Sandman Signature Hotel Edmonton South - Whirlpool

10111 Ellerslie Road SW Edmonton AB T6X 0J3 · Aquatic Facility

21 inspections

  1. Risk Management Inspection

    0 infractions

  2. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample submitted on 4 June 2026 was unsatisfactory: Pseudomonas aeruginosa isolated, Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
  3. Risk Management Inspection

    0 infractions

  4. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample result collected on April 2, 2026 and April 9, 2026 was unsatisfactory: Pseudomonas aeruginosa isolated. Operator confirmed that the chemical feed pump for chlorine was malfunctioning and requires replacement. The pool has been closed until chemical feed pump has been replaced and a satisfactory microbiological result is received.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample result collected on April 2, 2026 and Apeil 9, 2026 was unsatisfactory: HPC >100 CFU/mL. Operator confirmed that the chemical feed pump for chlorine was malfunctioning and requires replacement. The pool has been closed until chemical feed pump has been replaced and a satisfactory microbiological result is received.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Maintenance manager noted that the pH probe for the controller required replacing as it was found to be causing erroneous readings that lead to the chemical controller overfeeding during the weekend. Operators have since installed a new pH probe and corrected the issue with the system.* Flow switch was not working at time of inspection when the flow to the flow cell was turned off. Clean or replace the flow switch so that chemical feed does not occur when flow to the system is stopped.
  5. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample result collected on April 2, 2026, was unsatisfactory: Pseudomonas aeruginosa isolated. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample result collected on April 2, 2026, was unsatisfactory: HPC >100 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Maintenance manager noted that the pH probe for the controller required replacing as it was found to be causing erroneous readings that lead to the chemical controller overfeeding during the weekend. Operators have since installed a new pH probe and corrected the issue with the system.* Flow switch was not working at time of inspection when the flow to the flow cell was turned off. Clean or replace the flow switch so that chemical feed does not occur when flow to the system is stopped.
  6. Demand Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Maintenance manager noted that the pH probe for the controller required replacing as it was found to be causing erroneous readings that lead to the chemical controller overfeeding during the weekend. Operators have since installed a new pH probe and corrected the issue with the system.* Flow switch was not working at time of inspection when the flow to the flow cell was turned off. Clean or replace the flow switch so that chemical feed does not occur when flow to the system is stopped.
  7. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample submitted on 26 Feb 2026 was unsatisfactory: HPC 1810 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Jet eyelet fitting on the upper south wall by the steps is missing. Replace the missing jet eyelet fitting.
  8. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample submitted on 19 Feb 2026 was unsatisfactory: Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Jet eyelet fitting on the upper south wall by the steps is missing. Replace the missing jet eyelet fitting.
  9. Risk Management Inspection

    1 infraction

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Jet eyelet fitting on the upper south wall by the steps is missing. Replace the missing jet eyelet fitting.
  10. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample submitted on 11/12/2025 was unsatisfactory: Pseudomonas aeruginosa isolated, Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Jet eyelet fitting on the upper south wall by the steps is missing. Replace the missing jet eyelet fitting.
  11. Monitoring Inspection

    1 infraction

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Jet eyelet fitting on the upper south wall by the steps is missing. Replace the missing jet eyelet fitting.
  12. Risk Management Inspection

    0 infractions

  13. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample submitted on 25 Sept 2025 was unsatisfactory: Pseudomonas aeruginosa isolated, Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample submitted on 25 Sept 2025 was unsatisfactory: HPC >57000 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
  14. Risk Management Inspection

    0 infractions

  15. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample result collected on 31/07/2025 [25EN-212E00649] was unsatisfactory: Pseudomonas aeruginosa isolated. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
  16. Risk Management Inspection

    0 infractions

  17. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample submitted on 24 April 2025 was unsatisfactory: Pseudomonas aeruginosa isolated, Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample submitted on 24 April 2025 was unsatisfactory: HPC >57000 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The circulation pump has been replaced with a larger pump than on the last submitted anti-entrapment report. Ensure the anti-entrapment report is updated to reflect the correct pump and maximum flow rate.
  18. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The circulation pump has been replaced with a larger pump than on the last submitted anti-entrapment report. Ensure the anti-entrapment report is updated to reflect the correct pump and maximum flow rate.
  19. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample submitted on 19 Sept 2024 was unsatisfactory: HPC 650 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The circulation pump has been replaced with a larger pump than on the last submitted anti-entrapment report. Ensure the anti-entrapment report is updated to reflect the correct pump and maximum flow rate.
  20. Monitoring Inspection

    3 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • Records indicate that one of the days the free chlorine was noted at <1.0ppm. Chemical addition and controller adjustments were completed however a follow up chemical test to confirm chlorine concentration was not done. Ensure free chlorine test is done after a chemical addition.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow rate was noted at slightly above 100 GPM. Due to filter size flow cannot exceed 90 GPM. Operator adjusted flow to just below 90 GPM.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The circulation pump has been replaced with a larger pump than on the last submitted anti-entrapment report. Ensure the anti-entrapment report is updated to reflect the correct pump and maximum flow rate.
  21. Risk Management Inspection

    0 infractions