Movati Athletic - Cold Plunge 2(B)
135 Albany Drive NW Edmonton AB T6V 1J6 · Aquatic Facility
12 inspections
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological water sample result collected on 31/03/2026 was unsatisfactory: HPC 250 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Risk Management Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological sample collected 01/10/2025 [25EN-275E00158] was unsatisfactory: HPC 140 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The water level was below the skimmer during the previous site visit and was now too high. Adjustments are required
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological sample collected 01/10/2025 [25EN-275E00158] was unsatisfactory: HPC 140 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological sample collected 01/10/2025 [25EN-275E00158] was unsatisfactory: HPC 140 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Water level was not high enough for any skimming action. Please ensure the water level is above the skimmer to allow for adequate recirculation.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Water level was not high enough for any skimming action. Please ensure the water level is above the skimmer to allow for adequate recirculation.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate was 11 GPM which is too fast. Ideal flow rate is 1 - 9 GPM. The flow rate was decreased to 9 GPM at the time of inspection as per request.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological water sample result collected on 09/09/2025 [ID#: 25EN-252E00764] was unsatisfactory: HPC 130 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The automated chemical feeding and monitoring equipment readings are not consistent with manual tests. Manual pH levels are 7.72 and controller pH readings are 7.43 which is a difference 0.29. A difference of +/- 0.2 is considered acceptable.The flow rate is 18 GPM which is too fast. Ideal flow rate is 1 - 9 GPM.The filtration rate is 0.72 GPM/sq.ft. which exceeds manufacturer's specifications. A maximum filtration rate of 0.375 GPM/sq.ft. is permitted.Automated controller adjustments were made at the time of inspection.Skimmer was adjusted at the time of inspection.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The automated chemical feeding and monitoring equipment readings are not consistent with manual tests. Manual pH levels are 7.37 and controller pH readings are 7.07 which is a difference of 0.30. A difference of +/- 0.2 is considered acceptable.The flow rate is 18 GPM which is too fast. Ideal flow rate is 1 - 9 GPM.The filtration rate is 0.72 GPM/sq.ft. which exceeds manufacturer's specifications. A maximum filtration rate of 0.375 GPM/sq.ft. is permitted.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
0 infractions
- Initial Inspection
2 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- pH levels are 7.72 which is too high. Ensure pH levels are maintained between 6.8 - 7.6.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The automated chemical feeding and monitoring equipment readings are not consistent with manual tests. Manual pH levels are 7.72 and controller pH readings are 7.43 which is a difference 0.29. A difference of +/- 0.2 is considered acceptable.The flow rate is 18 GPM which is too fast. Ideal flow rate is 1 - 9 GPM.The filtration rate is 0.72 GPM/sq.ft. which exceeds manufacturer's specifications. A maximum filtration rate of 0.375 GPM/sq.ft. is permitted.Automated controller adjustments were made at the time of inspection.Skimmer was adjusted at the time of inspection.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?