Quality Inn & Suites - Swimming Pool

11710 102 Street Grande Prairie AB T8V 7S7 · Aquatic Facility

Inspection summary

Quality Inn & Suites - Swimming Pool has been inspected 17 times by Alberta Health Services (Environmental Public Health) since June 17, 2024. The most recent inspection, on September 8, 2026, found no infractions.

4 of 17 inspections on record found no infractions at all. In the past 12 months there were 7 inspections with 4 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality and Food temperature control.

Recent inspections have recorded fewer infractions than earlier ones, so the record is improving.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded 18 times across 12 separate inspections, most recently on August 28, 2026. For example: Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?

  • Food temperature controlHigher risk

    Inspectors check that anything that has to be kept at a set temperature, such as chilled or hot food, or equipment like sterilizers, stays in its safe range and that accurate thermometers are on hand. With food, temperature problems are one of the most common causes of food poisoning.

    Recorded once on January 13, 2026. For example: Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?

About this data

These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

17 inspections

  1. Risk Management Inspection

    0 infractions

  2. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 8/28. The bacterial water sample submitted on August 27th was not processed.- The sample collection date/time indicated on the requisition form was after the date/time the sample was submitted.
  3. Risk Management Inspection

    0 infractions

  4. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 7/20. The bacterial water sample submitted on July 16th was unsatisfactory. - TC: Absent-HPC: 210 CFU/mL. The pool had been closed for renovations in the ceiling of the aquatic facility. Treat as necessary and resample. Results of water sample collected on May 20, 2026:HPC: 150 cfu /100 mlEnsure HPC count is no more than 100 cfu/100 mL. Shock chlorinate the pool water, balance the pool water chemistry and then re-submit a water sample.
  5. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Results of water sample collected on May 20, 2026:HPC: 150 cfu /100 mlEnsure HPC count is no more than 100 cfu/100 mL. Shock chlorinate the pool water, balance the pool water chemistry and then re-submit a water sample.
  6. Risk Management Inspection

    0 infractions

  7. Monitoring Inspection

    1 infraction

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • One step on the stairwell leading to the slide has a small area of damage.Ensure the damaged section is repaired promptly to maintain safety and prevent potential injuries.
  8. Risk Management Inspection

    0 infractions

  9. Risk Management Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Results of water sample collected on August 6, 2025:HPC: 170 cfu /100 mlEnsure HPC count is no more than 100 cfu/100 mL. Shock chlorinate the pool water, balance the pool water chemistry and then re-submit a water sample.
  10. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Results of water sample collected on August 6, 2025:HPC: 170 cfu /100 mlEnsure HPC count is no more than 100 cfu/100 mL. Shock chlorinate the pool water, balance the pool water chemistry and then re-submit a water sample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • REPEAT - The turnover period for the swimming pool is unsatisfactory- The pool volume was noted as 19412 gallons and the flow rate was measured at 76.7 gallons per minute. This equals a 4.22 hour turnover time.ENSURE THE SWIMMING POOL HAS A TURNOVER PERIOD OF 4 HOURS OR LESS
  11. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Results of water sample collected on July 30, 2025:HPC: 150 cfu /100 mlEnsure HPC count is no more than 100 cfu/100 mL. Shock chlorinate the pool water, balance the pool water chemistry and then re-submit a water sample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • REPEAT - The turnover period for the swimming pool is unsatisfactory- The pool volume was noted as 19412 gallons and the flow rate was measured at 76.7 gallons per minute. This equals a 4.22 hour turnover time.ENSURE THE SWIMMING POOL HAS A TURNOVER PERIOD OF 4 HOURS OR LESS
  12. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Results of water sample collected on July 2, 2025:HPC: 1030 cfu/100 mlEnsure HPC count is no more than 100 cfu/100 mL. Shock chlorinate the pool water, balance the pool water chemistry and then re-submit a water sample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • REPEAT - The turnover period for the swimming pool is unsatisfactory- The pool volume was noted as 19412 gallons and the flow rate was measured at 76.7 gallons per minute. This equals a 4.22 hour turnover time.ENSURE THE SWIMMING POOL HAS A TURNOVER PERIOD OF 4 HOURS OR LESS
  13. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • REPEAT - The turnover period for the swimming pool is unsatisfactory- The pool volume was noted as 19412 gallons and the flow rate was measured at 76.7 gallons per minute. This equals a 4.22 hour turnover time.ENSURE THE SWIMMING POOL HAS A TURNOVER PERIOD OF 4 HOURS OR LESS
  14. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC: 150 CFU/mLEnsure HPC count is less than 100 CFU/mL.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • REPEAT - The turnover period for the swimming pool is unsatisfactory- The pool volume was noted as 19412 gallons and the flow rate was measured at 76.7 gallons per minute. This equals a 4.22 hour turnover time.ENSURE THE SWIMMING POOL HAS A TURNOVER PERIOD OF 4 HOURS OR LESS
  15. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC: 290 CFU/mLEnsure HPC count is less than 100 CFU/mL.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • REPEAT - The turnover period for the swimming pool is unsatisfactory- The pool volume was noted as 19412 gallons and the flow rate was measured at 76.7 gallons per minute. This equals a 4.22 hour turnover time.ENSURE THE SWIMMING POOL HAS A TURNOVER PERIOD OF 4 HOURS OR LESS
  16. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • REPEAT - The turnover period for the swimming pool is unsatisfactory- The pool volume was noted as 19412 gallons and the flow rate was measured at 76.7 gallons per minute. This equals a 4.22 hour turnover time.ENSURE THE SWIMMING POOL HAS A TURNOVER PERIOD OF 4 HOURS OR LESS
  17. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Unsatisfactory Laboratory result received June 17, 2024: HPC 230 CFU/ml.Please submit a resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • REPEAT - The turnover period for the swimming pool is unsatisfactory- The pool volume was noted as 19412 gallons and the flow rate was measured at 76.7 gallons per minute. This equals a 4.22 hour turnover time.ENSURE THE SWIMMING POOL HAS A TURNOVER PERIOD OF 4 HOURS OR LESS