Rocky Mountain Ski Lodge - Whirlpool

1711 Bow Valley Trail Canmore AB T1W 1L7 · Aquatic Facility

13 inspections

  1. Monitoring Inspection

    1 infraction

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Some of the whirlpool basin floor tiles were missing.-Ensure basin are maintained in good repair.
  2. Risk Management Inspection

    1 infraction

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Some of the whirlpool basin floor tiles were missing.-Ensure basin are maintained in good repair.*Scheduled to be replaced in October*
  3. Demand Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity measured was less than 60ppm (53ppm).-Ensure total alkalinity is between 60-180ppm.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Some of the whirlpool basin floor tiles were missing.-Ensure basin are maintained in good repair.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • Operator certificate was not available onsite.-Ensure an operator certificate is available from an approved organization.
  4. Monitoring Inspection

    0 infractions

  5. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample received 7/26/2024 was not processed by the lab, date on the form indicated it was received more than 24 hrs. after collection. Operators were informed to submit a re-sample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • 1) Total Alkalinity was low, measured around 15 ppm. - Raise the alkalinity levels, ensure it is in the 60-180 range. 2) Combined chlorine was high at the time of the inspection. - Ensure combined chlorines are maintained as low as possible. Recommend draining some water and adding balanced water.
  6. Demand Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • 1) Total Alkalinity was low, measured around 15 ppm. - Raise the alkalinity levels, ensure it is in the 60-180 range. 2) Combined chlorine was high at the time of the inspection. - Ensure combined chlorines are maintained as low as possible. Recommend draining some water and adding balanced water.
  7. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample from Monday June 3rd, 2024, had an HPC of 20,000 CFU/mL. - Operators were informed to treat and re-sample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • 1) Total Alkalinity was low, measured around 15 ppm. - Raise the alkalinity levels, ensure it is in the 60-180 range. 2) Combined chlorine was high at the time of the inspection. - Ensure combined chlorines are maintained as low as possible. Recommend draining some water and adding balanced water.
  8. Demand Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • 1) Total Alkalinity was low, measured around 15 ppm. - Raise the alkalinity levels, ensure it is in the 60-180 range. 2) Combined chlorine was high at the time of the inspection. - Ensure combined chlorines are maintained as low as possible. Recommend draining some water and adding balanced water.
  9. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Pseudomonas was present in water sample from January 15th, 2023.- Operators are to treat and resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • 1) Total Alkalinity was low, measured around 15 ppm. - Raise the alkalinity levels, ensure it is in the 60-180 range. 2) Combined chlorine was high at the time of the inspection. - Ensure combined chlorines are maintained as low as possible. Recommend draining some water and adding balanced water.
  10. Demand Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • 1) Total Alkalinity was low, measured around 15 ppm. - Raise the alkalinity levels, ensure it is in the 60-180 range. 2) Combined chlorine was high at the time of the inspection. - Ensure combined chlorines are maintained as low as possible. Recommend draining some water and adding balanced water.
  11. Risk Management Inspection

    3 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • Chlorine was 0.05ppm at the time of inspection. Bucket of chlorine was empty, and operator replaced it, chlorine was very high at the end of the inspection >8ppm. -Recommend performing a pseudomonas disinfection.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • pH of the pool was 6.6 at the time of the inspection. - Operator was able to repair and raise pH to 7.4.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was very low at the time of inspection 12ppm. - Corrected and levels were raised to above 61ppm.
  12. Demand Inspection

    5 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Aug. 14/23 water sample had total coliforms isolated. Treat water to remove contamination and resample.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The anti-entrapment plans were reviewed. Plans indicated that the jet pump’s suction outlet covers have been expired since 2022. The covers looked intact during the inspection. Please replace the covers as soon as possible. It’s recommended to complete weekly physical checks of the covers each week to ensure they are still in good repair.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The anti-entrapment plans were reviewed. Plans indicated that the recirculation pump’s suction outlet covers have been expired since 2021. The covers looked intact during the inspection. Please replace the covers as soon as possible. It’s recommended to complete weekly physical checks of the covers each week to ensure they are still in good repair.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The anti-entrapment plans were reviewed. There is a potential anti-entrapment hazard with the recirculation system. The suction outlet covers are rated for a maximum flow of 123 gpm. The maximum flow rate for the recirculation pump is 135 gpm. The current flow rate is 118 gpm. The flow of the recirculation pump must be throttled back/ valve should be removed so that flow rate is operating between a min of 77 gpm and a max of 120 gpm. Please change the outlet covers so that the recirculation pump’s suction outlets are rated greater than the the pump’s maximum flow rate. Please update the anti-entrapment plan once covers are changed and submit it to EPH.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • One of the screws for the closest main drain cover (square one) was missing. Please replace.
  13. Monitoring Inspection

    7 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • FAC was measured at 1.29 ppm. Operator corrected the chlorine to 4.56 ppm onsite. Please ensure that a pool > 30C has a FAC level of at least 2 ppm.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • pH was measured at 6.7 and 6.6 ppm. Operator corrected the pH to 7.0 onsite. Please ensure that the pool is operating at a pH level between 6.8 and 7.6.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity measure Lo and Lo (<10 ppm). Operator correct the alkalinity to 60 ppm onsite. Please ensure that the pool is operating at an alkalinity level between 60-180 ppm.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The anti-entrapment plans were reviewed. Plans indicated that the jet pump’s suction outlet covers have been expired since 2022. The covers looked intact during the inspection. Please replace the covers as soon as possible. It’s recommended to complete weekly physical checks of the covers each week to ensure they are still in good repair.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The anti-entrapment plans were reviewed. Plans indicated that the recirculation pump’s suction outlet covers have been expired since 2021. The covers looked intact during the inspection. Please replace the covers as soon as possible. It’s recommended to complete weekly physical checks of the covers each week to ensure they are still in good repair.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The anti-entrapment plans were reviewed. There is a potential anti-entrapment hazard with the recirculation system. The suction outlet covers are rated for a maximum flow of 123 gpm. The maximum flow rate for the recirculation pump is 135 gpm. The current flow rate is 118 gpm. The flow of the recirculation pump must be throttled back/ valve should be removed so that flow rate is operating between a min of 77 gpm and a max of 120 gpm. Please change the outlet covers so that the recirculation pump’s suction outlets are rated greater than the the pump’s maximum flow rate. Please update the anti-entrapment plan once covers are changed and submit it to EPH.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • One of the screws for the closest main drain cover (square one) was missing. Please replace.