Skip to content
Loading map…

Raymond Shores RV Resort - Whirlpool

SW 13-42-01 W5 Ponoka County AB · Aquatic Facility

7 inspections

  1. Monitoring Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Initial readings observed for total alkalinity were 36 mg/L and 31 mg/L. The operator was notified, and the alkalinity was corrected. Final reading for alkalinity after correction is 138 mg/L
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti -Entrapment plan is not current. Submerged suction outlet covers are expired (2024-06-01).Please ensure submerged suction outlet covers are replaced and a new anti-entrapment plan is created.
  2. Risk Management Inspection

    0 infractions

  3. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Unsatisfactory water sample results.Date collected: 06/08/2024Total coliforms = AbsentPsuedomonas aeruginosa = IsolatedHeterotrophic Plate Count = 60 CFU/mL
  4. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Unsatisfactory water sample results.Date collected: 23/07/2024Total coliforms = AbsentPsuedomonas aeruginosa = IsolatedHeterotrophic Plate Count = 30 CFU/mL
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Observed Flow - 50gpm1520 gals / 50 gpm = 30.4 minsPlease ensure that turnover is 20 minutes or less.
  5. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Observed Flow - 50gpm1520 gals / 50 gpm = 30.4 minsPlease ensure that turnover is 20 minutes or less.
  6. Monitoring Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Unsatisfactory water sample received.Total coliforms - PRESENTPseudomonas - ISOLATEDSample collected on June 11, 2024.ACTION: Please treat for Pseudomonas as outlined in the document below. Resample after treatment.https://www.albertahealthservices.ca/assets/wf/eph/wf-eh-pseudomona-in-hot-tubs.pdf
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Observed Flow - 50gpm1520 gals / 50 gpm = 30.4 minsPlease ensure that turnover is 20 minutes or less.
  7. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Unsatisfactory water sample received.Total coliforms - PRESENTPseudomonas - ISOLATEDSample collected on June 11, 2024.ACTION: Please treat for Pseudomonas as outlined in the document below. Resample after treatment.https://www.albertahealthservices.ca/assets/wf/eph/wf-eh-pseudomona-in-hot-tubs.pdf