Sandman Signature Sherwood Park Hotel - Whirlpool

901 Pembina Road Sherwood Park AB T8H 0Y7 · Aquatic Facility

27 inspections

  1. Risk Management Inspection

    2 infractions

    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • Clock was not available for use for those in the whirlpool. Install a working clock that is visible from the whirlpool.\Emergency phone was not in working condition.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Operator did not have written policies plans available to review. Operator discussed he'd liek to work on this. PHI will email templates for operator to fill out. The following is required-- Written policies - General Sanitation Plan- Written policies - Safety and Supervision Plan - Written policies - Water Quality Incident Response PlanPosted rules and safety information was observed.It is confirmed that we have the whirlpool anti-entrapment plan from 2023, and operator indicates it is up to date as per their discussion with automated aquatics.
  2. Monitoring Inspection

    3 infractions

    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • Temperature of Whirpool was at 42C. This is too hot and is a safety hazard. Operator voluntarily closed pool.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • Clock was not available for use for those in the whirlpool. Install a working clock that is visible from the whirlpool.\Emergency phone was not in working condition.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Operator did not have written policies plans available to review. Operator discussed he'd liek to work on this. PHI will email templates for operator to fill out. The following is required-- Written policies - General Sanitation Plan- Written policies - Safety and Supervision Plan - Written policies - Water Quality Incident Response PlanPosted rules and safety information was observed.It is confirmed that we have the whirlpool anti-entrapment plan from 2023, and operator indicates it is up to date as per their discussion with automated aquatics.
  3. Risk Management Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Pseudomonas Aeruginosa isolated. Clean and resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • CC at 1.11 mg/L Combined chlorine should be maintained as low as possible. If greater than 1.0 ppm it is recommended to shock chlorinate the pool.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • Clock was not available for use for those in the whirlpool. Install a working clock that is visible from the whirlpool.\Emergency phone was not in working condition.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Operator did not have written policies plans available to review. Operator discussed he'd liek to work on this. PHI will email templates for operator to fill out. The following is required-- Written policies - General Sanitation Plan- Written policies - Safety and Supervision Plan - Written policies - Water Quality Incident Response PlanPosted rules and safety information was observed.It is confirmed that we have the whirlpool anti-entrapment plan from 2023, and operator indicates it is up to date as per their discussion with automated aquatics.
  4. Risk Management Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • CC at 1.11 mg/L Combined chlorine should be maintained as low as possible. If greater than 1.0 ppm it is recommended to shock chlorinate the pool.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • Clock was not available for use for those in the whirlpool. Install a working clock that is visible from the whirlpool.\Emergency phone was not in working condition.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Operator did not have written policies plans available to review. Operator discussed he'd liek to work on this. PHI will email templates for operator to fill out. The following is required-- Written policies - General Sanitation Plan- Written policies - Safety and Supervision Plan - Written policies - Water Quality Incident Response PlanPosted rules and safety information was observed.It is confirmed that we have the whirlpool anti-entrapment plan from 2023, and operator indicates it is up to date as per their discussion with automated aquatics.
  5. Monitoring Inspection

    5 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Pseudomonas Aeruginosa isolated.Superchlorinate the hot tub and then resample.Jan 30, 2026 - waiting on water sample
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Heterotrophic Plate Count 310
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • CC at 1.11 mg/L Combined chlorine should be maintained as low as possible. If greater than 1.0 ppm it is recommended to shock chlorinate the pool.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • Clock was not available for use for those in the whirlpool. Install a working clock that is visible from the whirlpool.\Emergency phone was not in working condition.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Operator did not have written policies plans available to review. Operator discussed he'd liek to work on this. PHI will email templates for operator to fill out. The following is required-- Anti-entrapment plan- Written policies - General Sanitation Plan- Written policies - Safety and Supervision Plan - Written policies - Water Quality Incident Response PlanPosted rules and safety information was observed.Note - we have the whirlpool anti-entrapment plan from 2023, however if your main drains covers have been changed out this will need to be updated on the plan.
  6. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Pseudomonas Aeruginosa isolated.Superchlorinate the hot tub and then resample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Heterotrophic Plate Count 310
  7. Monitoring Inspection

    0 infractions

  8. Demand Inspection

    0 infractions

  9. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Pseudomonas Aeruginosa isolated.Superchlorinate the hot tub and then resample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Heterotrophic plate count of 1860.
  10. Monitoring Inspection

    0 infractions

  11. Demand Inspection

    1 infraction

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Floating weirs or floating baskets are not available at either of the swimming pools skimmer inlets.
  12. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Sample from March 27, 2024 is positive for pseudomonas aeruginosa and total coliforms. Operator indicates pool was drained, scrubbed, backwashed and re-balanced prior to the sample just being taken. Recommend to follow shock chlorination procedures again and pay attention to scrubbing biofilm. Operator indicates they will shock chlorinate today and re-sample tomorrow. Let operator know if next sample fails, it would lead to hot tub closure.
  13. Risk Management Inspection

    0 infractions

  14. Monitoring Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity was measured to be 23ppm. Raise the total alkalinity such that it is between the required concentration of 60 and 180ppm.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorine was measured to be 5.44 and 4.09ppm. Reduce the combined chlorine to be below 1.0ppm to maximize bather comfort.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Several debris items were observed in the skimmer baskets. Clean the skimmer baskets.
  15. Risk Management Inspection

    0 infractions

  16. Demand Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine was measured to be 2.20ppm. Decrease the combined chlorine and maintain it under 1.0ppm to maximize bather comfort.
  17. Risk Management Inspection

    0 infractions

  18. Risk Management Inspection

    0 infractions

  19. Risk Management Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • January 9, 2024 water sample.Pseudomonas aeruginosa isolated.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine was measured to be 1.45ppm on January 10 and 1.37ppm on January 11. Decrease the combined chlorine and maintain it to be under 1.0ppm to maximize bather comfort.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Chlorine concentration in the pool was measured to be approximately 25ppm using chlorine test strips. Reduce the chlorine concentration such that it is between 2.0ppm and 4.0ppm.
  20. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • January 9, 2024 water sample.Pseudomonas aeruginosa isolated.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine was measured to be 1.45ppm on January 10 and 1.37ppm on January 11. Decrease the combined chlorine and maintain it to be under 1.0ppm to maximize bather comfort.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured to be 33ppm on January 10 and 32ppm on January 11. Increase the alkalinity and maintain it between 60 and 180ppm
  21. Risk Management Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine was measured to be 1.45ppm on January 10 and 1.37ppm on January 11. Decrease the combined chlorine and maintain it to be under 1.0ppm to maximize bather comfort.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured to be 33ppm on January 10 and 32ppm on January 11. Increase the alkalinity and maintain it between 60 and 180ppm
  22. Demand Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine was measured to be 1.45ppm. Decrease the combined chlorine and maintain it to be under 1.0ppm to maximize bather comfort.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured to be 33ppm. Increase the alkalinity and maintain it between 60 and 180ppm.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Water testing of the chemical parameters are not being completed daily. Testing is to be completed daily to ensure water quality.
  23. Risk Management Inspection

    0 infractions

  24. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • October 6, 2023 water sample.Pseudomonas aeruginosa isolated.
  25. Risk Management Inspection

    0 infractions

  26. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Pseudomonas aeruginosa isolated. August 22, 2023 sample date.
  27. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Pseudomonas aeruginosa isolated. August 22, 2023 sample date.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Total alkalinity = 37ppm**Maintain total alkalinity between 60-180 ppm.