Landmark Of Thornhill 2 - YRCC 794
7825 Bayview Avenue, Markham, ON L3T 7N2 · Class B, Whirlpool/Spa
12 inspections
- Compliance Inspection
0 infractions
- Compliance Inspection
0 infractions
- Compliance Inspection
2 infractions
- Total bromine residual is within required range
- Fail to maintain total bromine residual between 5 - 10 ppm (Spa, Wading Pool, Hot Water Pool)
- Daily records completed and signed
- Fail to record any emergencies, rescues or breakdowns of equipment
- Fail to record TA, pH, FAC, TC or TBr, water clarity and water temperature (Spa, Hot Water Pool) 30 minutes before opening the facility
- Fail to record TA, pH, FAC, TC or TBr, water clarity and water temperature (Spa, Hot Water Pool) at least every 4 hours during daily use period where automatic sensing device is used
- Fail to record results of the emergency telephone test and time of day test was performed
- Fail to record type and amount of any chemicals added manually to facility unit
- Total bromine residual is within required range
- Compliance Inspection
0 infractions
- Compliance Inspection
0 infractions
- Re-inspection
0 infractions
- Compliance Inspection
4 infractions
- Total alkalinity is within required range
- Fail to maintain total alkalinity within range of 60 mg/L to 180 mg/L
- pH is within range of 7.2 to 7.8
- Fail to maintain pH within range of 7.2 to 7.8
- Total bromine residual is within required range
- Fail to maintain total bromine residual between 5 - 10 mg/L
- The premise appears to be free from conditions that might be a health hazard
- Fail to maintain facility in safe condition
- Total alkalinity is within required range
- Re-inspection
0 infractions
- Compliance Inspection
3 infractions
- Total alkalinity is within required range
- Fail to maintain total alkalinity within range of 60 mg/L to 180 mg/L
- Total bromine residual is within required range
- Fail to maintain total bromine residual between 5 - 10 mg/L
- Daily records completed and signed
- Fail to record TA, pH, FAC, TC or TBr, water clarity and water temperature (Spa) at least every 4 hours during daily use period where automatic sensing device is used
- Total alkalinity is within required range
- Compliance Inspection
1 infraction
- Total alkalinity is within range of 80 mg/L to 120 mg/L
- Fail to maintain total alkalinity within range of 80 mg/L to 120 mg/L
- Total alkalinity is within range of 80 mg/L to 120 mg/L
- Compliance Inspection
0 infractions
- Compliance Inspection
0 infractions