Pioneer Lodge - Swimming Pool

32134 Range Road 63 Sundre AB T0M 1X0 · Aquatic Facility

Inspection summary

Pioneer Lodge - Swimming Pool has been inspected 11 times by Alberta Health Services (Environmental Public Health) since July 18, 2024. The most recent inspection, on August 6, 2026, recorded 2 infractions.

5 of 11 inspections on record found no infractions at all. In the past 12 months there were 4 inspections with 5 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality and Chemicals and toxic substances.

The number of infractions per inspection has stayed roughly the same over time.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded 7 times across 5 separate inspections, most recently on August 6, 2026. For example: Is the bacteriological quality of the water in this pool satisfactory (Critical)?

  • Chemicals and toxic substancesHigher risk

    Pool chemicals such as chlorine and acid must be labelled, stored apart from each other and handled safely. Mixing them by mistake can release toxic gas, so storage and handling problems are treated seriously.

    Recorded 4 times across 3 separate inspections, most recently on July 7, 2026. For example: Is the chemical quality of the water in this pool satisfactory (Critical)?

  • Permits, records and postingLower risk

    Operating permits, water-test logs, posted bather rules and emergency procedures. Daily test logs are how operators show the water was checked and treated between inspections.

    Recorded 2 times across 2 separate inspections, most recently on July 7, 2026. For example: Are proper testing, monitoring, and other records being properly maintained?

About this data

These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

11 inspections

  1. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • 5 Aug - Water sample collected by PHIWater sample collected on July 29, 2026, was unsatisfactory showing TC present.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • 1. The installed main drain fittings had warped due to the expansion of the flexible pool liner and caused the fitting to pull away from the drain cover, exposing a space that could present an entrapment hazard. Rectify the main drain fitting so as to eliminate the entrapment hazard.A closure order has been issued until the main drain entrapment hazard has been eliminated.
  2. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample collected on July 29, 2026, was unsatisfactory showing TC present.
  3. Risk Management Inspection

    0 infractions

  4. Monitoring Inspection

    2 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • Water Chemistry: FC .16 pH 7.5The pool may not be opened until the free chlorine is 1.0 or greater.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • 1. The water test kit reagents were expired. Purchase new test reagents.Water chemistry was tested and recorded regularly during daily operation.The water chemistry records were reviewed during the inspection.
  5. Risk Management Inspection

    0 infractions

  6. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 1. Routine water sample result: HPC > 57,000 CFU/mlClose the pool from public use immediately. Shock chlorinate the pool. After shock chlorinating, backwash the filter. Re-balance the water chemistry to bring the free chlorine level to at least 1.0ppm. The pool can then be re-opened to the public.Resample on your regular sampling day
  7. Risk Management Inspection

    0 infractions

  8. Monitoring Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Water Chemistry: CC 0.0 Alk 200Alkalinity should be between 60-180.High alkalinity can cause pH lock. Add acid to lower the alkalinity.
    • 08. Does food preparation and consumption take place away from the pool?
      • 1. There was no signage prohibiting food inside the pool enclosure area. Install signage prohibiting food inside the pool enclosure.
  9. Monitoring Inspection

    0 infractions

  10. Risk Management Inspection

    0 infractions

  11. Monitoring Inspection

    5 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 1. The last bac-t sample was submitted nearly a year ago (16 Aug 2023). Bac-t samples must be submitted weekly during operation.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • Water Chemistry FC 0.18 pH 7.79 Cya 2.0The minimum free chlorine for a pool is 1.0. Adjust the free chlorine to meet or exceed the minimum required level.pH must be maintained between 6.8 - 7.6. Adjust the pH to within the required range.The pool must remain closed until such time as the water chemistry meets the mandated levels and this has been confirmed by a re-inspection from AHS.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Water Chemistry CC 0.10 Alk >200Alkalinity must be maintained between 60-180ppm. Adjust the alkalinity to within the required range.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The circulation / filtration system was not running fast enough to meet the mandated turnover time.Pool Volume 63,000 usgFlow Rate 100 gpmTurnover Time 10.6 hrsMax flow rate = 600 gpmThe minimum flow rate to meet the required 6 hour turnover time is 177 gpm.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Water chemistry was not tested and recorded regularly. The last water chemistry tests documented was 9 July. The inspection occurred on 18 July. Water chemistry testing must be completed at least daily.