Inspection summary
Pincher Creek Aquatic Centre - Hot Tub has been inspected 12 times by Alberta Health Services (Environmental Public Health) since January 12, 2024. The most recent inspection, on October 9, 2026, found no infractions.
7 of 12 inspections on record found no infractions at all. In the past 12 months there were 4 inspections with 1 infraction recorded. The higher-risk findings here relate to: Chemicals and toxic substances and Pool and spa water quality.
The last 2 inspections in a row found no infractions. The number of infractions per inspection has stayed roughly the same over time.
What these findings mean
Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.
Chemicals and toxic substancesHigher risk
Pool chemicals such as chlorine and acid must be labelled, stored apart from each other and handled safely. Mixing them by mistake can release toxic gas, so storage and handling problems are treated seriously.
Recorded 3 times across 3 separate inspections, most recently on October 16, 2024. For example:
Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
Pool and spa water qualityHigher risk
For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.
Recorded once on April 30, 2026. For example:
Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
Food safety training and certificationLower risk
Many jurisdictions require trained pool operators and certified lifeguards. These findings mean required training, certification or staffing records were missing at the time of inspection.
Recorded 2 times across 2 separate inspections, most recently on June 3, 2024. For example:
Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
About this data
These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.
12 inspections
- Monitoring Inspection
0 infractions
- Demand Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Jet pump flow was initially 503 GPM. Outlet configuration allowed for 264 GPM max. Adjusted to 253 GPM.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
0 infractions
- Demand Inspection
0 infractions
- Monitoring Inspection
0 infractions
- Monitoring Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The alkalinity measured 39 ppm. Discussed adding sodium bicarbonate and increase to minimum of 60 ppm.Combined chlorines measured 1.33 ppm. Combined chlorines should not be more than 1 ppm.The hot tub is due to be drained. Operator will be draining hot tub this weekend.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The alkalinity measured 49 ppm. Please increase to minimum 60 ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
2 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The alkalinity measured 49 ppm. Please increase to minimum 60 ppm.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Anti-entrapment plan was being updated but the complete plan was not provided yet. Please keep a complete updated anti-entrapment plan (see template). This will include details about the temporary jets pump plan.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Anti-entrapment plan was being updated but the complete plan was not provided yet. Please keep a complete updated anti-entrapment plan (see template). This will include details about the temporary jets pump plan.