Kananaskis Nordic Spa - Reflection Pool

1 Centennial Drive Kananaskis Village AB T0L 2H0 · Aquatic Facility

27 inspections

  1. Risk Management Inspection

    0 infractions

  2. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted on October 3, 2025 was not tested as it was received by the lab after it had closed for the weekend. New sample to be submitted.
  3. Risk Management Inspection

    0 infractions

  4. Risk Management Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured as 33ppm; to be kept between 60 and 180ppm.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Some of the skimmer baskets need cleaning and some circular weirs are not properly situated for skimming. Please clean the skimmer baskets and ensure the circular weirs are sitting properly in the baskets for skimming.
  5. Monitoring Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured as 33ppm; to be kept between 60 and 180ppm.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Some of the skimmer baskets need cleaning and some circular weirs are not properly situated for skimming. Please clean the skimmer baskets and ensure the circular weirs are sitting properly in the baskets for skimming.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plans could not be located. Written anti-entrapment plan required.
  6. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • March 7, 2025 water sample was not tested as it was not received by the Lab prior to the Lab closing for the weekend. Resample to be submitted.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plans could not be located. Written anti-entrapment plan required.
  7. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plans could not be located. Written anti-entrapment plan required.
  8. Demand Inspection

    2 infractions

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Float appears to be stuck in flow meter so reading may not be accurate. Ensure flow meter is functional and accurate.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plans could not be located. Written anti-entrapment plan required.
  9. Risk Management Inspection

    2 infractions

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Float appears to be stuck in flow meter so reading may not be accurate. Ensure flow meter is functional and accurate.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plans could not be located. Written anti-entrapment plan required.
  10. Risk Management Inspection

    2 infractions

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Float appears to be stuck in flow meter so reading may not be accurate. Ensure flow meter is functional and accurate.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plans could not be located. Written anti-entrapment plan required.
  11. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample from Thursday June 24th, 2024, had Pseudomonas isolated. - Operators were informed to treat and re-sample.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Float appears to be stuck in flow meter so reading may not be accurate. Ensure flow meter is functional and accurate.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plans could not be located. Written anti-entrapment plan required.
  12. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • May 10/24 water sample was not processed as there was no time of collection on the requisition form and no id# sticker on the bottle. Resample to be taken.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Float appears to be stuck in flow meter so reading may not be accurate. Ensure flow meter is functional and accurate.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plans could not be located. Written anti-entrapment plan required.
  13. Risk Management Inspection

    2 infractions

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Float appears to be stuck in flow meter so reading may not be accurate. Ensure flow meter is functional and accurate.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plans could not be located. Written anti-entrapment plan required.
  14. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • May 3, 2024 water sample was not tested as there was insufficient information to verify the sample on the requisition form. Resample to be submitted.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Float appears to be stuck in flow meter so reading may not be accurate. Ensure flow meter is functional and accurate.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plans could not be located. Written anti-entrapment plan required.
  15. Risk Management Inspection

    2 infractions

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Float appears to be stuck in flow meter so reading may not be accurate. Ensure flow meter is functional and accurate.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plans could not be located. Written anti-entrapment plan required.
  16. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample taken on April 18, 2024 had a heterotrophic plate count of 120 cfu/ml.Treat water to remove contamination and resample.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Float appears to be stuck in flow meter so reading may not be accurate. Ensure flow meter is functional and accurate.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plans could not be located. Written anti-entrapment plan required.
  17. Risk Management Inspection

    2 infractions

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Float appears to be stuck in flow meter so reading may not be accurate. Ensure flow meter is functional and accurate.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plans could not be located. Written anti-entrapment plan required.
  18. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • April 4/24 water sample had a plate count of 290 cfu/ml. Treat water to remove contamination and resample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • March 21/24 water sample had a plate count of over 57,000cfu/ml. Treat water to remove contamination.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • April 1/24 water sample had a plate count of 860cfu/ml. Treat water to remove contamination and submit a resample.
  19. Monitoring Inspection

    5 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • March 21/24 water sample had a plate count of over 57,000cfu/ml. Treat water to remove contamination.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • April 1/24 water sample had a plate count of 860cfu/ml. Treat water to remove contamination and submit a resample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • April 4/24 water sample had a plate count of 290 cfu/ml. Treat water to remove contamination and resample.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Float appears to be stuck in flow meter so reading may not be accurate. Ensure flow meter is functional and accurate.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plans could not be located. Written anti-entrapment plan required.
  20. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • April 1/24 water sample had a plate count of 860cfu/ml. Treat water to remove contamination and submit a resample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • March 21/24 water sample had a plate count of over 57,000cfu/ml. Treat water to remove contamination.
  21. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • March 21/24 water sample had Pseudomonas isolated. Treat water to remove contamination.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample taken and dropped off at lab on March 29/24 when it was closed (for stat holiday) so sample was not tested. Resample to be submitted.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • March 21/24 water sample had a plate count of over 57,000cfu/ml. Treat water to remove contamination.
  22. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • March 21/24 water sample had Pseudomonas isolated. Treat water to remove contamination.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • March 21/24 water sample had a plate count of over 57,000cfu/ml. Treat water to remove contamination.
  23. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Oct. 18/23 water sample had a plate count of 110cfu/ml. Treat water to remove contamination.
  24. Risk Management Inspection

    0 infractions

  25. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The left skimmer next to the stairs is not pulling in water properly. Flow is very weak. - Repair the skimmer to improve the flow and water circulation of the pool.
  26. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Aug. 17/23 water sample had a plate count of 310cfu/ml. Treat water to remove contamination.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • Due to several braziers wood-burning fire pits surrounding the pool, a lot of ash was getting into the pool which can affect the water chemistry and use of chlorine. Remove/reduce/relocate braziers to prevent ash getting into the pool.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Flow meter that was installed was for 6" pipe but the pipe diameter was only 2" so not accurate flow rate. Install a functional and accurate flow meter so the flow rate for the pool can be determined.
  27. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • July 25/23 water sample had a plate count of 320cfu/ml. Treat water to remove contamination.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • Due to several braziers wood-burning fire pits surrounding the pool, a lot of ash was getting into the pool which can affect the water chemistry and use of chlorine. Remove/reduce/relocate braziers to prevent ash getting into the pool.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Flow meter that was installed was for 6" pipe but the pipe diameter was only 2" so not accurate flow rate. Install a functional and accurate flow meter so the flow rate for the pool can be determined.