Quality Inn & Suites - Swimming Pool
11710 102 Street Grande Prairie AB T8V 7S7 · Aquatic Facility
14 inspections
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Results of water sample collected on May 20, 2026:HPC: 150 cfu /100 mlEnsure HPC count is no more than 100 cfu/100 mL. Shock chlorinate the pool water, balance the pool water chemistry and then re-submit a water sample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- One step on the stairwell leading to the slide has a small area of damage.Ensure the damaged section is repaired promptly to maintain safety and prevent potential injuries.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Risk Management Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Results of water sample collected on August 6, 2025:HPC: 170 cfu /100 mlEnsure HPC count is no more than 100 cfu/100 mL. Shock chlorinate the pool water, balance the pool water chemistry and then re-submit a water sample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Results of water sample collected on August 6, 2025:HPC: 170 cfu /100 mlEnsure HPC count is no more than 100 cfu/100 mL. Shock chlorinate the pool water, balance the pool water chemistry and then re-submit a water sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- REPEAT - The turnover period for the swimming pool is unsatisfactory- The pool volume was noted as 19412 gallons and the flow rate was measured at 76.7 gallons per minute. This equals a 4.22 hour turnover time.ENSURE THE SWIMMING POOL HAS A TURNOVER PERIOD OF 4 HOURS OR LESS
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Results of water sample collected on July 30, 2025:HPC: 150 cfu /100 mlEnsure HPC count is no more than 100 cfu/100 mL. Shock chlorinate the pool water, balance the pool water chemistry and then re-submit a water sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- REPEAT - The turnover period for the swimming pool is unsatisfactory- The pool volume was noted as 19412 gallons and the flow rate was measured at 76.7 gallons per minute. This equals a 4.22 hour turnover time.ENSURE THE SWIMMING POOL HAS A TURNOVER PERIOD OF 4 HOURS OR LESS
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Results of water sample collected on July 2, 2025:HPC: 1030 cfu/100 mlEnsure HPC count is no more than 100 cfu/100 mL. Shock chlorinate the pool water, balance the pool water chemistry and then re-submit a water sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- REPEAT - The turnover period for the swimming pool is unsatisfactory- The pool volume was noted as 19412 gallons and the flow rate was measured at 76.7 gallons per minute. This equals a 4.22 hour turnover time.ENSURE THE SWIMMING POOL HAS A TURNOVER PERIOD OF 4 HOURS OR LESS
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- REPEAT - The turnover period for the swimming pool is unsatisfactory- The pool volume was noted as 19412 gallons and the flow rate was measured at 76.7 gallons per minute. This equals a 4.22 hour turnover time.ENSURE THE SWIMMING POOL HAS A TURNOVER PERIOD OF 4 HOURS OR LESS
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC: 150 CFU/mLEnsure HPC count is less than 100 CFU/mL.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- REPEAT - The turnover period for the swimming pool is unsatisfactory- The pool volume was noted as 19412 gallons and the flow rate was measured at 76.7 gallons per minute. This equals a 4.22 hour turnover time.ENSURE THE SWIMMING POOL HAS A TURNOVER PERIOD OF 4 HOURS OR LESS
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC: 290 CFU/mLEnsure HPC count is less than 100 CFU/mL.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- REPEAT - The turnover period for the swimming pool is unsatisfactory- The pool volume was noted as 19412 gallons and the flow rate was measured at 76.7 gallons per minute. This equals a 4.22 hour turnover time.ENSURE THE SWIMMING POOL HAS A TURNOVER PERIOD OF 4 HOURS OR LESS
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- REPEAT - The turnover period for the swimming pool is unsatisfactory- The pool volume was noted as 19412 gallons and the flow rate was measured at 76.7 gallons per minute. This equals a 4.22 hour turnover time.ENSURE THE SWIMMING POOL HAS A TURNOVER PERIOD OF 4 HOURS OR LESS
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory Laboratory result received June 17, 2024: HPC 230 CFU/ml.Please submit a resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- REPEAT - The turnover period for the swimming pool is unsatisfactory- The pool volume was noted as 19412 gallons and the flow rate was measured at 76.7 gallons per minute. This equals a 4.22 hour turnover time.ENSURE THE SWIMMING POOL HAS A TURNOVER PERIOD OF 4 HOURS OR LESS
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water results are unsatisfactory:- HPC 520 cfu/mLEnsure all water parameters is balanced and maintained and; samples are submitted as soon as possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- REPEAT - The turnover period for the swimming pool is unsatisfactory- The pool volume was noted as 19412 gallons and the flow rate was measured at 76.7 gallons per minute. This equals a 4.22 hour turnover time.ENSURE THE SWIMMING POOL HAS A TURNOVER PERIOD OF 4 HOURS OR LESS
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?