Pomeroy Kananaskis Mountain Lodge - Whirlpool
1 Centennial Drive Kananaskis Village AB T0L 2H0 · Aquatic Facility
24 inspections
- Risk Management Inspection
3 infractions
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- As there is no valve for adjusting the flow from the main drain, need to confirm whether majority of flow through the whirlpool is through the skimmers. Was advised some re-piping is going to be done and these valves added.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- There was at least one weir missing from a skimmer. To be replaced.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- There was some incorrect information on the anti-entrapment plan with regards to the cover that was recently changed. Was advised all the main drain covers are going to be changed out in the near future. Please provide updated anti-entrapment plan when done.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Risk Management Inspection
3 infractions
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- As there is no valve for adjusting the flow from the main drain, need to confirm whether majority of flow through the whirlpool is through the skimmers. Was advised some re-piping is going to be done and these valves added.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- There was at least one weir missing from a skimmer. To be replaced.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Some of the pumps for the jets have been changed. Please provide up-dated anti-entrapment plans with new pump information and new flow rates.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Risk Management Inspection
4 infractions
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- As there is no valve for adjusting the flow from the main drain, need to confirm whether majority of flow through the whirlpool is through the skimmers. Was advised some re-piping is going to be done and these valves added.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Drain cover on bottom of whirlpool to the right of the stair railing (interior portion of whirlpool) was damaged (piece missing). To be replaced with new drain cover (installed according to manufacturer's requirements and in good condition) before public again has access to interior portion of whirlpool; currently is no public access to indoor area as construction still ongoing in indoor pool area and barrier installed between indoor and outdoor portions of the whirlpool.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- There was at least one weir missing from a skimmer. To be replaced.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Some of the pumps for the jets have been changed. Please provide up-dated anti-entrapment plans with new pump information and new flow rates.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Monitoring Inspection
3 infractions
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- As there is no valve for adjusting the flow from the main drain, need to confirm whether majority of flow through the whirlpool is through the skimmers. Was advised some re-piping is going to be done and these valves added.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- There was at least one weir missing from a skimmer. To be replaced.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Some of the pumps for the jets have been changed. Please provide up-dated anti-entrapment plans with new pump information and new flow rates.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Risk Management Inspection
3 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate for the whirlpool was fluctuating between 250-275gpm according to the flow meter during last inspection and today the float appeared stuck at 350gpm. Minimum required flow rate if 361gpm. Please ensure flow meter is working properly and flow rate is maintained between 361gpm and 441gpm.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- As there is no valve for adjusting the flow from the main drain, need to confirm whether majority of flow through the whirlpool is through the skimmer. Recommend using an ultrasonic flow meter to determine flow through skimmers versus main drains.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- There was at least one weir missing from a skimmer. To be replaced.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
5 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample taken on October 27, 2025 had total coliforms present. Treat water to remove contamination. Resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Dec.29/25; Sample had missing id label, not tested. Resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate for the whirlpool was fluctuating between 250-275gpm according to the flow meter during last inspection and today the float appeared stuck at 350gpm. Minimum required flow rate if 361gpm. Please ensure flow meter is working properly and flow rate is maintained between 361gpm and 441gpm.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- As there is no valve for adjusting the flow from the main drain, need to confirm whether majority of flow through the whirlpool is through the skimmer. Recommend using an ultrasonic flow meter to determine flow through skimmers versus main drains.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- There was at least one weir missing from a skimmer. To be replaced.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample taken on October 27, 2025 had total coliforms present. Treat water to remove contamination. Resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate for the whirlpool was fluctuating between 250-275gpm according to the flow meter during last inspection and today the float appeared stuck at 350gpm. Minimum required flow rate if 361gpm. Please ensure flow meter is working properly and flow rate is maintained between 361gpm and 441gpm.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- As there is no valve for adjusting the flow from the main drain, need to confirm whether majority of flow through the whirlpool is through the skimmer. Recommend using an ultrasonic flow meter to determine flow through skimmers versus main drains.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- There was at least one weir missing from a skimmer. To be replaced.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
3 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate for the whirlpool was fluctuating between 250-275gpm according to the flow meter during last inspection and today the float appeared stuck at 350gpm. Minimum required flow rate if 361gpm. Please ensure flow meter is working properly and flow rate is maintained between 361gpm and 441gpm.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- As there is no valve for adjusting the flow from the main drain, need to confirm whether majority of flow through the whirlpool is through the skimmer. Recommend using an ultrasonic flow meter to determine flow through skimmers versus main drains.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- There was at least one weir missing from a skimmer. To be replaced.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample taken on October 6, 2025 had Pseudomonas isolated. Close whirlpool until a Pseudomonas disinfection is done. Resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate for the whirlpool was fluctuating between 250-275gpm according to the flow meter during last inspection and today the float appeared stuck at 350gpm. Minimum required flow rate if 361gpm. Please ensure flow meter is working properly and flow rate is maintained between 361gpm and 441gpm.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- As there is no valve for adjusting the flow from the main drain, need to confirm whether majority of flow through the whirlpool is through the skimmer. Recommend using an ultrasonic flow meter to determine flow through skimmers versus main drains.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- There was at least one weir missing from a skimmer. To be replaced.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample submitted on October 3, 2025 was not tested as it was received by the lab after it had closed for the weekend. New sample to be submitted.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate for the whirlpool was fluctuating between 250-275gpm according to the flow meter during last inspection and today the float appeared stuck at 350gpm. Minimum required flow rate if 361gpm. Please ensure flow meter is working properly and flow rate is maintained between 361gpm and 441gpm.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- As there is no valve for adjusting the flow from the main drain, need to confirm whether majority of flow through the whirlpool is through the skimmer. Recommend using an ultrasonic flow meter to determine flow through skimmers versus main drains.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- There was at least one weir missing from a skimmer. To be replaced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample taken on July 15, 2025 had a heterotrophic plate count of 110 cfu/ml. Treat water to remove contamination. Resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate for the whirlpool was fluctuating between 250-275gpm according to the flow meter during last inspection and today the float appeared stuck at 350gpm. Minimum required flow rate if 361gpm. Please ensure flow meter is working properly and flow rate is maintained between 361gpm and 441gpm.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- As there is no valve for adjusting the flow from the main drain, need to confirm whether majority of flow through the whirlpool is through the skimmer. Recommend using an ultrasonic flow meter to determine flow through skimmers versus main drains.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- There was at least one weir missing from a skimmer. To be replaced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
3 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate for the whirlpool was fluctuating between 250-275gpm according to the flow meter during last inspection and today the float appeared stuck at 350gpm. Minimum required flow rate if 361gpm. Please ensure flow meter is working properly and flow rate is maintained between 361gpm and 441gpm.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- As there is no valve for adjusting the flow from the main drain, need to confirm whether majority of flow through the whirlpool is through the skimmer. Recommend using an ultrasonic flow meter to determine flow through skimmers versus main drains.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- There was at least one weir missing from a skimmer. To be replaced.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
6 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- March 7, 2025 water sample was not tested as it was not received by the Lab prior to the Lab closing for the weekend. Resample to be submitted.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Combined chlorine level was measured as 1.82ppm. Combined chlorine level is to be reduced.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate for the whirlpool was fluctuating between 250-275gpm according to the flow meter. Minimum required flow rate if 361gpm. Please ensure flow rate increased to between 361gpm and 441gpm.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- As there is no valve for adjusting the flow from the main drain, need to confirm whether majority of flow through the whirlpool is through the skimmer. Recommend using an ultrasonic flow meter to determine flow through skimmers versus main drains.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Whirlpool water temperature was measured as 41.9C. Reduce temperature to no more than 40C.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- There was at least one weir missing from a skimmer. To be replaced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
5 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Combined chlorine level was measured as 1.82ppm. Combined chlorine level is to be reduced.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate for the whirlpool was fluctuating between 250-275gpm according to the flow meter. Minimum required flow rate if 361gpm. Please ensure flow rate increased to between 361gpm and 441gpm.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- As there is no valve for adjusting the flow from the main drain, need to confirm whether majority of flow through the whirlpool is through the skimmer. Recommend using an ultrasonic flow meter to determine flow through skimmers versus main drains.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Whirlpool water temperature was measured as 41.9C. Reduce temperature to no more than 40C.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- There was at least one weir missing from a skimmer. To be replaced.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate for the whirlpool was 350gpm according to the flow meter. Minimum required flow rate if 361gpm. Please ensure flow rate increased to between 361gpm and 441gpm.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- As there is no valve for adjusting the flow from the main drain, need to confirm whether majority of flow through the whirlpool is through the skimmer. Recommend using an ultrasonic flow meter to determine flow through skimmers versus main drains.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
5 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Chlorine was measured as 0.09ppm. Was advised that dechlor had just been added and too much had accidentally been added.Pool operator adjusted chlorine level to 2.15ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The smaller filter (TR-140) has been bypassed so all flow is going through only the larger filter. Are now exceeding allowable flow rate through the larger filter. New TR-140 filter was just installed; was advised flow to it would be turned on later today.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Skimmer valve to circulation pump is not fully open. Was advised that if the skimmer valve is fully open, air gets into the pump. Need to determine whether majority of flow through the whirlpool is through the skimmer. Recommend using an ultrasonic flow meter to determine flow through skimmers versus main drains.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- There is no clock visible in the pool area to whirlpool users.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Flow meter for the jets were not working.Repair/replace flow meters so they are functional and accurate.Some of the weirs were missing from the skimmers. To be replaced.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
5 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- May 10/24 water sample was not processed as there was no time of collection on the requisition form and no id# sticker on the bottle. Resample to be taken.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The smaller filter has been bypassed so all flow is going through only the larger filter. Are now exceeding allowable flow rate through the larger filter. Smaller filter needs to be repaired and handling enough of the flow so 12.5gpm/sq.ft is not being exceeded through either filter.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Skimmer valve to circulation pump is not fully open. Keep fully open to maximize water remove from the pool through the skimmers.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- There is no clock visible in the pool area to whirlpool users.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Flow meter for the jets were not working.Repair/replace flow meters so they are functional and accurate.Some of the weirs were missing from the skimmers. To be replaced.Some of the weirs were stuck in place. Please ensure all weirs are working properly.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
4 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The smaller filter has been bypassed so all flow is going through only the larger filter. Are now exceeding allowable flow rate through the larger filter. Smaller filter needs to be repaired and handling enough of the flow so 12.5gpm/sq.ft is not being exceeded through either filter.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Skimmer valve to circulation pump is not fully open. Keep fully open to maximize water remove from the pool through the skimmers.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- There is no clock visible in the pool area to whirlpool users.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Flow meter for the jets were not working.Repair/replace flow meters so they are functional and accurate.Some of the weirs were missing from the skimmers. To be replaced.Some of the weirs were stuck in place. Please ensure all weirs are working properly.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
5 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample submitted May 3, 2024 was submitted under the wrong access number and there was insufficient information on the requisition form to verify the sample. Resample to be submitted.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The smaller filter has been bypassed so all flow is going through only the larger filter. Are now exceeding allowable flow rate through the larger filter. Smaller filter needs to be repaired and handling enough of the flow so 12.5gpm/sq.ft is not being exceeded through either filter.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Skimmer valve to circulation pump is not fully open. Keep fully open to maximize water remove from the pool through the skimmers.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- There is no clock visible in the pool area to whirlpool users.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Flow meter for the jets were not working.Repair/replace flow meters so they are functional and accurate.Some of the weirs were missing from the skimmers. To be replaced.Some of the weirs were stuck in place. Please ensure all weirs are working properly.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
5 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample taken and dropped off at lab on March 29/24 when it was closed (for stat holiday) so sample was not tested. Resample to be submitted.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The smaller filter has been bypassed so all flow is going through only the larger filter. Are now exceeding allowable flow rate through the larger filter. Smaller filter needs to be repaired and handling enough of the flow so 12.5gpm/sq.ft is not being exceeded through either filter.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Skimmer valve to circulation pump is not fully open. Keep fully open to maximize water remove from the pool through the skimmers.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- There is no clock visible in the pool area to whirlpool users.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Flow meter for the jets were not working.Repair/replace flow meters so they are functional and accurate.Some of the weirs were missing from the skimmers. To be replaced.Some of the weirs were stuck in place. Please ensure all weirs are working properly.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
4 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Skimmer valve to circulation pump is not fully open. Keep fully open to maximize water remove from the pool through the skimmers.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The smaller filter has been bypassed so all flow is going through only the larger filter. Are now exceeding allowable flow rate through the larger filter. Smaller filter needs to be repaired and handling enough of the flow so 12.5gpm/sq.ft is not being exceeded through either filter.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- There is no clock visible in the pool area to whirlpool users.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Flow meter for the jets were not working.Repair/replace flow meters so they are functional and accurate.Some of the weirs were missing from the skimmers. To be replaced.Some of the weirs were stuck in place. Please ensure all weirs are working properly.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
5 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Jan. 5/24 water sample had Pseudomonas isolated. Treat water to remove contamination.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Jan 5/24 water sample had a plate count of 620 cfu/ml. Treat water to remove contamination.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow meter for overall system flow rate was not working. Could not determine the flow rate for the pool.
- 08. Does food preparation and consumption take place away from the pool?
- People were consuming pop/coffee while sitting in the whirlpool. A staff advised them this was not allowed at time of inspection but strongly recommend signage be installed advising guests of this. Can have a designated/marked off area for consumption of food/beverages but are not to be consumed while in the pool.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Overall flow meter for the system was not working.Flow meter for the jets were also not working.Repair/replace flow meters so they are functional and accurate.One of the weirs was missing from skimmer (one next to outside stairs into whirlpool). To be replaced.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Nov.2/23 water sample was not tested as there was no id# on the bottle. Please resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow meter for overall system flow rate was not working. Could not determine the flow rate for the pool.
- 08. Does food preparation and consumption take place away from the pool?
- People were consuming pop/coffee while sitting in the whirlpool. A staff advised them this was not allowed at time of inspection but strongly recommend signage be installed advising guests of this. Can have a designated/marked off area for consumption of food/beverages but are not to be consumed while in the pool.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Overall flow meter for the system was not working.Flow meter for the jets were also not working.Repair/replace flow meters so they are functional and accurate.One of the weirs was missing from skimmer (one next to outside stairs into whirlpool). To be replaced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample taken Aug. 29/23 was not tested as there was no time of collection on the form. Resample needed.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow meter for overall system flow rate was not working. Could not determine the flow rate for the pool.
- 08. Does food preparation and consumption take place away from the pool?
- People were consuming pop/coffee while sitting in the whirlpool. A staff advised them this was not allowed at time of inspection but strongly recommend signage be installed advising guests of this. Can have a designated/marked off area for consumption of food/beverages but are not to be consumed while in the pool.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Overall flow meter for the system was not working.Flow meter for the jets were also not working.Repair/replace flow meters so they are functional and accurate.One of the weirs was missing from skimmer (one next to outside stairs into whirlpool). To be replaced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?