New Imperial Suites - Swimming Pool
3331 35 Street Whitecourt AB T7S 0A2 · Aquatic Facility
69 inspections
- Risk Management Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- A heterotrophic plate count (HPC) of the sample submitted indicated >57000 cfu.The operator requested our office to complete a site visit to check pool chemistry. The pool has not been open since the last failed pool sample April 6, 2026.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- pH measured out of range. Free chlorine measured out of range. Total alkalinity measured 159 mg/L
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- A heterotrophic plate count (HPC) of the sample submitted indicated >57000 cfu.The operator requested our office to complete a site visit to check pool chemistry. The pool has not been open since the last failed pool sample April 6, 2026.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- A heterotrophic plate count (HPC) of the sample submitted indicated >57000 cfu.The operator requested our office to complete a site visit to check pool chemistry. The pool has not been open since the last failed pool sample April 6, 2026.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The pH measured >8.4 ppm. pH must be maintained between 6.8 - 7.6. A pH of 8.4 ppm renders the chlorine ineffective and the growth of bacteria. It was noted that the pH container connected to the automated system does not have adequate sodium bisulfate. The operator is aware of this concern and is to obtain this chemical.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- A heterotrophic plate count (HPC) of 140 was observed in the sample that was submitted.Please check pool chemical levels and ensure they are adequate, increase if needed and resubmit sample next week.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Pool water sample returned with coliforms. Resample next week. Pool chemistry checked and no concerns noted. See closing comments pool chemistry measurements.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Salt measured 2000 ppm. Display ORP 676 mV pH 7.2 AHS measurement: ORP 637 mV, Alk 111, pH 6.69, FC 0.13 ppm, TC 0.20 ppm. - Controller pH readjusted to increase pH. - Chlorine added to - The operator is going to obtain and add more salt to reach 3000 as per manufacturer's recommendations. - Noted that the chlorine generator is activating on a more frequent basis to produce chlorine. Activation intervals are two minutes.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Morning measurements: Salt added over the weekend. Salt still measuring low and salt added to the pool. Display ORP 649 mV pH 7.5 AHS measurement: ORP 644 mV, Alk 131, pH 7.05, FC 0.23 ppm, TC 0.40 ppm. Afternoon reading after salt addition. Salt measured 1600 ppm, more salt added and will wait 24 hours for equilibrium. Digital display: 662 mV, pH 7.5AHS measurements: ORP 661 mV, Alk 138 mV, pH 7.03, FC 0.19 ppm, TC 0.36 ppm
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Morning test:Alk 107 ppm, pH 6.75 FC 0.31 ppm ORP 737 mVAfternoon test: Alk 105 ppm pH 6.84 FC 0.39 ppmSat chlorine generator indicates the salt level is low. The operator shall obtain salt and add appropriate amount. Pool water sample submitted yesterday December 9. December 2 pool water sample result returned with satisfactory results.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Morning test:Alk 22 ppm, pH 6.50 FC 0.19 ppm ORP 727 mVSodium bicarbonate added.Afternoon test: Alk 37 ppm pH 6.70 FC 0.39 ppmSodium bicarbonate added
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Alk 6 ppm, pH 6.50 FC 0.05 ppm Sodium bicarbonate added. Ensure pH pump does not engage. Chlorine generator fuse changed.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- pH 6.5. FCl 0Troubleshoot the automatic controller system to produce chlorine and slightly raise the pH to acceptable levels.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- pH 6.5. FCl 0.11Chlorine slightly detected. pH steadfast. Water sample results are pending.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
1 infraction
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- pH measured above 8.3. The automatic pH monitoring equipment was calibrated to ensure acid added for pH control.Our office will check the pH later today.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- No change to pH. The operator added pH down. Troubleshooting completed on the automatic monitoring equipment to ensure acid added for pH control.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Sample returned with total coliforms present.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- AHS ORP measured 530 mVAHS FC measured 0.11 and 0.06 ppmFacility digital display measured 830 mV and the salt generator was not active even though set at 850 mV. The pool chemistry automation system is not working to maintain proper pool water chemistry. Please contact a service provider to troubleshoot and repair the system. The operator has agreed to voluntarily close the pool .
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Sample returned with total coliforms present.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- AHS ORP measured 530 mVAHS FC measured 0.11 and 0.06 ppmFacility digital display measured 830 mV and the salt generator was not active even though set at 850 mV. The pool chemistry automation system is not working to maintain proper pool water chemistry. Please contact a service provider to troubleshoot and repair the system. The operator has agreed to voluntarily close the pool .
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- 25EN-246E00806 submitted September 2, 2025 returned with coliforms and >57000 HPC. Pool is closed at this time.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- AHS ORP measured 530 mVAHS FC measured 0.11 and 0.06 ppmFacility digital display measured 830 mV and the salt generator was not active even though set at 850 mV. The pool chemistry automation system is not working to maintain proper pool water chemistry. Please contact a service provider to troubleshoot and repair the system. The operator has agreed to voluntarily close the pool .
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- AHS ORP measured 530 mVAHS FC measured 0.11 and 0.06 ppmFacility digital display measured 830 mV and the salt generator was not active even though set at 850 mV. The pool chemistry automation system is not working to maintain proper pool water chemistry. Please contact a service provider to troubleshoot and repair the system. The operator has agreed to voluntarily close the pool .
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- August 26, 2025 25EN-239E00620 returned with HPC 830 cfu. Indication of low free chlorine levels as detected on the August 27, 2025 site, prior to shock.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- AHS ORP measured 530 mVAHS FC measured 0.11 and 0.06 ppmFacility digital display measured 830 mV and the salt generator was not active even though set at 850 mV. The pool chemistry automation system is not working to maintain proper pool water chemistry. Please contact a service provider to troubleshoot and repair the system. The operator has agreed to voluntarily close the pool .
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Pool chemistry tested ORP 330 pH 7.01, FC 0.01ppm, TC 0.03 ppm, Alk 86 ppm. During the inspection the pool was shocked and ORP monitoring device adjusted. FC measured 0.72 ppm and ORP 730. Reinspection required later on this day to confirm adjustments.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
0 infractions
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- 1. Pool water sample (25EN-211E00573)taken and submitted on July 29, 2025 returned with Total Coliforms.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- 1) Sample 25EN-211E00573 came back with an HPC of >57,000.Please shock-chlorinate the pool.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- 1. Pool water sample (25EN184E00849)taken and submitted on July 2, 2025 returned with Total Coliforms present.2. Pool water sample 25EN-197E00978 returned with Total Coliforms present.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- AHS measured:Free chlorine - 0.02 ppm.Total chlorine - 0.14 ppmAlk - 75 ppmORP measured 311 mV.pH 7.12Facility digital display ORP 477mVpH 7.2The chlorine generator has power but is not maintaining chlorine and ORP at required levels. Investigate and repair ensuring free chlorine levels can be maintained at acceptable levels.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- 1. Pool water sample (25EN184E00849)taken and submitted on July 2, 2025 returned with Total Coliforms present.2. Pool water sample 25EN-197E00978 returned with Total Coliforms present.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- AHS measured:Free chlorine - 0.02 ppm.Total chlorine - 0.14 ppmAlk - 75 ppmORP measured 311 mV.pH 7.12Facility digital display ORP 477mVpH 7.2The chlorine generator has power but is not maintaining chlorine and ORP at required levels. Investigate and repair ensuring free chlorine levels can be maintained at acceptable levels.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Leak test set up completed to determine if natural pool water loss through evaporation or pool leak occurring.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- 1. Pool water sample (25EN184E00849)taken and submitted on July 2, 2025 returned with Total Coliforms present.2. Pool water sample 25EN-197E00978 returned with Total Coliforms present.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- AHS measured:Free chlorine - 0.02 ppm.Total chlorine - 0.14 ppmAlk - 75 ppmORP measured 311 mV.pH 7.12Facility digital display ORP 477mVpH 7.2The chlorine generator has power but is not maintaining chlorine and ORP at required levels. Investigate and repair ensuring free chlorine levels can be maintained at acceptable levels.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- It was observed that the pool water level is below the skimmer line. Pool water is not being drawn off the top water level and recirculated for treatment. Potential loss of pool water, please investigate.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Pool water sample (25EN184E00849)taken and submitted on July 2, 2025 returned with Total Coliforms present.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- AHS measured:Free chlorine - 0.02 ppm.Total chlorine - 0.14 ppmAlk - 75 ppmORP measured 311 mV.pH 7.12Facility digital display ORP 477mVpH 7.2The chlorine generator has power but is not maintaining chlorine and ORP at required levels. Investigate and repair ensuring free chlorine levels can be maintained at acceptable levels.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- It was observed that the pool water level is below the skimmer line. Pool water is not being drawn off the top water level and recirculated for treatment. Potential loss of pool water, please investigate.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- AHS measured:Free chlorine measured 0.02 ppm.ORP measured 280 mV.pH 7.12Facility digital display ORP 300mVpH 7.2The chlorine generator has power but is not maintaining chlorine and ORP at required levels. Investigate and repair ensuring free chlorine levels can be maintained at acceptable levels.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- 25EN-176E00801 returned with HPC >57000. Day of sample, no concerns with free chlorine or pH. Operator will re-sample next week.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Monitoring Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Coliforms present. Contacted the pool operator who indicated the pool has already been shocked.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Free available chlorine measured 0.02 ppm. ORP measured 275 mV.
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- The pool water is not being continuously disinfected. It was observed that the salt chlorine generator was not operating and had no power. Please investigate and ensure the chlorine generator is in proper working order.Based on no chlorine in the pool water, the facility voluntarily closed the pool. A sign was placed on the door indicating the pool was closed.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Coliforms present. Contacted the pool operator who indicated the pool has already been shocked. May shock again. After shocking, re-balance the pool water chemistry and submit a water sample for analysis.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Non-critical water sample result. HPC measured 410.Spoke to the operator who stated he had been away the previous week (no sample submitted March 10 -14) and when he got back, the chemistry was off so suspects this is the problem. He says chemistry results are good now and will submit another sample tomorrow.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Non-critical water sample result. HPC measured >57000 cfu. Spoke to the operator and it was determined that the pH was 8.0 on the sample day. At this time, the pH measures 7.6. Please ensure the pH level is maintained between 6.8 to 7.6 (preferably around 7). Resample next week as per usual sampling frequency.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- February 2, 2025 pool water sample ID 2739560, 25EN-0043E00249 returned with HPC 750. Contacted the operator and instructed to check pool chemistry and make appropriate adjustments if need be. Resample next week.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Risk Management Inspection
2 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Measured pool water chemistry at the time of inspection was;ORP-708mvFree chlorine: 1.36PH - 7.80ppmThis PH reading is unsatisfactory and above recommended range of 6.8-7.6. This will decrease the effectiveness of chlorine disinfectant used to maintain the pool water quality, making it harder to kill germs. It can also result in eye and skin irritation when contact is made with the pool water.Operator was told to temporarily close pool, treat pool water, and also call the maintenance company to troubleshoot the automated pool chemical feeder/controller in the mechanical room while monitoring pool chemistry PHI will conduct another pool water chemistry test and confirm pool water chemistry parameters is within recommended range, before pool is re-opened for use.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Measured pool water chemistry result isAlkalinity:200ppmCombined Chlorine:0.09ppmTemperature:28degree CelsiusAlkalinity is above the recommended range of 60-180ppm. This can increase the PH of the pool water thereby reducing effectiveness of chlorine in the pool and water quality.Please treat the pool water to lower both alkalinity and PH.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
2 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The operator sludged in Sodium bio-sulphate prior to the arrival of PHI and testing of pool water chemical parameters.Result of pool water chemical test measured at the time of inspection;ORP-662mvFree chlorine:1.32ppmpH - 7.87This PH reading is unsatisfactory and above recommended range of 6.8-7.6. This will decrease the effectiveness of chlorine sanitizer, making it harder to kill germs. It can also make the pool water to cause eye/skin, irritation.Operator was told to temporarily close pool, allow more time for the added sodium bio-sulphate to act before retest of pool water chemistry.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Measured pool water chemistry result isAlkalinity:200ppmCombined Chlorine:0.09ppmTemperature:28degree CelsiusAlkalinity is above the recommended range of 60-180ppm. This can increase the PH of the pool water thereby reducing effectiveness of chlorine in the pool.Please treat the pool water to lower both alkalinity and PH.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
2 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The operator poured in Sodium bio-sulphate prior to the arrival of PHI and conducting of pool chemistry test.Measured pool water chemistry at the time of inspection was;ORP-672mvFree chlorine:0.52ppmpH - 7.77This PH reading is unsatisfactory and above recommended range of 6.8-7.6. This will decrease the effectiveness of chlorine disinfectant used to maintain the pool water quality, making it harder to kill germs. It can also result in eye and skin irritation when contact is made with the pool water.Operator was told to temporarily close pool, treat pool water, troubleshoot and repeat the pool water chemistry test.PHI will conduct another pool water chemistry test and confirm pool water chemistry parameters is within recommended range, before pool is open for use.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Measured pool water chemistry result isAlkalinity:200ppmCombined Chlorine:0.09ppmTemperature:28degree CelsiusAlkalinity is above the recommended range of 60-180ppm. This can increase the PH of the pool water thereby reducing effectiveness of chlorine in the pool and water quality.Please treat the pool water to lower both alkalinity and PH.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Discussed the sample results with the operator and the pool was voluntarily closed.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC was >57000.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The pH measured 7.6. The digital ORP is set to engage acid injection at 7.3. Please make equipment adjustments and reduce the pH to 7.0 - 7.2.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Discussed the sample results with the operator and the pool was voluntarily closed.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Discussed the result with the pool operator and indicated the HPC was >57000.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The pH measured 7.6. The digital ORP is set to engage acid injection at 7.3. Please make equipment adjustments and reduce the pH to 7.0 - 7.2.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Discussed the sample results with the operator and the pool was voluntarily closed.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Discussed the result with the pool operator and indicated the HPC was >57000.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- TC detected and present in the submitted water sample.Accession# 24EN-241E00705Ensure the pool remains closed and shock/ treat, balance the water chemistry prior to resampling and submitting.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- TC detected and present in the submitted water sample.Accession# 24EN-288E00400Ensure to close the pool and shock/ treat, balance the water chemistry prior to resampling as detailed in the closing remarks.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC >57,000.Operator notified and shock chlorination was discussed.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC >57,000.Operator notified and shock chlorination was discussed.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Total Coliforms were detected in the sample. Pool has been closed for a number of weeks. Results are still suggesting a problem with the system.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC of 12870 present.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
0 infractions
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC 440 cfu.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- 0 ppm free chlorine was measured in the pool water. The water appears cloudy. The operator voluntarily closed the pool. It was noted the salt generator intermittently turns off. Please investigate.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC 57000 cfu. Pool operator contacted and discussed checking water chemistry and retesting this week.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- 0 ppm free chlorine was measured in the pool water. The water appears cloudy. The operator voluntarily closed the pool. It was noted the salt generator intermittently turns off. Please investigate.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC 57000 cfu. Pool operator contacted and discussed checking water chemistry and retesting this week.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- January 2, 2024 WE-24-0000579 returned with coliforms present. Contacted the operator and discussed the result. The operator shall confirm satisfactory water chemistry and re-sample next week.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- January 9, 2024 WE-24-0003741 water sample was unprocessed. January 2, 2024 WE-24-0000579 returned with coliforms present and HPC 30. Contacted the operator and discussed the result. The operator shall confirm satisfactory water chemistry and re-sample next week.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- January 2, 2024 WE-24-0000579 returned with coliforms present. Contacted the operator and discussed the result. The operator shall confirm satisfactory water chemistry and re-sample next week.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- January 2, 2024 WE-24-0000579 returned with coliforms present and HPC 30. Contacted the operator and discussed the result. The operator shall confirm satisfactory water chemistry and re-sample next week.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample returned with a HPC >57000. Please check the pool chemistry and resample next week.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample WE-23-01-9008 submitted October 10, 2023 returned with HPC 1300. The operator has voluntarily closed the swimming pool. The operator has potentially diagnosed an equipment malfunction and has completed repairs.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample WE-23-0102292 submitted September 20, 2023 returned with HPC 57000. Check equipment and chemistry and make necessary adjustments. Please re-sample next week.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC 310. Ensure water chemistry is balanced and equipment is operating in a satisfactory manner.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC of 1660 was detected in the sample.