Skip to content
Loading map…

Saddletowne YMCA - Main Pool

7556 Falconridge Boulevard NE Calgary AB T3J 0C9 · Aquatic Facility

5 inspections

  1. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate for the pool is too slow and doesn't meet the minimum turnover requirements.REQUIREMENT: Increase the flow rate so that the flow is greater than 645 USGPM.Status: Outstanding.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • You can copy this or write your own:Anti-entrapment plan identified that drain cover expiry date was in 2020. Operator has evidence that the covers have been replaced since then, but the plan has not been updated.-Provide updated anti-entrapment plan
  2. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate for the pool is too slow and doesn't meet the minimum turnover requirements.REQUIREMENT: Increase the flow rate so that the flow is greater than 645 USGPM.
  3. Monitoring Inspection

    0 infractions

  4. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on December 22nd was not processed. According to the laboratory, the date/time of sample collection was later than the date and time of receipt. The date provided was December 23rd.REQUIREMENT: Ensure the correct date/time of collection is recorded on the requisition form.
  5. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on July 20, 2023, had HPC detected at 110 CFU/mL.REQUIREMENT: Please review the water chemistry for the pool and balance as needed. An immediate re-sample is not required for the main pool at this time.