135 Albany Drive NW Edmonton AB T6V 1J6 · Aquatic Facility

6 inspections

  1. Risk Management Inspection

    2 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The pH was 7.64. The pH of the water in a pool must be maintained between 6.8 and 7.6. Please make necessary adjustments.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The water level was below the skimmer during the previous site visit and was now too high. Adjustments are required.
  2. Risk Management Inspection

    0 infractions

  3. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate was 11 GPM which is too fast. Ideal flow rate is 1 - 9 GPM. The flow rate was decreased to 9 GPM at the time of inspection as per request.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The automated chemical feeding and monitoring equipment readings are not consistent with manual tests. Manual pH levels are 7.61 and controller pH readings are 7.20 which is a difference 0.41. A difference of +/- 0.2 is considered acceptable. Please take corrective actions as deemed necessary.2. The water level was below the skimmer. Adjustments are required.
  4. Risk Management Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The automated chemical feeding and monitoring equipment readings are not consistent with manual tests. Manual pH levels are 8.01 and controller pH readings are 7.43 which is a difference 0.53. A difference of +/- 0.2 is considered acceptable.The flow rate is 18 GPM which is too fast. Ideal flow rate is 1 - 9 GPM.The filtration rate is 0.72 GPM/sq.ft. which exceeds manufacturer's specifications. A maximum filtration rate of 0.375 GPM/sq.ft. is permitted.Automated controller adjustments were made at the time of inspection.Skimmer was adjusted at the time of inspection.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The automated chemical feeding and monitoring equipment readings are not consistent with manual tests. Manual pH levels are 7.22 and controller pH readings are 6.85 which is a difference of 0.37. A difference of +/- 0.2 is considered acceptable.The flow rate is 20 GPM which is too fast. Ideal flow rate is 1-9 GPM.The filtration rate is 0.80 GPM/sq.ft. which exceeds manufacturer's specifications. A maximum filtration rate of 0.375 GPM/sq.ft. is permitted as specified by the manufacturer.
  5. Risk Management Inspection

    0 infractions

  6. Initial Inspection

    2 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The pH level is 8.01, which is too high. Adjustments were made at the time of inspection.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The automated chemical feeding and monitoring equipment readings are not consistent with manual tests. Manual pH levels are 8.01 and controller pH readings are 7.43 which is a difference 0.53. A difference of +/- 0.2 is considered acceptable.The flow rate is 18 GPM which is too fast. Ideal flow rate is 1 - 9 GPM.The filtration rate is 0.72 GPM/sq.ft. which exceeds manufacturer's specifications. A maximum filtration rate of 0.375 GPM/sq.ft. is permitted.Automated controller adjustments were made at the time of inspection.Skimmer was adjusted at the time of inspection.