Lamphouse Hotel - Whirlpool
610 8 Street Canmore AB T1W 2B5 · Aquatic Facility
Inspection summary
Lamphouse Hotel - Whirlpool has been inspected 16 times by Alberta Health Services (Environmental Public Health) since June 25, 2024. The most recent inspection, on August 4, 2026, recorded 1 infraction.
1 of 16 inspections on record found no infractions at all. In the past 12 months there were 7 inspections with 12 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality.
The number of infractions per inspection has stayed roughly the same over time.
What these findings mean
Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.
Pool and spa water qualityHigher risk
For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.
Recorded 23 times across 15 separate inspections, most recently on August 4, 2026. For example:
Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
Food safety training and certificationLower risk
Many jurisdictions require trained pool operators and certified lifeguards. These findings mean required training, certification or staffing records were missing at the time of inspection.
Recorded 4 times across 4 separate inspections, most recently on August 19, 2025. For example:
Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
About this data
These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.
16 inspections
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate exceeded max flow rate of 61GPM, flow meter was reading 70 GPM. Filtration rate was 14.3 GPM/sqft. Requirement:- Please adjust flow rate so it does not exceed the max flow rate for the filter.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample taken on July 13, 2026 had total coliforms isolated. Treat water to remove contamination; submit a new sample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample taken on July 20, 2026 was not tested as there was no time of collection on the requisition form. New sample to be submitted this week.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate exceeded max flow rate of 61GPM, flow meter was reading 70 GPM. Filtration rate was 14.3 GPM/sqft. Requirement:- Please adjust flow rate so it does not exceed the max flow rate for the filter.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample taken on July 13, 2026 had total coliforms isolated. Treat water to remove contamination; submit a new sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate exceeded max flow rate of 61GPM, flow meter was reading 70 GPM. Filtration rate was 14.3 GPM/sqft. Requirement:- Please adjust flow rate so it does not exceed the max flow rate for the filter.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate exceeded max flow rate of 61GPM, flow meter was reading 70 GPM. Filtration rate was 14.3 GPM/sqft. Requirement:- Please adjust flow rate so it does not exceed the max flow rate for the filter.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample taken on February 23, 2026 had total coliforms present. Treat water to remove contamination. Resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate exceeded max flow rate of 61GPM, flow meter was reading 70 GPM. Filtration rate was 14.3 GPM/sqft. Requirement:- Please adjust flow rate so it does not exceed the max flow rate for the filter.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate exceeded max flow rate of 61GPM, flow meter was reading 70 GPM. Filtration rate was 14.3 GPM/sqft. Requirement:- Please adjust flow rate so it does not exceed the max flow rate for the filter.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample taken on February 9, 2026 had total coliforms present. Treat water to remove contamination. Resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate exceeded max flow rate of 61GPM, flow meter was reading 70 GPM. Filtration rate was 14.3 GPM/sqft. Requirement:- Please adjust flow rate so it does not exceed the max flow rate for the filter.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate exceeded max flow rate of 61GPM, flow meter was reading 70 GPM. Filtration rate was 14.3 GPM/sqft. Requirement:- Please adjust flow rate so it does not exceed the max flow rate for the filter.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- August 11, 2025 water sample had a plate count of 430cfu/ml. Treat water to remove contamination. Resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate exceeded max flow rate of 61GPM, flow meter was reading 70 GPM. Filtration rate was 14.3 GPM/sqft. Requirement:- Please adjust flow rate so it does not exceed the max flow rate for the filter.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- New anti-entrapment plans were submitted; correction needed on plan for the jet suction outlets. Please correct and resend.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- August 11, 2025 water sample had a plate count of 430cfu/ml. Treat water to remove contamination. Resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate exceeded max flow rate of 61GPM, flow meter was reading 70 GPM. Filtration rate was 14.3 GPM/sqft. Requirement:- Please adjust flow rate so it does not exceed the max flow rate for the filter.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The anti-entrapment plan was not completed properly.-Submit an appropriately completed anti-entrapment plan.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate exceeded max flow rate of 61GPM, flow meter was reading 70 GPM. Filtration rate was 14.3 GPM/sqft. Requirement:- Please adjust flow rate so it does not exceed the max flow rate for the filter.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The anti-entrapment plan was not completed properly.-Submit an appropriately completed anti-entrapment plan.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate exceeded max flow rate of 61GPM, flow meter was reading 70 GPM. Filtration rate was 14.3 GPM/sqft. Requirement:- Please adjust flow rate so it does not exceed the max flow rate for the filter.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- The jet suction outlet covers have expired.RequirementReplace all expired suction outlet covers.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The anti-entrapment plan was not completed properly.-Submit an appropriately completed anti-entrapment plan.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample from Monday September 23rd, 2024, had pseudomonas isolated. - Operators were informed to treat and re-sample.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sample not processed (Aug 6, 2024) incorrect date on the form. Submit re-sample on Thursday.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sample not processed (June 24, 2024) the sample was missing ID number on the bottle. Submit re-sample on Thursday.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?