Sandman Hotel - Whirlpool

888 7 Avenue SW Calgary AB T2P 3J3 · Aquatic Facility

16 inspections

  1. Risk Management Inspection

    0 infractions

  2. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample (26ES-139E00032) collected on May 19th, 2026, came back unsatisfactory as Pseudomonas aeruginosa was isolated in the sample. Please close the whirlpool, complete treatment, rebalance the water chemistry, and resample as soon as possible.
  3. Risk Management Inspection

    0 infractions

  4. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample (26ES-104E00639) collected on April 14th, 2026, came back unsatisfactory as pseudomonas aeruginosa were isolated in the sample. Please treat the whirlpool, rebalance the water, and resample immediately.
  5. Risk Management Inspection

    0 infractions

  6. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample (26ES-083E00647) collected on March 24th, 2026, came back unsatisfactory as total coliforms were present in the sample. Please treat the whirlpool, rebalance the water, and resample immediately.
  7. Risk Management Inspection

    0 infractions

  8. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample (25ES-308E00631) collected on November 4th, 2025, came back unsatisfactory as Pseudomonas aeruginosa was isolated in the sample. Please treat the hot tub and resample as soon as possible.
  9. Monitoring Inspection

    1 infraction

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The free chlorine was tested to be 1.16ppm at the time of the inspection. The whirlpool was currently being filled. The fill was stopped, and the chlorine was adjusted by the pool operator. The free chlorine was tested again later during the inspection to be 5.32.Please ensure the whirlpool free chlorine is mainatined at a level of at least 2.0ppm.
  10. Monitoring Inspection

    0 infractions

  11. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample taken Aug 13, 2024 - Pseudomonas isolated.-Treat and resample
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity reading was 35 mg/L.- Adjust the total alkalinity so that it is within the acceptable range of 60 to 180 mg/L.
  12. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample taken Aug 6, 2024 - Pseudomonas isolated.-Treat and resample
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity reading was 35 mg/L.- Adjust the total alkalinity so that it is within the acceptable range of 60 to 180 mg/L.
  13. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample taken Jun 18, 2024 - Pseudomonas isolated.-Treat and resample
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity reading was 35 mg/L.- Adjust the total alkalinity so that it is within the acceptable range of 60 to 180 mg/L.
  14. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Pseudomonas aeruginosa isolated.-Treat and re-sample
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity reading was 35 mg/L.- Adjust the total alkalinity so that it is within the acceptable range of 60 to 180 mg/L.
  15. Monitoring Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity reading was 35 mg/L.- Adjust the total alkalinity so that it is within the acceptable range of 60 to 180 mg/L.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Water level in hot tub was below the skimmer.-Ensure regular monitoring of the water level and prompt adjustment when low for effective debris removal
  16. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Pseudomonas isolated.-Treat and resample
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • VIOLATION NOTED: Total alkalinity measured 'LO'. The lowest concentration the testing equipment is able to measure is 10 mg/L, meaning the total alkalinity of the water is below 10 mg/L. COMPLETE THE FOLLOWING:Adjust the total alkalinity so that it is within the acceptable range of 60 to 180 mg/L.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • VIOLATION NOTED:Daily main drain checks are not recorded in the log. The template revised in Jan 2019 includes a section for drain covers, but the templates revised in May 2020 has the category removed. COMPLETE THE FOLLOWING:Prior to opening the pool for the day, the main drain cover must be inspected. Results of the inspectionmust be documented. Update the log to include a section for main drain cover checks.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • VIOLATED NOTED ON PREVIOUS REPORTS: Supervision and Safety Plan and Water Quality Incident Response Plan are incomplete. COMPLETE THE FOLLOWING: Complete the plans as per Sections 10 to 12 in the Pool Standards.