Kananaskis Nordic Spa - Elements Pool

1 Centennial Drive Kananaskis Village AB T0L 2H0 · Aquatic Facility

16 inspections

  1. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted on July 10, 2026 had a heterotrophic plate count of 180 cfu/ml. In speaking with pool operator, pool water had already been treated. New water sample to be submitted.
  2. Risk Management Inspection

    0 infractions

  3. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample taken on January 19, 2026 had a plate count of 110cfu/ml. Treat water to remove contamination. Resample.
  4. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample taken on January 14, 2026 had Pseudomonas present. Close pool until treatment is done to remove contamination. Submit a resample.
  5. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted on October 3, 2025 was not tested as it was received by the lab after it had closed for the weekend. New sample to be submitted.
  6. Risk Management Inspection

    0 infractions

  7. Monitoring Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan could not be located. Written anti-entrapment plan required.
  8. Demand Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • March 7, 2025 water sample was not tested as it was not received by the Lab prior to the Lab closing for the weekend. Resample to be submitted.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured as 38ppm. Please keep alkalinity between 60-180ppm.
    • 08. Does food preparation and consumption take place away from the pool?
      • There were bathers that were sitting in the pool drinking beverages from the restaurant on-site. Consumption is to be in a designated area away from the pool(s). Signage will need be moved to NOT include a consumption area around the pools.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan could not be located. Written anti-entrapment plan required.
  9. Demand Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured as 38ppm. Please keep alkalinity between 60-180ppm.
    • 08. Does food preparation and consumption take place away from the pool?
      • There were bathers that were sitting in the pool drinking beverages from the restaurant on-site. Consumption is to be in a designated area away from the pool(s). Signage will need be moved to NOT include a consumption area around the pools.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan could not be located. Written anti-entrapment plan required.
  10. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan could not be located. Written anti-entrapment plan required.
  11. Demand Inspection

    2 infractions

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • One of the main drain covers was cracked. Pool not to be opened back up to the public until a new (undamaged) cover is installed.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan could not be located. Written anti-entrapment plan required.
  12. Risk Management Inspection

    0 infractions

  13. Monitoring Inspection

    2 infractions

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Some of the circular weirs were not sitting properly in skimmer basket and/or skimmer basket was not sitting properly in the skimmer assembly. Corrected during inspection but please ensure these are checked regularly to ensure they are in the proper position for optimal skimming action.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan could not be located. Written anti-entrapment plan required.
  14. Demand Inspection

    5 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample taken on April 1/24 had Pseudomonas isolated. Pool is to be immediately close and treated to remove contamination and may not reopen until a new water sample is submitted that is confirmed to be satisfactory.
    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample taken on March 21/24 has Pseudomonas isolated. Treat water to remove contamination.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample taken on April 1/24 had a plate count of 1000cfu/ml. Pool to be closed, treated and may not reopen until a new water sample is taken that is confirmed to be satisfactory.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample taken and dropped off at lab on March 29/24 when it was closed (for stat holiday) so sample was not tested. Resample to be submitted.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • Flow rate for the pool could not be determined as the flow meter not functional. Ensure a functional and accurate flow meter is installed and that the flow rate for the pool is kept between 32-106gpm.
  15. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample taken on March 21/24 has Pseudomonas isolated. Treat water to remove contamination.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample taken and dropped off at lab on March 29/24 when it was closed (for stat holiday) so sample was not tested. Resample to be submitted.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • Flow rate for the pool could not be determined as the flow meter not functional. Ensure a functional and accurate flow meter is installed and that the flow rate for the pool is kept between 32-106gpm.
  16. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample taken on March 21/24 has Pseudomonas isolated. Treat water to remove contamination.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • Flow rate for the pool could not be determined as the flow meter not functional. Ensure a functional and accurate flow meter is installed and that the flow rate for the pool is kept between 32-106gpm.