cover.**Please replace the drain cover immediately.**Perform daily visual checks on the drain cover.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample (26ES-041E00809) collected on February 10, 2026, was not processed by the lab as the sample collection was later than the date/time of receipt on the requisition form.Please submit another water sample for the swimming pool.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing concern** The flow rate for the pool is too fast. The current flow of 92 USGPM exceeds the maximum rate of filtration.REQUIREMENT: The maximum rate of filtration for a high-rate sand filter must not be greater than 10 liters per second per square meter (15 US gallons per minute per square foot) for swimming pools.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Minor crack observed on the upper left corner of the drain cover.**Please replace the drain cover immediately.**Perform daily visual checks on the drain cover.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing concern** The flow rate for the pool is too fast. The current flow of 92 USGPM exceeds the maximum rate of filtration.REQUIREMENT: The maximum rate of filtration for a high-rate sand filter must not be greater than 10 liters per second per square meter (15 US gallons per minute per square foot) for swimming pools.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Minor crack observed on the upper left corner of the drain cover.**Please replace the drain cover immediately.**Perform daily visual checks on the drain cover.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sample ID 25ES-322E00758The Date/Time of sample collection is LATER than the Date/Time of receipt.Resampling advised.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing concern** The flow rate for the pool is too fast. The current flow of 92 USGPM exceeds the maximum rate of filtration.REQUIREMENT: The maximum rate of filtration for a high-rate sand filter must not be greater than 10 liters per second per square meter (15 US gallons per minute per square foot) for swimming pools.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Minor crack observed on the upper left corner of the drain cover.**Please replace the drain cover immediately.**Perform daily visual checks on the drain cover.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing concern** The flow rate for the pool is too fast. The current flow of 92 USGPM exceeds the maximum rate of filtration.REQUIREMENT: The maximum rate of filtration for a high-rate sand filter must not be greater than 10 liters per second per square meter (15 US gallons per minute per square foot) for swimming pools.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Minor crack observed on the upper left corner of the drain cover.**Please replace the drain cover immediately.**Perform daily visual checks on the drain cover.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on August 5, 2025, was not tested as there was no identification number present on the bottle.**Please resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing concern** The flow rate for the pool is too fast. The current flow of 92 USGPM exceeds the maximum rate of filtration.REQUIREMENT: The maximum rate of filtration for a high-rate sand filter must not be greater than 10 liters per second per square meter (15 US gallons per minute per square foot) for swimming pools.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Minor crack observed on the upper left corner of the drain cover.**Please replace the drain cover immediately.**Perform daily visual checks on the drain cover.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing concern** The flow rate for the pool is too fast. The current flow of 92 USGPM exceeds the maximum rate of filtration.REQUIREMENT: The maximum rate of filtration for a high-rate sand filter must not be greater than 10 liters per second per square meter (15 US gallons per minute per square foot) for swimming pools.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Minor crack observed on the upper left corner of the drain cover.**Please replace the drain cover immediately.**Perform daily visual checks on the drain cover.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sample collected on May 27, 2025, was not tested as there was no identification number on the bottle.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing concern** The flow rate for the pool is too fast. The current flow of 112 USGPM exceeds the maximum rate of filtration.REQUIREMENT: The maximum rate of filtration for a high-rate sand filter must not be greater than 10 liters per second per square meter (15 US gallons per minute per square foot) for swimming pools.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on September 04, 2024, had an HPC Count of 750 CFU/mL in the sample.REQUIREMENT: Begin treatment for the swimming pool; Submit a re-sample after you complete necessary treatments and the water chemistry is rebalanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sample collected on October 8, 2024, was not processed because it was received more than 24 hours after collection.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing concern** The flow rate for the pool is too fast. The current flow of 112 USGPM exceeds the maximum rate of filtration.REQUIREMENT: The maximum rate of filtration for a high-rate sand filter must not be greater than 10 liters per second per square meter (15 US gallons per minute per square foot) for swimming pools.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on September 04, 2024, had an HPC Count of 750 CFU/mL in the sample.REQUIREMENT: Begin treatment for the swimming pool; Submit a re-sample after you complete necessary treatments and the water chemistry is rebalanced.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing concern** The flow rate for the pool is too fast. The current flow of 112 USGPM exceeds the maximum rate of filtration.REQUIREMENT: The maximum rate of filtration for a high-rate sand filter must not be greater than 10 liters per second per square meter (15 US gallons per minute per square foot) for swimming pools.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing concern** The flow rate for the pool is too fast. The current flow of 112 USGPM exceeds the maximum rate of filtration.REQUIREMENT: The maximum rate of filtration for a high-rate sand filter must not be greater than 10 liters per second per square meter (15 US gallons per minute per square foot) for swimming pools.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on May 07, 2024, had an HPC count of 900 CFU/mL.REQUIREMENT: Begin treatment for the pool. Collect and send a re-sample after you complete necessary treatments, and the water chemistry is balanced. Indicate on the requisition form that the sample is a ‘resample’.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing concern** The flow rate for the pool is too fast. The current flow of 120 USGPM exceeds the maximum rate of filtration.REQUIREMENT: The maximum rate of filtration for a high-rate sand filter must not be greater than 10 liters per second per square meter (15 US gallons per minute per square foot) for swimming pools.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing concern** The flow rate for the pool is too fast. The current flow of 120 USGPM exceeds the maximum rate of filtration.REQUIREMENT: The maximum rate of filtration for a high-rate sand filter must not be greater than 10 liters per second per square meter (15 US gallons per minute per square foot) for swimming pools.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on October 10, 2023, had HPC detected at 220 CFU/mL.REQUIREMENT: Review the water chemistry for the swimming pool and balance as needed. Send in a re-sample for the main pool.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate for the pool is too fast. The current flow of 90 USGPM exceeds the maximum rate of filtration.REQUIREMENT: The maximum rate of filtration for a high-rate sand filter must not be greater than 10 liters per second per square meter (15 US gallons per minute per square foot) for swimming pools.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on September 26, 2023, had HPC detected at 4120 CFU/mL.REQUIREMENT: Review the water chemistry for the swimming pool and balance as needed. An immediate re-sample is not required for the main pool at this time.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate for the pool is too fast. The current flow of 90 USGPM exceeds the maximum rate of filtration.REQUIREMENT: The maximum rate of filtration for a high-rate sand filter must not be greater than 10 liters per second per square meter (15 US gallons per minute per square foot) for swimming pools.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?