Mount Royal University - Swimming Pool
4825 Mount Royal Gate SW Calgary AB T3E 6K6 · Aquatic Facility
7 inspections
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- 1. Sample collected on January 8, 2026 had a heterotrophic plate count of greater than 57,000 colony forming units/mL.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Total alkalinity was measured at 33 ppm. - Please ensure that the total alkalinity is maintained between 60 and 180 ppm.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Several ceiling and wall lights around the pool are not operational. Ensure these are repaired.*Update July 29, 2025*Parts are on order from US.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Total alkalinity was measured at 33 ppm. - Please ensure that the total alkalinity is maintained between 60 and 180 ppm.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Several ceiling and wall lights around the pool are not operational. Ensure these are repaired.*Update July 29, 2025*Parts are on order from US.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample taken November 13 was not tested since there was no identification number on the bottle.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Total alkalinity was measured at 33 ppm. - Please ensure that the total alkalinity is maintained between 60 and 180 ppm.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Several ceiling and wall lights around the pool are not operational. Ensure these are repaired.*Update July 29, 2025*Parts are on order from US.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Total alkalinity was measured at 33 ppm. - Please ensure that the total alkalinity is maintained between 60 and 180 ppm.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Several ceiling and wall lights around the pool are not operational. Ensure these are repaired.*Update July 29, 2025*Parts are on order from US.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- 1. Several ceiling and wall lights around the pool are not operational. Ensure these are repaired.2. There is a small build up of algae in the gutter near the diving board. Ensure this area is cleaned.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Turnover at 860gpm is 8.2hours.- Please ensure turnover is at least 8 hours.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?