Skip to content
Loading map…

Miette Hot Springs - Hot Pool Shallow

Miette Road Jasper AB T0E 1E0 · Aquatic Facility

14 inspections

  1. Monitoring Inspection

    0 infractions

  2. Demand Inspection

    0 infractions

  3. Risk Management Inspection

    0 infractions

  4. Demand Inspection

    3 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • Free chlorine in the pool water is too low. - Increase free chlorine to 2 ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate reading was not available as the pump was shut down during inspection.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The anti-entrapment plan is to be updated as the system's flow rate has changed after the system upgrade.
  5. Risk Management Inspection

    0 infractions

  6. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on Jul 9 is reported unsatisfactory, with HPC >100 CFU/ml.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The skimmer weir doors are missing. Reinstallation of the weir doors is required to ensure contaminants flow into the skimmers, not to flow back to pool. Circular floating weirs can be installed instead of the flap weir doors.
  7. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The skimmer weir doors are missing. Reinstallation of the weir doors is required to ensure contaminants flow into the skimmers, not to flow back to pool. Circular floating weirs can be installed instead of the flap weir doors.
  8. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample collected on Jun 24 is reported unsatisfactory. - A thorough system check is required.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The skimmer weir doors are missing. Reinstallation of the weir doors is required to ensure contaminants flow into the skimmers, not to flow back to pool. Circular floating weirs can be installed instead of the flap weir doors.
  9. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The skimmer weir doors are missing. Reinstallation of the weir doors is required to ensure contaminants flow into the skimmers, not to flow back to pool. Circular floating weirs can be installed instead of the flap weir doors.
  10. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Pool water sample collected on May 27 is reported unsatisfactory with HPC > 100 CFU/ml. ** June 07,2024 - Unsatisfactory water report was received. Water sample collected on June 04,2024, was unsatisfactory. HPC at 110 CFU/mL24EN-157E00236
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The skimmer weir doors are missing. Reinstallation of the weir doors is required to ensure contaminants flow into the skimmers, not to flow back to pool. Circular floating weirs can be installed instead of the flap weir doors.
  11. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Pool water sample collected on May 27 is reported unsatisfactory with HPC > 100 CFU/ml.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The skimmer weir doors are missing. Reinstallation of the weir doors is required to ensure contaminants flow into the skimmers, not to flow back to pool. Circular floating weirs can be installed instead of the flap weir doors.
  12. Monitoring Inspection

    3 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • Free available chlorine level of the pool water is lower than the required level. Free available chlorine level is to be kept above 2 ppm. Immediate correction was completed during inspection.
    • 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
      • The filtration and circulation equipment was found not in operation. Immediate correction was completed during inspection. The daily operation start procedures are to be followed.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The skimmer weir doors are missing. Reinstallation of the weir doors is required to ensure contaminants flow into the skimmers, not to flow back to pool. Circular floating weirs can be installed instead of the flap weir doors.
  13. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on Oct 3 is reported to be satisfactory. - HPC at 110 CFU/ml.
  14. Monitoring Inspection