Richardson Pioneer Central Peace Aquatic Centre - Pool
4812 44 Avenue Spirit River AB T0H 3G0 · Aquatic Facility
11 inspections
- Risk Management Inspection
0 infractions
- Demand Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 6/8/2026. The flow meters were not working. Repair/replace flow meters.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- 6/8/2026. There was algae observed throughout the pool basin. Clean pool basin and ensure chlorine is at or above the minimum required concentration.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
1 infraction
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Cyanuric acid was found to be 0 mg/L at the time of inspection.The testing equipment currently in use has faded markings, making accurate readings difficult.Staff was instructed to add more Cyanuric acid.Please ensure the following as per regulation:Where cyanuric acid is used in an outdoor public swimming pool, the concentration:a) must not exceed 50 mg/L, andb) must be measured and recorded at least once per week.Replace the testing equipment to ensure clear and accurate measurements.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- During the inspection, it was observed that the pool ladder rail is wobbling. Ensure that the pool ladder rail is securely fastened at both the pool-end (in the water) and the ground-end (outside the pool). All connection points must be tightened and stabilized to prevent movement or instability.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Monitoring Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- No gauge was avalible for 2nd sand filter. Ensure that a pressure gauge is installed for both the water inlet and outlet of the second sand filter, or directly on the sand filter itself. The pressure gauges must be functional and clearly readable. Backwashing of the filter should be conducted when the pressure differential between the inlet gauge and the outlet gauge reaches 10–15 psi.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- During the inspection, it was observed that the pool ladder rail is wobbling. Ensure that the pool ladder rail is securely fastened at both the pool-end (in the water) and the ground-end (outside the pool). All connection points must be tightened and stabilized to prevent movement or instability.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- AT TIME OF RE-INSPECTION:1. ONE SKIMMER / SKIMMING DEVICE (LOCATED CLOSE TO THE TWO SLIDES) WAS NOT IN GOOD WORKING CONDITION.THE OWNER / OPERATOR OF THIS FACILITY IS REQUESTED TO CONDUCT THE FOLLOWING, NAMELY:1. IMMEDIATELY DEVISE A WORK ORDER TO ENSURE SITE FACILITIES MAINTENANCE CONDUCTS AN INSPECTION OF THIS SKIMMING DEVICE AND MAKES ANY NECESSARY REPAIRS TO ENSURE IT OPERATES PROPERLY.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water Result(s);Total Coliforms: PresentWater result is unsatisfactory. Resubmit another sample after pool water chemistry has been balanced.*****AT TIME OF RE-INSPECTION, THE OPERATOR OF THIS POOL IS PLANNING TO SUBMIT A MICROBIOLOGICAL WATER SAMPLE ON WEDNESDAY, MAY 29, 2024. THIS SAMPLE RESULT WILL THEREFORE BE PENDING.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC: 550 CFU/mL HPC is greater than 100 CFU/mL. Operator was instructed to monitor the cyanuric acid & combined chlorine levels. The pool will have to be shocked chlorinated if the HPC numbers increase from the next sample result.May 23, 2024: Facility closed for the season so resample was not submitted. Water sample will be submitted for 2024 season before opening. Results pending. May 28, 2024HPC : >57,000 CFU/mL*****AT TIME OF RE-INSPECTION, THE OPERATOR OF THIS POOL IS PLANNING TO SUBMIT A MICROBIOLOGICAL WATER SAMPLE ON WEDNESDAY, MAY 29, 2024. THIS SAMPLE RESULT WILL THEREFORE BE PENDING.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Free Chlorine: 10 ppmTotal Chlorine: 10 ppmpH: 7.0Cyanuric Acid: 55 ppmOperator stated that pool water was super-chlorinated and water chemistry has not been balanced. Ensure pool remains closed until water chemistry is balanced and a satisfactory water result is obtained. Follow-up by PHI is required. ****AT TIME OF RE-INSPECTION, THE FOLLOWING PARAMETERS WERE NOTED:PH @ 7.0 (SATISFACTORY)FAC@ 5.0 PPM (HIGH)CYANURIC ACID @ 60 PPM (HIGH)PLEASE SCAN / SUBMIT (BY EMAIL) CHEMICAL PARAMETER RECORDS (TO THE ACTING AHS EXECUTIVE OFFICER) FOR TODAY (MAY 28, 2024) AND ONWARDS UNTIL FURTHER NOTICE - TO DETERMINE IF ALL PARAMETERS ARE FULLY BALANCED IN THE NEAR FUTURE.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- AT TIME OF RE-INSPECTION:1. ONE SKIMMER / SKIMMING DEVICE (LOCATED CLOSE TO THE TWO SLIDES) WAS NOT IN GOOD WORKING CONDITION.THE OWNER / OPERATOR OF THIS FACILITY IS REQUESTED TO CONDUCT THE FOLLOWING, NAMELY:1. IMMEDIATELY DEVISE A WORK ORDER TO ENSURE SITE FACILITIES MAINTENANCE CONDUCTS AN INSPECTION OF THIS SKIMMING DEVICE AND MAKES ANY NECESSARY REPAIRS TO ENSURE IT OPERATES PROPERLY.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water Result(s);Total Coliforms: PresentWater result is unsatisfactory. Resubmit another sample after pool water chemistry has been balanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC: 550 CFU/mL HPC is greater than 100 CFU/mL. Operator was instructed to monitor the cyanuric acid & combined chlorine levels. The pool will have to be shocked chlorinated if the HPC numbers increase from the next sample result.May 23, 2024: Facility closed for the season so resample was not submitted. Water sample will be submitted for 2024 season before opening. Results pending. May 28, 2024HPC : >57,000 CFU/mL
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Free Chlorine: 10 ppmTotal Chlorine: 10 ppmpH: 7.0Cyanuric Acid: 55 ppmOperator stated that pool water was super-chlorinated and water chemistry has not been balanced. Ensure pool remains closed until water chemistry is balanced and a satisfactory water result is obtained. Follow-up by PHI is required.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water Result(s);Total Coliforms: PresentWater result is unsatisfactory. Resubmit another sample after pool water chemistry has been balanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC: 550 CFU/mL HPC is greater than 100 CFU/mL. Operator was instructed to monitor the cyanuric acid & combined chlorine levels. The pool will have to be shocked chlorinated if the HPC numbers increase from the next sample result.May23, 2024: Facility closed for the season so resample was not submitted. Water sample will be submitted for 2024 season before opening. Results pending.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Free Chlorine: 10 ppmTotal Chlorine: 10 ppmpH: 7.0Cyanuric Acid: 55 ppmOperator stated that pool water was super-chlorinated and water chemistry has not been balanced. Ensure pool remains closed until water chemistry is balanced and a satisfactory water result is obtained. Follow-up by PHI is required.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC: 550 CFU/mL HPC is greater than 100 CFU/mL. Operator was instructed to monitor the cyanuric acid & combined chlorine levels. The pool will have to be shocked chlorinated if the HPC numbers increase from the next sample result.May23, 2024: Facility closed for the season so resample was not submitted. Water sample will be submitted for 2024 season before opening. Results pending.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Free Chlorine: 10 ppmTotal Chlorine: 10 ppmpH: 7.0Cyanuric Acid: 55 ppmOperator stated that pool water was super-chlorinated and water chemistry has not been balanced. Ensure pool remains closed until water chemistry is balanced and a satisfactory water result is obtained. Follow-up by PHI is required.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC: 550 CFU/mL HPC is greater than 100 CFU/mL. Operator was instructed to monitor the cyanuric acid & combined chlorine levels. The pool will have to be shocked chlorinated if the HPC numbers increase from the next sample result.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?