Northern Lights Aquatic Centre - Whirlpool

1201 Main Street SE Slave Lake AB T0G 2A3 · Aquatic Facility

12 inspections

  1. Risk Management Inspection

    0 infractions

  2. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • 1. Combined chlorine is measured at a concentration of 1.51 ppm at the time of inspection. Ensure to take necessary actions to reduce combined chlorine levels to be as low as possible for bather comfort.2. Total alkalinity is measured at a concentration of 23 ppm at the time of inspection. Operator was able make adjustments to the pool chemistry by adding sodium bicarbonate to increase the concentration of the alkalinity during the inspection. Alkalinity was measured at 37 ppm after adjustments, which still does not meet the minimum requirement of 60 ppm. Ensure to take necessary action to increase the alkalinity so it is maintained at no less than 60 ppm and no greater than 180 ppm.
  3. Risk Management Inspection

    0 infractions

  4. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine levels measured by operator were at a residual of 2.0 ppm. Combined chlorine levels could not be measured by PHI test kit, as the total available chlorine was over-range (OR). Ensure to take necessary actions to reduce combined chlorine levels to be as low as possible for bather comfort.
  5. Risk Management Inspection

    0 infractions

  6. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Unsatisfactory water sample result received. Sample submitted on February 20, 2025. Pseudomonas aeruginosa = ISOLATED
  7. Monitoring Inspection

    1 infraction

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • Chemical parameters measured:Free chlorine 4.54 ppmTemperature 39 degrees Celsius***pH 7.8, 7.7, 8.2, 7.9Electronic monitoring system:ORP 786 mVpH 7.54Temperature 40 degrees CelsiusCl2 3.03pH of the whirlpool was measured to be greater than 7.6Correction:- pH was adjusted to 6.8 at the time of inspection
  8. Monitoring Inspection

    0 infractions

  9. Risk Management Inspection

    0 infractions

  10. Demand Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The automated chemical feeder/monitoring device is in disrepair with readings indicating free available chlorine level at 0.00 ppm, and pH at 7.70.Ensure that the automated chemical feeder is maintained in good repair and calibrated correctly to keep the pool water balanced within acceptable range.
  11. Risk Management Inspection

    0 infractions

  12. Monitoring Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Total alkalinity was measured below the minimum level of 60 ppm. Ensure that the total alkalinity concentration is maintained between 60 and 180 ppm.Total Alkalinity: 44 ppmCombined Chlorine: 1.18 ppm
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Pool volume: 14.3 cubic meters = 3777.66 gallonsFlow rate: UnknownTurnover rate: UnknownFlowmeter for the filtration system of the whirlpool basin was noted to be in disrepair. Ensure that a flow rate monitoring system is in place to ensure adequate filtration and turnover of the pool water.