Skip to content
Loading map…

Kananaskis Nordic Spa - Gathering Pool

1 Centennial Drive Kananaskis Village AB T0L 2H0 · Aquatic Facility

25 inspections

  1. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan to be updated indicating VSD was installed.
  2. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted on December 22, 2025 had a heterotrophic plate count of 770 cfu/ml. Treat water to remove contamination. Resample.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan to be updated indicating VSD was installed.
  3. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan to be updated indicating VSD was installed.
  4. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan to be updated indicating VSD was installed.
  5. Demand Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted on October 3, 2025 was not tested as it was received by the lab after it had closed for the weekend. New sample to be submitted.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Skimmers for the lower level of the pool that was advised are functional don't appear to have good flow through them. Please ensure these skimmers are skimming adequately.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • As system is capable of exceeding a flow rate of 398gpm, written plans/procedures need to be in place to ensure that 398gpm is not exceeded. This information needs to be communicated to all pool operators. Was advised variable speed device will be installed.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan could not be located. Written anti-entrapment plan required.
  6. Demand Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample from Friday August 15th, 2025, had an HPC of 190 CFU/ml. - Operators were informed to treat and re-sample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Skimmers for the lower level of the pool that was advised are functional don't appear to have good flow through them. Please ensure these skimmers are skimming adequately.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • As system is capable of exceeding a flow rate of 398gpm, written plans/procedures need to be in place to ensure that 398gpm is not exceeded. This information needs to be communicated to all pool operators. Was advised variable speed device will be installed.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan could not be located. Written anti-entrapment plan required.
  7. Monitoring Inspection

    3 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Skimmers for the lower level of the pool that was advised are functional don't appear to have good flow through them. Please ensure these skimmers are skimming adequately.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • As system is capable of exceeding a flow rate of 398gpm, written plans/procedures need to be in place to ensure that 398gpm is not exceeded. This information needs to be communicated to all pool operators. Was advised variable speed device will be installed.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan could not be located. Written anti-entrapment plan required.
  8. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • March 7, 2025 water sample was not tested as it was not received by the Lab prior to the Lab closing for the weekend. Resample to be submitted.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The main drain valve and the skimmer valve are both 50% open. Are to maximize water removal through the skimmers.There are only about 9 skimmers that don't appear to have good flow through them or are not being used. Based on flow rate, need 9 working skimmers, only about 7 appeared to be working adequately at this time.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan could not be located. Written anti-entrapment plan required.
  9. Demand Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The main drain valve and the skimmer valve are both 50% open. Are to maximize water removal through the skimmers.There are only about 9 skimmers that don't appear to have good flow through them or are not being used. Based on flow rate, need 9 working skimmers, only about 7 appeared to be working adequately at this time.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan could not be located. Written anti-entrapment plan required.
  10. Risk Management Inspection

    2 infractions

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • A couple of the skimmers had a circular weir missing or the weir was not sitting properly in the skimmer assembly (bottom part of pool). Please ensure all skimmer have weirs and that they are sitting properly in the skimmer assembly for optimal skimming action. Also ensure that there is good flow from the skimmers in the bottom part of the pool, not just the top area.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan could not be located. Written anti-entrapment plan required.Now that pool is classified as a swimming pool (not a whirlpool), the batherload based on surface area should only be 58, not 87. Please change on signage.
  11. Risk Management Inspection

    3 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was not functional.- Please repair or replace the flow meter to determine the flow rate and ensure turnover and filtration rates are being met.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • A couple of the skimmers had a circular weir missing or the weir was not sitting properly in the skimmer assembly (bottom part of pool). Please ensure all skimmer have weirs and that they are sitting properly in the skimmer assembly for optimal skimming action. Also ensure that there is good flow from the skimmers in the bottom part of the pool, not just the top area.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan could not be located. Written anti-entrapment plan required.Now that pool is classified as a swimming pool (not a whirlpool), the batherload based on surface area should only be 58, not 87. Please change on signage.
  12. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample from Thursday June 27th, 2024, had pseudomonas isolated. - Operators were informed to treat and re-sample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was not functional.- Please repair or replace the flow meter to determine the flow rate and ensure turnover and filtration rates are being met.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • A couple of the skimmers had a circular weir missing or the weir was not sitting properly in the skimmer assembly (bottom part of pool). Please ensure all skimmer have weirs and that they are sitting properly in the skimmer assembly for optimal skimming action. Also ensure that there is good flow from the skimmers in the bottom part of the pool, not just the top area.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan could not be located. Written anti-entrapment plan required.Now that pool is classified as a swimming pool (not a whirlpool), the batherload based on surface area should only be 58, not 87. Please change on signage.
  13. Demand Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • May 10/24 water sample was not processed as there was no time of collection on the requisition form and id# sticker on the bottle. Resample to be taken.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was not functional.- Please repair or replace the flow meter to determine the flow rate and ensure turnover and filtration rates are being met.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • A couple of the skimmers had a circular weir missing or the weir was not sitting properly in the skimmer assembly (bottom part of pool). Please ensure all skimmer have weirs and that they are sitting properly in the skimmer assembly for optimal skimming action. Also ensure that there is good flow from the skimmers in the bottom part of the pool, not just the top area.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan could not be located. Written anti-entrapment plan required.Now that pool is classified as a swimming pool (not a whirlpool), the batherload based on surface area should only be 58, not 87. Please change on signage.
  14. Risk Management Inspection

    3 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was not functional.- Please repair or replace the flow meter to determine the flow rate and ensure turnover and filtration rates are being met.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • A couple of the skimmers had a circular weir missing or the weir was not sitting properly in the skimmer assembly (bottom part of pool). Please ensure all skimmer have weirs and that they are sitting properly in the skimmer assembly for optimal skimming action. Also ensure that there is good flow from the skimmers in the bottom part of the pool, not just the top area.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan could not be located. Written anti-entrapment plan required.Now that pool is classified as a swimming pool (not a whirlpool), the batherload based on surface area should only be 58, not 87. Please change on signage.
  15. Demand Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted on May 6, 2024 was not tested as there was insufficient information on the requisition form to verify the sample. Resample to be submitted.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was not functional.- Please repair or replace the flow meter to determine the flow rate and ensure turnover and filtration rates are being met.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • A couple of the skimmers had a circular weir missing or the weir was not sitting properly in the skimmer assembly (bottom part of pool). Please ensure all skimmer have weirs and that they are sitting properly in the skimmer assembly for optimal skimming action. Also ensure that there is good flow from the skimmers in the bottom part of the pool, not just the top area.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan could not be located. Written anti-entrapment plan required.Now that pool is classified as a swimming pool (not a whirlpool), the batherload based on surface area should only be 58, not 87. Please change on signage.
  16. Risk Management Inspection

    3 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was not functional.- Please repair or replace the flow meter to determine the flow rate and ensure turnover and filtration rates are being met.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • A couple of the skimmers had a circular weir missing or the weir was not sitting properly in the skimmer assembly (bottom part of pool). Please ensure all skimmer have weirs and that they are sitting properly in the skimmer assembly for optimal skimming action. Also ensure that there is good flow from the skimmers in the bottom part of the pool, not just the top area.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan could not be located. Written anti-entrapment plan required.Now that pool is classified as a swimming pool (not a whirlpool), the batherload based on surface area should only be 58, not 87. Please change on signage.
  17. Demand Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample taken on April 18, 2024 had a heterotrophic plate count of 160 cfu/ml.Treat water to remove contamination and resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was not functional.- Please repair or replace the flow meter to determine the flow rate and ensure turnover and filtration rates are being met.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • A couple of the skimmers had a circular weir missing or the weir was not sitting properly in the skimmer assembly (bottom part of pool). Please ensure all skimmer have weirs and that they are sitting properly in the skimmer assembly for optimal skimming action. Also ensure that there is good flow from the skimmers in the bottom part of the pool, not just the top area.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan could not be located. Written anti-entrapment plan required.Now that pool is classified as a swimming pool (not a whirlpool), the batherload based on surface area should only be 58, not 87. Please change on signage.
  18. Risk Management Inspection

    3 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was not functional.- Please repair or replace the flow meter to determine the flow rate and ensure turnover and filtration rates are being met.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • A couple of the skimmers had a circular weir missing or the weir was not sitting properly in the skimmer assembly (bottom part of pool). Please ensure all skimmer have weirs and that they are sitting properly in the skimmer assembly for optimal skimming action. Also ensure that there is good flow from the skimmers in the bottom part of the pool, not just the top area.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan could not be located. Written anti-entrapment plan required.Now that pool is classified as a swimming pool (not a whirlpool), the batherload based on surface area should only be 58, not 87. Please change on signage.
  19. Monitoring Inspection

    6 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample taken on March 21/24 had a plate count of 1240cfu/ml. Treat water to remove contamination.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • April 1/24 water sample had a plate count of 300cfu/ml. Treat water to remove contamination and submit a resample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample taken on April 4/24 had a plate count of 120 cfu/ml. Treat water to remove contamination and resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was not functional.- Please repair or replace the flow meter to determine the flow rate and ensure turnover and filtration rates are being met.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • A couple of the skimmers had a circular weir missing or the weir was not sitting properly in the skimmer assembly (bottom part of pool). Please ensure all skimmer have weirs and that they are sitting properly in the skimmer assembly for optimal skimming action. Also ensure that there is good flow from the skimmers in the bottom part of the pool, not just the top area.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan could not be located. Written anti-entrapment plan required.Now that pool is classified as a swimming pool (not a whirlpool), the batherload based on surface area should only be 58, not 87. Please change on signage.
  20. Demand Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample taken on April 4/24 had a plate count of 120 cfu/ml. Treat water to remove contamination and resample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample taken on March 21/24 had a plate count of 1240cfu/ml. Treat water to remove contamination.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • April 1/24 water sample had a plate count of 300cfu/ml. Treat water to remove contamination and submit a resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was not functional.- Please repair or replace the flow meter to determine the flow rate and ensure turnover and filtration rates are being met.
  21. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • April 1/24 water sample had a plate count of 300cfu/ml. Treat water to remove contamination and submit a resample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample taken on March 21/24 had a plate count of 1240cfu/ml. Treat water to remove contamination.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was not functional.- Please repair or replace the flow meter to determine the flow rate and ensure turnover and filtration rates are being met.
  22. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample taken and dropped off at lab on March 29/24 when it was closed (for stat holiday) so sample was not tested. Resample to be submitted.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample taken on March 21/24 had a plate count of 1240cfu/ml. Treat water to remove contamination.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was not functional.- Please repair or replace the flow meter to determine the flow rate and ensure turnover and filtration rates are being met.
  23. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample taken on March 21/24 had a plate count of 1240cfu/ml. Treat water to remove contamination.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was not functional.- Please repair or replace the flow meter to determine the flow rate and ensure turnover and filtration rates are being met.
  24. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was not functional.- Please repair or replace the flow meter to determine the flow rate and ensure turnover and filtration rates are being met.
  25. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was broken and was not giving a reading. - Please repair or replace the flow meter to determine the flow rate and ensure turnover and filtration rates are being met.