Northern Lights Aquatic Centre - Main Pool

1201 Main Street SE Slave Lake AB T0G 2A3 · Aquatic Facility

Inspection summary

Northern Lights Aquatic Centre - Main Pool has been inspected 11 times by Alberta Health Services (Environmental Public Health) since October 25, 2023. The most recent inspection, on March 4, 2026, recorded 1 infraction.

4 of 11 inspections on record found no infractions at all. In the past 12 months there was 1 inspection with 1 infraction recorded. The higher-risk findings here relate to: Pool and spa water quality and Chemicals and toxic substances.

The number of infractions per inspection has stayed roughly the same over time.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded 5 times across 5 separate inspections, most recently on March 25, 2024. For example: Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?

  • Chemicals and toxic substancesHigher risk

    Pool chemicals such as chlorine and acid must be labelled, stored apart from each other and handled safely. Mixing them by mistake can release toxic gas, so storage and handling problems are treated seriously.

    Recorded 2 times across 2 separate inspections, most recently on March 4, 2026. For example: Is the chemical quality of the water in this pool satisfactory (Non-Critical)?

About this data

These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

11 inspections

  1. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Total alkalinity is measured at a concentration of 33 ppm at the time of inspection. Operator was able make adjustments to the pool chemistry by adding sodium bicarbonate to raise the alkalinity during the inspection. Alkalinity was measured at 71 ppm after adjustments. Ensure that the alkalinity of the pool is maintained at a concentration of no less than 60 ppm and no greater than 180 ppm.
  2. Monitoring Inspection

    0 infractions

  3. Risk Management Inspection

    0 infractions

  4. Monitoring Inspection

    0 infractions

  5. Risk Management Inspection

    0 infractions

  6. Risk Management Inspection

    1 infraction

    • 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
      • The flow rate displayed on the flowmeter has decreased in comparison to the previous inspection. Readings and Turnover rates are the following:Pool volume: 630.5 cubic meters = 166560 gallonsFlow rate: 330 gallons per minuteTurnover rate: 8.412 hours (Unsatisfactory)Operator stated that a new flowmeter is available on site for replacement and backwash will be completed within a week from inspection. Please ensure that there is adequate flow to allow complete recirculation of the pool water within 6 hours.
  7. Monitoring Inspection

    1 infraction

    • 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
      • Unsatisfactory turnover was noted with insufficient flow rate. Ensure that there is adequate flow to allow complete recirculation of the pool water within 6 hours.
  8. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity reading was noted to be below the minimum acceptable level of 60 ppm. Operator corrected the violation during inspection.Pool chemistry reading after correction:Free Chlorine: 1.53 ppmpH: 6.9Total Alkalinity: 82 ppmCombined Chlorine: 0.32 ppm
  9. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Unsatisfactory turnover was noted with insufficient flow rate. Ensure that there is adequate flow to allow complete recirculation of the pool water within 6 hours.Pool volume: 630.5 cubic meters (approximately 166560 gallons)Flow rate: 435 gallons per minuteTurnover rate: 6.38 hoursUpdate: Turnover rate remains unsatisfactory.
  10. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Unsatisfactory turnover was noted with insufficient flow rate. Ensure that there is adequate flow to allow complete recirculation of the pool water within 6 hours.Pool volume: 630.5 cubic meters (approximately 166560 gallons)Flow rate: 430 gallons per minuteTurnover rate: 6.45 hoursUpdate: Turnover rate remains unsatisfactory with the flow rate unchanged.
  11. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Unsatisfactory turnover was noted with insufficient flow rate. Ensure that there is adequate flow to allow complete recirculation of the pool water within 6 hours.Pool volume: 630.5 cubic meters (approximately 166560 gallons)Flow rate: 430 gallons per minuteTurnover rate: 6.45 hoursUpdate: Turnover rate remains unsatisfactory with the flow rate unchanged.