Sandman Hotel - Whirlpool

888 7 Avenue SW Calgary AB T2P 3J3 · Aquatic Facility

14 inspections

  1. Monitoring Inspection

    4 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorine (CC) was measured to be 2.88ppm. Please keep the CC as low was possible (at least under 1.0ppm) to reduce bather skin and mucous membrane irritation.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The manual testing indicated a free chlorine of 7.26ppm. The automated controller showed a reading of 2.94ppm. Please investigate the discrepancy between the manual testing and the automated readings and calibrate if needed.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The filtration rate was calculated to be 14.33 gpm/sqft The maximum rate of filtration for a high-rate sand filter must not be greater than 8.5 litres per second per square meter (12.5 US gallons per minute per square foot) for a whirlpool. Please reduce the flow of the system.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The anti-entrapment plan has not been updated with the new cover details. A copy of the AHS anti-entrapment plan template will be emailed along with this report. Please complete the plan and submit to the undersigned PHI for review.
  2. Risk Management Inspection

    0 infractions

  3. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample (26ES-139E00032) collected on May 19th, 2026, came back unsatisfactory as Pseudomonas aeruginosa was isolated in the sample. Please close the whirlpool, complete treatment, rebalance the water chemistry, and resample as soon as possible.
  4. Risk Management Inspection

    0 infractions

  5. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample (26ES-104E00639) collected on April 14th, 2026, came back unsatisfactory as pseudomonas aeruginosa were isolated in the sample. Please treat the whirlpool, rebalance the water, and resample immediately.
  6. Risk Management Inspection

    0 infractions

  7. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample (26ES-083E00647) collected on March 24th, 2026, came back unsatisfactory as total coliforms were present in the sample. Please treat the whirlpool, rebalance the water, and resample immediately.
  8. Risk Management Inspection

    0 infractions

  9. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample (25ES-308E00631) collected on November 4th, 2025, came back unsatisfactory as Pseudomonas aeruginosa was isolated in the sample. Please treat the hot tub and resample as soon as possible.
  10. Monitoring Inspection

    1 infraction

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The free chlorine was tested to be 1.16ppm at the time of the inspection. The whirlpool was currently being filled. The fill was stopped, and the chlorine was adjusted by the pool operator. The free chlorine was tested again later during the inspection to be 5.32.Please ensure the whirlpool free chlorine is mainatined at a level of at least 2.0ppm.
  11. Monitoring Inspection

    0 infractions

  12. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample taken Aug 13, 2024 - Pseudomonas isolated.-Treat and resample
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity reading was 35 mg/L.- Adjust the total alkalinity so that it is within the acceptable range of 60 to 180 mg/L.
  13. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample taken Aug 6, 2024 - Pseudomonas isolated.-Treat and resample
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity reading was 35 mg/L.- Adjust the total alkalinity so that it is within the acceptable range of 60 to 180 mg/L.
  14. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample taken Jun 18, 2024 - Pseudomonas isolated.-Treat and resample
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity reading was 35 mg/L.- Adjust the total alkalinity so that it is within the acceptable range of 60 to 180 mg/L.